HomeMy WebLinkAboutUse Modification Solar Project WHITMAN Corporate Headquarters Tel: 732.390.5858 ® Fax: 732.390.9496 7 Pleasant Hill Road www.whitmanco.com Cranbury, NJ 08512 September 25, 2015 Mr. Syed H. Rahman, P.E. New York State Department of Environmental Conservation Division of Materials Management, Region 1 SUNY @ Stony Brook 50 Circle Road Stony Brook,NY 11790 RE: Town of Southold Landfill Post-Closure Use Modification Solar Project Whitman Project No. 14-06-15T Dear Mr. Rahman: Whitman is in receipt of your July 24, 2015 comments letter for the two documents that were submitted on behalf of Sun Edison and the Town of Southold. The documents are Southold Landfill Engineering Report, and Southold Landfill Post Closure Report. Whitman has reviewed your comments and revised both reports as,well as prepared this response letter. Please find the following responses: Engineering Report 1.§ 1.2 Landfill Closure Design - The report states, "The landfill cap as designed and constructed is sufficient to support the planned solar system. " The report must provide the necessary load calculations to support this statement, including the maximum load the cap can withstand and the design load of the solar system in psi or psf. Response: Based on the load provided by RBI, the worst case scenario has the solar rack load at 300.5 lbs/sf. The cap is constructed of approximately 2.5 feet of compacted silty sand with up to 10 feet of compacted fill. The footing load decreases with the depth of the bearing strata. Using the footing width of 3.66 ft (width of ballast rack) the pressure of the foundation on the soil diminishes to approximately 156 lbs/sf at a depth of 4 feet and to approximately 91 lbs/sf at a depth of 8 ft. Creating Solutions. Exceeding Expectations. GIPROJECTS12011114-06-IST Sun Edison Southhold Landfill\Landfill Closure Reports\NYDEC Response Letterdoa Mr. Syed H.Rahman,P.E. New York State Department of Environmental Conservation September 25,2015 Page 2 Calculating the allowable bearing capacity of the cover soil and cap using the Terzaghi equation, results in an ultimate bearing capacity of approximately 5,032.5 lbs/sf and applying a factor of safety of 2.5 results in an allowable bearing capacity of 2,013 lbs/sf. Calculations are included in the report. 2.§ 1.3 Purpose and Scope - The report states, "All work associated with the installation of the solar panels will be conducted consistent with the revised Southold Landfill Post Closure Report. " The Department did not receive a Southold Landfill Post Closure Report. Did you mean to-reference the Southold Landfill Post Closure Plan?If so,please change all references in the report to consistently reference "Southold Landfill Post Closure Plan. " Response: Changes made in the Plan. 3.§2.0 Solar Farm - The report states, "the solar modules will be supported by 339 concrete ballast blocks which will be approximately 10'x 4'and weigh approximately 10,000 lbs. The concrete blocks will be placed on approximately 6" of gravel on top of the landfill barrier cap. " What is the third dimension that is missing from the block size? Are the blocks 10,000 lbs. each or is that the weight of all 339 blocks?Are the blocks poured in place or will these be pre-cast? What size and type of gravel is planned for this application? Response: The proposed blocks are designed to be 3'-8"w x 9'-6"1 x 2'-0" h, and will each have a weight of 10,450 lbs, (using and concrete weight of 150 pcf). The blocks will be..... Please refer to the design drawings as prepared by RBI Solar, dated 7/14/15, for layout, and design specifications. 4.§2.0 Solar Farm - The report states, "electrical equipment will be installed on a concrete slab of varying thickness, generally 10" or greater. The slabs will be placed on approximately 6" of gravel on top of the landfill barrier cap. " What are the other two missing dimensions for the concrete slabs?Are the slabs poured in place or will they be pre-cast? What size and type of gravel is planned for this application? Response: The proposed solar equipment, in particular the inverter, will be installed on a cast in place concrete slab with an overall size of 12'-9" w x 30'-9"1 x 12" thick. The gravel proposed is specified to be a minimum of 1-1/2" dense graded aggregate (QP- quarry process) stone. 5.§ 2.0 Solar Farm - Please provide the actual dimensions of the solar arrays. In addition, please clarify if in fact each row will consist of two rows of arrays. How does this impact the sustainability of the vegetative layer? NV Y WHITMAN G:\PROJECTS\2014\14.06-151 Sun Edison Southhold LandfilRlandfill Closure Reports\NYDEC Response Letter doa Mr. Syed H.Rahman,P.E. New York State Department of Environmental Conservation September 25,2015 Page 3 Response: The proposed solar arrays vary in overall size, but are approximately 600' x 175' in area. The design of the racking is a 2 module high in portrait orientation that is approximately 12'-4" in length, x the length of each row. The modules are tilted at a 20 degree pitch form horizontal,which should have minimal impact on the vegetative layer. In our experience if properly seeded and maintained any disturbed areas will sustain growth below to modules.As part of the agreement Sun Edison is required to maintain the site and vegetative growth is one requirement. 6.§2.0 Solar Farm -Please provide plans and cross section details of the solar farm which provide sufficient detail to understand the solar module design, support frames, combiner boxes, inverter/transformers, aluminum cable trays, rubber and concrete sleepers, ballast anchoring system, where electrical conduit will be positioned, etc. Response: Please find attached a set of preliminary construction drawings. 7.§ 2.0 Solar Farm - Will the electric conduit be installed under the ground surface or rest on the ground surface? How will the vegetation around the solar panels and electrical conduit be maintained? Response: The proposed electrical conduit will run above grade to avoid disturbance of the cap material. The proposed design calls for the conduits to be placed on industry standard recycled rubber supports similar to Eaton DURA-BLOK product (httn://www.cooperindustries.com/content/>public/en/b-line/brands/Dura-Blok.html), spacing and sizing of actual block to be finalized during final construction drawing preparation. A layer of gravel is proposed to be placed on geotextile weed block along the route of the conduits, to provide both a leveling surface, as well as a means to block weed growth between the conduits. The reaming areas of the array, around and under the arrays will be maintained with normal grass mowing operations, performed by Sun Edison's operation and maintenance sub contractors. 8.§2.0 Solar Farm - Will the geo-membrane cap be penetrated at any point? If so, provide details to explain how the integrity of the cap will be maintained. Response: The geo-membrane cap will not be penetrated by this installation. 9.§2.1 Methane Hazards- The report states, "air monitoring will be completed daily for the duration of the installation. " Who will be doing the air monitoring? How will the air monitoring be performed? What will happen if the air monitoring results indicate dangerous levels of methane? W WHITMAN G:\PROJECTS12014\I4-06-I5T Sun Edison Southhold Landfi111Landfill Closure Reports\NYDEC Response Letterdocx Mr. Syed H.Rahman,P.E. New York State Department of Environmental Conservation September 25,2015 Page 4 Response: The monitoring will be conducted by trained personnel. Details are in the Post Closure Plan. 10. § 2.2 Additional Load - The report states, "The existing conditions are sufficient to support the proposed load of the solar panels and associated equipment." The report must provide the necessary load calculations to support this statement, including the maximum load the cap can withstand and the design load of the solar system in psi or psf Response: Based on the load provided by RBI, the worst case scenario has the solar rack load at 300.5 lbs/sf. The cap is constructed of approximately 2.5 feet of compacted silty sand with up to 10 feet of compacted fill. The cap and fill layers should bridge over any localized soft spot in the underlying landfill material. 11. sr 2.3 Potential Settlements - The report states, "limited settling has occurred to date and potential settling is not anticipated" The report must provide the actual settling to date and the calculated anticipated settling that will occur during the life cycle of the solar farm. The report must also provide details of the solar farm design to accommodate the future settling. Response: As per the settlement analysis submitted with the Final Closure Plan prepared by Dvirka and Bartilucci, and Tectonic Engineering, the primary settlement occurs within the first year that the cap and fill are placed, and the secondary settlement will occur between years 1 and 50. The site has been capped for over 10 years, so the primary settlement has occurred and the landfill is approximately 20% through the secondary settlement phase. The Final Closure Plan presented settlement data for various landfill material thickness and various fill thickness with the cap. As per the report,the worst case (40 feet of landfill material with 10 feet of fill) for secondary settlement will be 2.72 feet. Thus it can be inferred that the landfill still has the potential to settle approximately 2.2 additional feet in certain areas. Under this assumption the 10 feet of fill material along with the 2.5 feet of cap material will impart a surcharge of approximately 1,400 lbs/sf on the landfill material. As calculated above, the ballast rack will add an additional 300 lbs/sf. However, in this scenario, the stresses in the soil from the ballast rack will diminish with depth and be negligible at approximately 8-10 feet below grade. The topographic survey shows a fairly uniform slope over the central part of the landfill suggesting that localized settlements have not occurred within the capped area. Regardless of the new loading, there will continue to be secondary settlement of the landfill and a maintenance plan to inspect the solar facility for settlements and repairs will be required. ®Y j WHITMAN G-1PROJECTS12014114-06-IST Sun Edison Southhold LandfllUandfill Closure ReportslNYDEC Response letterdocx Mr.Syed H.Rahman,P.E. New York State Department of Environmental Conservation September 25,2015 Page 5 12. §2.4 Wind Uplift- The report states, "The solar array racking system will be designed in accordance with International Building Code for the State of New York"Did you mean to reference the International Building Code (IBC) or the Building Code of New York State?Please clarify which code you planned to reference and why. Response: The solar array was designed based on the IBC 2009/2010 Building Code of New York State. Please refer to reference on RBI design drawings attached. 13. §2.4 Wind Uplift-Please provide wind uplift calculations to confirm that the solar panel ballast design is sufficient. Response: Please find attached the signed structural calculations from RBI solar. 14. §2.6 Side Slope Stability- The report states, "there are no slopes in excess of 20 percent associated with the landfill." The report must provide the necessary geotechnical information and slope stability calculations to support this statement, including any recent land surveys. Veneer failure calculations must be performed as part of the slope stability analysis. Response: By applying existing data from the Final Closure Plan prepared by Dvirka and Bartilucci, and Tectonic Engineering, along with several assumptions based on published literature, we were able to apply the Koerner and Hwu (1991) method to calculate the factor of safety against sliding of the cover soil. Our calculations resulted in a factor of safety of 1.94, which is consistent with the factor of safety presented in the Final Closure Plan. By adding the additional 300 lbs/sf surcharge imparted by the proposed solar ballast, the calculated factor of safety drops to 1.92,which is still well within the acceptable limits. 15. §2.7 Stormwater Collection System - The report states, "The design of the solar farm is not anticipated to impact the function of the existing stormwater collection system. " The report must include the necessary calculations to support this statement including the _ design capacity of the swales and recharge basin. Response: Currently, the area anticipated to receive the solar panels is covered with a maintained low growth vegetation. The drainage swales are lined with rip-rap with vegetation growing around the stone and in the joints between stones. The drainage area, designated as D1 on the Dvirka and Bartilucci consulting engineers plans where the solar panels are to be constructed, discharges to vegetated Recharge Basin No. 1. Typically, the ground cover under the solar panels will remain vegetated as it currently exists. There is no regarding of the area. Even though the panels are impervious,they are raised above the grade allowing stormwater to infiltrate the ground. From a stormwater perspective, keeping the ground cover the same in pre and post development conditions ‘,„ N WHITMAN G:\PROJECTS\2014\I4-06-15T Sun Edison Southhold Landfill\Landfill Closure Repom\NYDEC Response Letter.doa Mr. Syed H.Rahman,P.E. New York State Department of Environmental Conservation September 25,2015 Page 6 and the slope of the land in the same direction (toward Basin D1) the stormwater will flow at the same rate. However, due to the nature of the landfill cap, the panels will be anchored by concrete ballasts, approximately 9' 6" x 3' 6" in size, and will be considered impervious cover. When all the ballast areas are added together, the impervious cover is 11,145 SF (0.26 acres). The perimeter security fence will also be ballasted and will provide approximately 2,160 SF (0.05 acres) of impervious cover for a total of 13,305 SF (0.31 acres)new impervious cover. Calculating the pre and post development runoff for the site, there is an increase in runoff as shown in Table 1 for the 25 year and 100 year storm events. TABLE 1 Storm Event,years Existing Runoff, cfs propos cf Runoff, Change, cfs 25 16.2 17.0 +0.8 100 19.8 20.7 +0.9 Comparing the increase to the overall runoff in the current conditions, it appears as a diminimous increase. Further, Basin 1 has a freeboard of 6.7 feet and 3.2 feet for the 25 year and 100 storm events respectfully. The increased runoff will raise the water surface elevation by 0.1 feet and 0.2 feet for the storm events as,shown in Table 2. TABLE 2 Storm Event,years Existing Freeboard, ft.* Resulting Freeboard,ft. 25 6.7 6.6 100 3.2 3.0 * From Final Closure Plan by Dvirka and Bartilucci Even though the calculations reveal an increase in runoff for the 25 and 100 year storm events, it appears as though Basin 1 has sufficient capacity to store the increase without any regrading or alteration to the basin. 16. §2.'8 Gas Collection System - The report states, "The current gas collection system will not be impacted by the installation of the solar panels. " The current gas collection system is a passive venting system that relies on prevailing wind to control or prevent gas build up. The report must include the necessary information to support this statement NAN WHITMAN G:\PROJECiS\2014114-06-I5T Sun Edison Southhold LandfilllLand611 Closure AeportslNYDEC Response Letterdoa Mr. Syed H.'Rahman,P.E. New York State Department of Environmental Conservation September 25,2015 Page 7 (diagram to illustrate that the short gas venting pipes are not going to be blocked by the solar panels). Response: The location of the gas vent pipes was considered in the design of the solar array. The module racks were placed so that a minimum of 3' was maintained around the well. None of the solar array racks were placed over a gas vent. There are 3 vent pipes located within the northern most array as well as 3 within the southern array. The solar array racks are located so that all vent pipes are located in row, in between, each module rack row. Refer to both the construction drawings as well as the RBI drawings for reference to locations of the vent pipes. 17. § 2.9 Equipment Use on the Landfill - The report states, "The installation of the solar panels and the associated equipment will be completed through the use of equipment no larger than a pickup truck on the landfill." The report must provide the details of the equipment that will be used on the final cover system. Please provide the minimum specifications, including example vehicle model(s), which will be used on the landfill footprint. In addition, please provide the maximum load in psi by axle for each vehicle for both loaded and unloaded conditions. This load must not exceed 10 psi. Response: Included herein are typical equipment types and loading. Post Closure Plan 18. § 1.2 Landfill Closure Design - The plan states, "The existing conditions are sufficient to support the proposed load of the solar panels and associated equipment. " The report must provide the necessary load calculations to support this statement, including the maximum load the cap can withstand and the design load of the solar system in psi or' psf. Response: Based on the load provided by RBI, the worst case scenario has the solar rack load at 300.5 lbs/sf. The cap is constructed of approximately 2.5 feet of compacted silty sand with up to 10 feet of compacted fill. The cap and fill layers should bridge over any localized soft spot in the underlying landfill material. 19. § 1.3 Purpose and Scope - Change Southold Landfill Engineering Report to Southold Landfill Post Closure Plan in the first sentence of the first paragraph. Response: Change made. ` 7 WHITMAN G:\PROJECTS\2014\14-06-15T Sun Edison Southhold Landfill\Landfill Closure Reports\NYDEC Response letter.doa Mr. Syed H.Rahman,P.E. New York State Department of Environmental Conservation September 25,2015 Page 8 20. § 1.3 Purpose and Scope - Please change all references in the report to consistently reference "Southold Landfill Post Closure Plan". Response: Change made. 21. § 1.3 Purpose and Scope - The plan states, "The purpose of the Southold Landfill Post- Closure Monitoring and Maintenance Manual is to define the procedures for personnel performing routine inspection, maintenance or repair work on the landfill following its closure." The Department did not receive a Southold Landfill Post-Closure Monitoring and Maintenance Manual. Did you mean to reference the Southold Landfill Post Closure Plan? If so, please change all references in the plan to consistently reference "Southold Landfill Post Closure Plan". Response: Change made in the report. 22. §2.1 Cap Integrity - The Plan fails to mention how the cap integrity will be maintained during and after the installation of the solar panels. Response: The proposed solar array design does not require any penetration of the cap for the installation. However it's understood that during construction the cap entirety must be maintained and repaired immediately if disturbed. This section was revised. 23. § 2.3 Access and Maintenance Roads - The plan states, "The electricity from the solar cells will need to be transmitted across the gravel access road to make the connection to the grid" Please note that the access roads to the east and to the south of the planned solar cells are paved Response: It is understood that the section of the road that the electrical conduit needs to cross is paved,please refer to construction drawings for design of proposed crossing. 24. § 3.0 Maintenance and Repair - No mention of the maintenance and repair work associated with the solar panels is made. Appropriate sections should be added to address the maintenance and repair of solar panels, including identifying the responsible parties. Response: Typically maintenance will be performed as needed to maintain manufacturer warranty utilizing their guidelines, and surpassing these where necessary based on field experience best practices. Frequency and schedule will be included in the Sun Edison Contract. All initial repair work, related to workmanship, would be covered under Engineering, Procurement, Contractor(EPC)warranty, and EPC would be responsible for repairs. NIN, WHITMAN G:\PROJECTS\2014114.06-IST Sun Edison Southhold Landfill\Landfill Unsure Reports\NYDEC Response Letter doa Mr. Syed H.Rahman,P.E. New York State Department of Environmental Conservation September 25,2015 Page 9 25. § 6.0 Personnel and Equipment-No mention of the personnel and equipment related to the solar panels is made. Appropriate sections should be added to address the personnel and equipment of solar panels, including identifying the responsible parties. Response: This section of the report has been revised to include.a section for personnel and equipment as it relates to the solar array. 26. § 7.0 Contingency Plan- Would there be any specific contingency plan associate with the addition of the solar panels? Response: Changes have been made in the plan. 27. § 7.0 Contingency Plan - Please revise Table 7-1 to reflect correct name and phone numbers. Note that the DEC's Division of Solid and Hazardous Materials is now called Division of Materials Management. The Albany phone number is (518) 402-8676. Response: Changes have been made in the plan. 28. § 8.0 Post-Closure Cost Estimate - The plan states, "This section of the Manual provides an estimate of the costs expected to be incurred during the post-closure monitoring and maintenance of the Southold Landfill." The Department did not receive a Manual. Did you mean to reference the Southold Landfill Post Closure Plan? If so, please change all references in the plan to consistently reference "Southold Landfill Post Closure Plan". Response: Report name corrected. 29. § 8.0 Post-Closure Cost Estimate - The plan states, "the total projected cost during the 30 year post-closure period, based on 2015 dollars, is approximately $2,654,136. " How is it possible that this total is less than the total amount ($5,771,000)provided by Dvirka and Bartilucci in 2003 for the same time period with no solar farm? Please provide an updated 30 year post closure cost estimate which includes the cost to maintain and ultimately remove the solar farm. Response: The costs associated with the maintenance and decommissioning of the system are the responsibility of the system owner, Sun Edison. For the purpose of this approval, Sun Edison has indicated that the yearly maintenance costs associated with a system of this size are approximately $5,000 which includes routing repairs and system checks. An estimate of the decommissioning costs is approximately$90,000- $100,000 to return the site back to original condition. ®N WHITMAN G-\PROJECTS12014\14-06-15T Sun Edison Southhold LandfiH\Landfill Closure Reports\NYDEC Response Letterdoa Mr. Syed H.Rahman,P.E. ! New York State Department of Environmental Conservation September 25,2015 Page 10 - 30. § 8.0 Post-Closure Cost Estimate - Would the addition of solar panels incur additional costs for inspection and maintenance? _ Response: The post closure cost estimate should not incur additional costs as a result of monitoring and maintenance of the solar array. As part of the contract between Sun Edison and the Town, Sun Edison is required to provide operation and maintenance of the system that is a direct cost to Sun Edison and not the town. 31. § 9.0 Communication Procedures - Would there be any revisions to this section as a result of solar panel addition? Response: Section 9 has been updated. 32. § 10.0 Record Keeping and Reporting - Would there be any additional record keeping and reporting associated with solar panel addition? Response: Section 10 has been revised to include a subs section on solar installation report, please refer to the revised report. 33. § 10.0 Record Keeping and Reporting - Would Table 10-1 have items related to solar panel? Response: Section 10 has been revised to include a subs section on solar installation report, please refer to the revised report. Additional Comments 34. Please provide a contingency plan that address contingency measures that will be implemented during construction such as (but not limited to) damage to the geomembrane, erosion repair and detection of methane gas during construction. Response: Addressed in the Plan 35. The submittal did not include an original Professional Engineer (PE), licensed to practice in the State of New York stamp or statement of certification. Please submit a letter referencing the report that contains a statement of certification, original signature with date, and original PE stamp. Response: Addressed in the current submittal �A WHITMAN G•1PROJECfS\2014\14-06-IST Sun Edison Southhold Landfill\Landfill Closure ReportslRYDEC Response Letter.doa Mr. Syed H.Rahman,P.E. New York State Department of Environmental Conservation September 25,2015 Page 11 36. Please provide the Department construction level drawings for review. The Department will provide additional comments if needed at that time. Response: Attached 37. Please provide a copy of any agreement, including a lease if applicable, between the Town of Southold, Whitman, solar panel Construction Company, and the solar panel operator. Response: Previously supplied by Sun Edison 38. It appears that the Town was not copied on the distribution of the Engineering Report and the Post Closure Plan. Please include the appropriate Town personnel on all future correspondence. Response: The town will be copied on this and all future submittals We trust these revisions will satisfy the review comments. Should you have any questions, or require additional information,please do not hesitate to contact us. 4{ati P:IiiS,i, , Jrlr1 4 !YR cl$:101t tc�lu BS/ndd �Q'`')OFESS\i_'',� Encs. cc: Honorable Supervisor Scott Russell,Town of Southold Michael Collins,P.E., Town of Southold William Duffy,Town of Southold James Bunchuck,Town of Southold Jason Funk, Sun Edison Carey Ruetsch, Whitman Attachments: Construction Drawings _ ; Nli's: WHITMAN G.IPROJECTS12014114-06-I5T Sun Edison Southhold Iandfi111Landfill Closure ReportslNYDEC Response Letterdoa PROJECT INFORMATION SITE INFORMATION PRELIMINARY & FINAL SITE PLAN PROJECT DEVELOPER SITE NAME/ADDRESS 6155 COX LANE SUN EDISON REPRESENTATIVE SOUTHOLD,NY 11935 FOR RAISED GROUND MOUNTED SUN EDISON(CORPORATE OFFICE) GRACE TANGIRALA 12500 BALTIMORE MD 5NUE (85)GTANGIRALA@SUNEDISON COM SITE MAP(S)/LOT(S) 6IT COX LANE 1,123.2kW (DC), 781kW (AC) PHOTOVOLTAIC SYSTEM WHITMAN BELTSVILLE,MD 20705 (856) 330-1482 DISTRICT 1000,SECTION 96,BLOCK 1;LOT:17 5 (443)909-7200 OWNER TOWN OF SOUTHOLD SOLID WASTE MANAGEMENT SUN EDISON(REGIONAL OFFICE) 6155 COX LANE CONSISTING OF (3,456) 325 WATT SOLAR PANELS E""'°""`•Mecha" " Owl Structural•Mechanical•Elecmnl 100 TWINBRIDGE DRIVE,SUITE J SOUTHOLD,NY 11935 i 7 PLEASANT HILL ROAD PENNSAUKEN,NJ 08110 CRANBURY,NJ 08512 (856)330-1482 APPLICANT. SUNEDISON PE-(732)i90-9856 PENNS90-5858 AUKEN, )0811 ,SUITE) SUN EDISON PROJECT #(NY i12-0028) PENNSAUKEN,NJ 08110 ' CIVIL ENGINEER (856)330-1482 I BARRY SKOULTCHI,P E SOUTHOLD LANDFILL SEA` WHITMAN PV SYSTEM SPECIFICATIONS 7 PLEASANT HILL ROAD 6155 COX LANE CRA 390-58 NJ 08512 I INVERTER(S) (1)POWER ELECTRONICS 830kW INVERTER(FS0830CU-360V) (732) 58 I NY PE#0771 9 EXP 12/31/17 PROJECT RATED T 781kW CABINET Cl OUTHOLD, NY 11935 WITH DISCONNECT CABINET(FSDK 12 L3 3 N S 1 E) SOLAR MODULE (3,456)SUNEDISON 325W(SE-F325BzC) SUFFOLK COUNTY KEY MAP SCALE: 1"=±1200' STRING SIZE (18)MODULES PER STRING 9yn,;E RACKING* RBI BALLASTED 20°TILT Sheet List Table DRAWIAG NOTES: 1 IF THIS DRAWING DOES NOT CONTAIN THE I �tTq�' Drawing Number Sheet Number Drawing Title ORIGINAL SEAL OF THE PROFESSIONAL - ENGINEER,IT IS NOT A VALID DOCUMENT .i- I^-,, �r< `f _ _ - y� d n T-100 1 TITLE SHEET AND NO LIABILITY IS ASSUMED FOR THE N '''�y [�� Sun Ed�sonTM, T-101 2 NOTES AND SYMBOLS INFORMATION SHOWN �' 4� - simplifying solar D-101 3 SITE DETAILS 2 THIS DRAWING HAS BEEN PREPARED AS A ° - 'D'SIZE DOCUMENT DO NOT SCALE THIS ' _ _ 100 TWINBRIDGE DRIVE, SUITE J E-001 4 SUN EDISON NOTES SWING IF IT IS PLOTTED AS ANY OTHER tp,G. PENNSAUKENNJ 0�110 E-010 5 CONDUIT AND GROUNDING DETAILS , E-011 6 GROUNDING DETAILS k,} ° PROJECT NOTESItirE-012 7 CONDUIT DETAILS SUri Edison' ,�dJ„dis _ �° • ' 1 THE APPLICANT PROPOSES TO CONSTRUCT A PHOTOVOLTAIC GROUND MOUNTED E-013 8 CONDUIT DETAILS IC),2OID SUN EDISON,LLC AND ITS PROJECT SYSTEM. AFFILIATES,ALL RIGHTS RESERVED / - EC sITE E-020 9 EQUIPMENT TAG SCHEDULE 2 THE LOCATION OF PROPOSED ELECTRIC UTILITIES ARE SUBJECT TO THE FINAL 12500 BALTIMORE AVE 4'''"•_ �•«•,.° E-021 10 EQUIPMENT TAG SCHEDULE BELTSVILLE,MD 20705 iAPPROVAL OF THE APPROPRIATE UTILITY COMPANIES (443)909-7200 SCALE: 1"=±600' 3 ALL MATERIALS,WORKMANSHIP AND CONSTRUCTION FOR THE SITE IMPROVEMENTS E-030 11 TYPICAL PHOTOVOLTAIC SYSTEM MONITORING SCHEMATIC — AERIAL MAP �� �r SHOWN HERE ON SHALL BE IN ACCORDANCE WITH E-031 12 METERING&MONITORING DETAILS Y� '' aAiZA �1 Vt?. r;^,Y �-” ` %jy � 'i3.;-c'. A CURRENT AND REQUIREMEN SG MUNICIPAL AND/OR COUNTY SPECIFICATIONS,STANDARDS E-032 13 TEMPERATURE EQUIPMENT MOUNTING DETAILS r i-•'.'� w"''' X " � _y;,, `-C'a ' B CURRENT PREVAILING UTILITY COMPANY SPECIFICATIONS,STANDARDS AND a E-033 14 SEEDS MOUNTING DETAILS r1,,_.,„--•--.40 ,!--0-.::,.,_-t,„,,.--'.--,,a,‘4,„, ?:,,rea.-'r REQUIREMENTS k44,,,,,,4-,!1 b"��.aE, �, <7- 4.,, , -•e4", ';'' 'V-,,,• .,,,, ,� ,K; E-100 15 OVERALL ELECTRICAL LAYOUT PLAN •'ryF�i:F'y t 1 ` t _'�/y!i 'c + > ALL INFORMATION SHOWN MUST BE VERIFIED PRIOR TO USE FOR CONSTRUCTION ,'".,' Lz. . �.-,,c? _ -, ACTIVITIES E-110 16 ELECTRICAL EQUIPMENT LAYOUT PLAN t '- s, clW r,, ,,.,�r�" 3J? NO DATE REVISION DESCRIPTION ( .'' --1?:/,/. fc:'�._^;,;.-+.. E-200 8 1 N ,• F I ` •-, �; .. t!; -i-,? -J:.ta I,-,- ra, 5 PROPOSED SOLAR PANEL SUPPORT FRAMES TO BE INSTALLED IN a wave pRND RAc1 sI somal°N '` '-_'° E-210 18 ELECTRIC SCHEDULES E -.45, ",f1_.;" : ,,±-',s ,-'%1/4-;y .,, t `�;�, .,, ACCORDANCE WITH MANUFACTURERS SPECIFICATIONS AND STRUCTURAL I_ , ,-,7_•;,;;1e , s_-,,,.f s, - -,,,,;.'1'1"-- --,,,/,'',.-;-- REQUIREMENTS,TO BE PROVIDED UNDER SEPARATE COVER. ° ,,"-;;)IW,;‘" r ', � ��N19 v3 •" • _ • -�,=g,�`��--,�';;fir, -� ���'_� :• �• � �`• =t"' t' � CODE REQUIREMENTS E-3OO PV ARRAY(SA1-1 THRU SA1-6) ` e „''+ ,.-,,,,:-, t.`„>,... _.-t-•1 7r ;i4 7'' ,.', ' E-301 20 PV ARRAY(SA1 7 THRU SA1 12) _ C -Ir'';?' T . 'A. 7,:-:;/"- ," 'i ,1 'TS� ,/E' / =!.c '1 REGULATIONS,LAWS AND ORDINANCES AS REQUIRED BY THE STATE OF NEW YORK W Z5<; ' f''' y;ys• f p / ,f"_ '- � AND LOCAL AUTHORITIES HAVING JURISDICTION INCLUDING BUT NOT LIMITED TO (.` f1�`ty� •�,� `c" 1Y} -"ljtF�F. TT '_(`, :>w-}: • ��. j`-'_ ' ti, r ._ •NEW YORK STATE BUILDING CODE WHICH IS COMPRISED OF THE 2009 ' s' '' ‘,.,1,:, 'y "2,`:...W°,2:', ' 1 INTERNATIONAL BUILDING CODE PROJECT: -:_':„%-4,-.' ,,u-- • `F PROJECT 1,123.2kW(DC),781kW(AC) y°'I,'..,,.,., _' -- : - . '_ •2008 NATIONAL ELECTRICAL CODE • ��,. -• 3r r/ +; SITE •NATIONAL FIRE PROTECTION ASSOCIATION 70E o ; _ !-' i " .�j r �fp RAISED GROUND MOUNTED PHOTOVOLTAIC SYSTEM aSUN EDISON(NY-12-0028) o SOUTHOLD LANDFILL - _ - 6155 COX LANE o SOUTHOLD,NY 11935 SUFFOLK COUNTY O 131.00, 1 175 h Z SCALE ^S SHOWN W. lIbR / .... 1•1- I 0 Co PLOT DATE_ 9/24/1S CLIENTSIINEDItON O W DRAWNBI pE REVIEWED BY CA Z BEFORE YOU DRAWING 777ZE I-- DIG MODULES ARE ORIENTED AT ��®^ TITLE SHEET 180°AZIMUTH AND 20°TILTS. r DRAwRVGJVG / CALL T-100 F- sx THE COPYING OR REUSE OF THIS DOCUMENT,OR PORTIONS THEREOF,WITHOUT THE WRITTEN AGREEMENT OF WHITMAN IS PROHIBITED,COPYRIGHT 2015,WHITMAN DO NOT SCALE THIS DRAWING 1 OF 20 i7:4 - TYPICAL ABBREVIATIONS GENERAL SAFETY NOTES GENERAL INSTALLATION NOTES ELECTRICAL NOTES: TYPICAL SYMBOLS w A AMPERE(S) S1 PANELS ARE WRAPPED AND SECURED IN THE CRATE BY A MEANS G1 THE INSTALLATION CONTRACTOR IS RESPONSIBLE FOR INSTALLING El ALL WORK SHALL BE IN ACCORDANCE WITH THE CURRENTLY ADOPTED EDITION OF THE AC ALTERNATING CURRENT _ I THAT WILL ALLOW THE INSTALLER TO REMOVE ONE PANEL AT A ALL EQUIPMENT AND FOLLOWING ALL DIRECTIONS AND NEC,IBC AND LOCAL CODES (auAIR AIR HANDLING UNIT TIME WITHOUT COMPROMISING THE STABILITY OF THE REMAINING INSTRUCTIONS CONTAINED IN THIS DRAWING PACKAGE AND RACKING TRANSFORMER AL ALUMINUM PANELS(IF THE CRATE IS OPENED AND PANELS ARE REMOVED AND PANEL SPECIFICATIONS E2 IN EVERY PULL BOX AND IN ALL PLACES WHERE WIRES MAY NOT BE READILY IDENTIFIED AWG AMERICAN WIRE GAUGE FROM THE WRONG END,PANEL STABILITY WILL BE COMPROMISED BY NAMEPLATE MARKINGS ON THE EQUIPMENT TO WHICH THEY CONNECT.THE -- ' AND WILL CREATE A DANGEROUS SITUATION) G2 THE INSTALLATION CONTRACTOR IS RESPONSIBLE FOR READING AND INSTALLATION CONTRACTOR WILL BE RESPONSIBLE FOR IDENTIFYING EACH CIRCUIT WITH EKED BLACKBOARD WHITMAN UNDERSTANDING ALL DRAWINGS,COMPONENT AND INVERTER A PLASTIC LABEL OR TAG I C CONDUIT 52 EACH INDIVIDUAL PHOTOVOLTAIC MODULE WEIGHS 485 LBS FOR MANUALS PRIOR TO INSTALLATION THE INSTALLATION CONTRACTOR CB CIRCUIT BREAKER THE EASE AND SAFETY OF LIFTING,IT IS RECOMMENDED BY THE IS ALSO REQUIRED TO HAVE ALL COMPONENT SWITCHES IN THE OFF E3 THE LAYOUT OF THE CONDUIT SHOWN IN THIS DRAWING PACKAGE IS INDICATIVE ONLY m Envuon <2tal•Ge#t«hmcal•L1W MANUFACTURER THAT THIS OPERATION BE PERFORMED BY NO POSITION AND FUSES REMOVED PRIOR TO THE INSTALLATION OF ALL THE INSTALLATION CONTRACTOR WILL BE RESPONSIBLE FOR FIELD ROUTING AND FUSED DISCONNECT SWITCH CCB CIRCUIT Structural•Mechamwl•Eleannl LESS THAN TWO INSTALLERS EACH INSTALLER SHALL USE THE FUSE BEARING SYSTEM COMPONENTS LOCATING ALL CONDUITS TO SUIT SPECIFIC SITE CONDITIONS THE INSTALLATION 7 PLEASANT HILL ROAD CORRECT METHOD OF LIFTING AND PLACING CONTRACTOR WILL COORDINATE ALL LOCATIONS WITH THE OWNER/GENERAL CONDICONDUCTOR CRANBURY,NJ 08512 G3 FOR SAFETY IT IS RECOMMENDED BY THE MANUFACTURER THAT THE CONTRACTOR AND ANY OTHER TRADES THAT THE NEW ROUTING MAY AFFECT CT CURRENT TRANSFORMER TEL(7321390.5858 S3 ONCE A MODULE IS REMOVED FROM THE CRATE,NEVER LEAVE INSTALLATION CREW ALWAYS HAVE A MINIMUM OF TWO PERSONS 1 MEDIUM VOLTAGE CONTACTOR CU I COPPER FAX(732)390-9496 THE MODULE STANDING UNSUPPORTED OR UNSECURED WORKING TOGETHER AND THAT EACH OF THE INSTALLATION CREW E4 WHERE THE WIRING AND CABLE ROUTING IS NOT SHOWN AND THE DESTINATION IS ONLY T ,- REMEMBER THAT DURING DAYLIGHT HOURS THE MODULE WILL BE MEMBERS BE TRAINED IN FIRST AID AND CPR INDICATED,THE INSTALLATION CONTRACTOR WILL BE RESPONSIBLE FOR DETERMINING DC ' DIRECT CURRENT PRODUCING 600VDC IF THE MODULE IS DAMAGED THERE IS A THE EXACT ROUTING AND LENGTHS REQUIRED IN ACCORDANCE WITH THE BUILDINGI DISC DISCONNECT SWITCH CHANCE OF BEING EXPOSED TO THE FULL VOLTAGE AND CURRENT G4 THIS SOLAR PHOTOVOLTAIC SYSTEM IS TO BE INSTALLED FOLLOWING OWNER AND THE NEC DN DOWN SEAL BEING GENERATED IF A MODULE IS SHIPPED DAMAGED OR THE CONVENTIONS OF THE NATIONAL ELECTRIC CODE ANY LOCAL )1 CIRCUIT BREAKER DP DOUBLE POLE BECOMES DAMAGED AT THE JOBSITE,CAREFULLY HANDLE THE CODE WHICH MAY SUPERSEDE THE NEC SHALL GOVERN E5 ALL WIRING SHALL BE RUN IN SPECIFIED CONDUIT THE CONTRACTOR WILL BE REQUIRED MODULE AND PLACE IT OUT OF THE SUNLIGHT TO SEEK APPROVAL BY THE GENERAL CONTRACTOR/DESIGN AGENCY PRIOR TO I ECELECTRICAL CONTRACTOR G5 ALL SYSTEM COMPONENTS TO BE INSTALLED WITH THIS SYSTEM ARE CHANGING ANY MATERIAL SPECIFICATIONS EM I EMERGENCY S4 EVEN IF THE MODULE IS NOT DAMAGED,KEEP IN MIND THAT TO BE"U12 LISTED ALL EQUIPMENT WILL BE NEMA 3R OUTDOOR - CONDUIT NUMBER(REFER EMT 1 ELECTRICAL METALLIC TUBING ` WHENEVER THE MODULE OR SYSTEM IS EXPOSED TO SUNLIGHT IT RATED UNLESS LOCATED INDOORS E6 ANY BENDS IN THE CONDUIT OR RACEWAY SHALL NOT DAMAGE OR SIGNIFICANTLY PIX TO CABLE SCHEDULE) ER EXISTING TO BE REMOVED CAN GENERATE UP TO 600VDC AND AS HIGH AS 480VAC WHEN CHANGE THE INTERNAL DIAMETER(NO KINKS) 1 WORKING WITH THIS EQUIPMENT,TAKE EVERY PRECAUTION TO GE THE DC VOLTAGE FROM THE ARRAY IS ALWAYS PRESENT AT THE DCI FS FUSIBLE SWITCH — AVOID CONTACT WITH ANY ELECTRICAL TERMINAL OR WIRE DISCONNECT ENCLOSURE AND THE DC TERMINALS OF THE INVERTER E7 ANY CONDUCTORS RUN IN A VERTICAL CONDUIT WILL BE SUPPORTED IN ACCORDANCE O FU FUSE UNLESS SYSTEM VOLTAGE IS TESTED,LOCKED OUT AND DEEMED DURING DAYLIGHT HOURS ALL PERSONS WORKING ON OR INVOLVED WITH NEC REQUIREMENTS POLE MOUNTED GANG SAFE FOR WORK. WITH THIS PHOTOVOLTAIC SYSTEM ARE WARNED THAT THE SOLAR OPERATED HORIZONTAL DEC GROUNDING ELECTRODE CONDUCTOR — MODULES ARE ENERGIZED WHENEVER THEY ARE EXPOSED TO LIGHT E8 THE INSTALLATION CONTRACTOR SHALL INSTALL ALL WIRING MATERIALS IN A NEAT AND ' I SWITCH GFI GROUND FAULT INTERRUPTER S5 THE CONTRACTOR SHALL BE RESPONSIBLE FOR ADEQUATE WORKMANLIKE MANNER.USING GOOD TRADE PRACTICES WIRING SHALL BE INSTALLED GND/G GROUND BRACING AND PROTECTION OF ALL WORK DURING CONSTRUCTION G7 ALL PORTIONS OF THIS SOLAR PHOTOVOLTAIC SYSTEM SCALE BE PER CHAPTER 3 OF THE NEC GS,gs GROUND SHOT(ELEVATION SHOT AT ROOF) TO AVOID DAMAGE,COLLAPSE,DISTORTION,MISALIGNMENT, MARKED CLEARLY IN ACCORDANCE WITH THE NATIONAL ELECTRIC ft VOIDING ROOFING WARRANTIES,ETC PROTECTION SHALL BE IN CODE ARTICLE 690 E9 THE INSTALLATION CONTRACTOR WILL ARRANGE CONDUIT IN SUCH A MANNER THAT WILL HZ FREQUENCY(CYCLES PER SECOND) COMPLIANCE WITH ALL APPLICABLE CODES,STANDARDS,AND MAINTAIN HEADROOM AND IN A NEAT,INCONSPICUOUS MANNER,RUN PARALLEL AND AT �-�p POLE MOUNTED FUSED BEST PRACTICES ALL SURFACES SHALL BE RESTORED TO GB PRIOR TO SYSTEM START-UP,THE INSTALLATION CONTRACTOR RIGHT ANGLES TO STRUCTURAL MEMBERS,PROVIDE BOXES,FITTINGS,AND BENDS FOR 1 I CUTOUTS JB JUNCTION BOX DRAWING NOTES COMPLETE WATER TIGHTNESS WITH THE APPROVED MATERIAL SHALL ASSIST IN PERFORMING ALL INITIAL HARDWARE CHECKS AND CHANGE OF DIRECTION INSTALLATION CONTRACTOR IS TO FASTEN ALL CONDUIT I AND AS PRE-APPROVED BY THE OWNER IN WRITING DC WIRING CONDUCTIVITY CHECKS THE FINAL START-UP SHALL BE SECURELY IN PLACE K KEY OPERATED 1 IF THIS DRAWING DOES NOT CONTAIN THE PERFORMED BY CONTRACTOR KVAI KILOVOLT AMPERE(S) ORIGINAL SEAL OF THE PROFESSIONAL S6 THE CONTRACTOR SHALL BEAR FULL RESPONSIBILITY FOR THE E10 THE INSTALLATION CONTRACTOR WILL PROVIDE PULL AND JUNCTION BOXES WHERE --7/1-0 LIGHTNING ARRESTER KW KILOWATT ENGINEER,IT IS NOT A VALID DOCUMENT MEANS AND METHODS OF CONSTRUCTING THE WORK SHOWN ON GB FOR THE PROPER MAINTENANCE AND ISOLATION OF THE INVERTERS, REQUIRED TO FACILITATE THE INSTALLATION OF WIRING,IN ADDITION TO THOSE THAT KWH KILOWATT HOUR AND NO LIABILITY IS ASSUMED FOR THE THESE PLANS ALL WORK SHALL BE PERFORMED IN ACCORDANCE REFER TO THE ISOLATION PROCEDURES IN THE INVERTER MAYBE SHOWN ON THE DRAWINGS ❑ INFORMATION SHOWN WITH LOCAL LAWS,RULES AND REGULATIONS CONCERNING OPERATIONS MANUAL R POLE MOUNTED RECLOSER L LINE CONSTRUCTION HEALTH AND SAFETY STANDARDS THE . E11 ANY BENDS IN THE CONDUIT RUNS SHALL UTILIZE MANUFACTURERS STANDARD ELBOWS CONTRACTOR SHALL INSURE ALL WORKING CONDITIONS ARE G10 THE OWNER MAY HAVE WORK PERFORMED UNDER SEPARATE WHERE PRACTICAL USE OF LB'S IS NOT PERMITTED PER SUN EDISON SPECIFICATIONS mA MILLIAMP 2 THIS DRAWING HAS BEEN PREPARED AS A SANITARY AND ARE NOT HAZARDOUS OR DANGEROUS TO THE CONTRACT,CONCURRENT WITH THE WORK OF THIS CONTRACT THE MCB MAIN CIRCUIT,BREAKER 'D'SIZE DOCUMENT DO NOT SCALE THIS HEALTH AND SAFETY OF THE WORK CREWS OR BUILDING CONTRACTOR SHALL COORDINATE ALL CONSTRUCTION ACTIVITIES E12 INSTALL CONDUIT CONTINUOUS BETWEEN BOXES AND CABINETS WITH NO MORE THAN MLO MAIN LUGS ONLY DRAWING IF IT IS PLOTTED AS ANY OTHER OCCUPANTS PRECAUTION SHALL BE EXERCISED AT ALL TIMES WITH THE LANDLORD TO AVOID ANY CONFLICTS WITH SITE ACTIVITIES FOUR(4)90 DEGREE BENDS SECURELY FASTEN IN PLACE WITH STRAPS,HANGERS AND �W TRANSFORMER FEED MCM THOUSAND CIRCULAR MIL(S) SIZE FOR THE PROTECTION OF PERSONS AND PROPERTY ALL SAFETY OR CURRENT USES STEEL SUPPORTS AS REQUIRED DO NOT SUPPORT THE CONDUIT FROM SUSPENDED 1Y PROVISIONS OF APPLICABLE LOCAL LAWS,OSHA REGULATIONS CEILING GRID OR SUSPENSION WIRES REAM CONDUIT ENDS BEFORE INSTALLATION AND THROUGH INSERT N NEUTRAL NORMALLY CLOSED -� FOR ALL CONTRACTORS --- AND BUILDING AND CONSTRUCTION CODES MUST BE OBSERVED THOROUGHLY CLEAN BEFORE INSTALLATION OPENINGS SHALL E PLUGGED OR COVERED /(..,�� NC TO KEEP CONDUIT CLEAN i CURRENT TRANSFORMER NEC NATIONAL ELECTRICAL CODE i fill NF NON FUSE ,Sun Edison' S7 THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL E13 WHERE FIELD CUTTING IS REQUIRED,THE CONDUIT SHALL BE CUT SQUARE AND THE (RATING AS SHOWN)AND NO NORMALLY OPEN INSTALLATION CONTRACTOR WILL PROVIDE THE NECESSARY PROTECTION IN ORDER TO PROTECTIVE DEVICE simp1J8�� CONSTRUCTION SCHEDULING AND ASSOCIATED HOISTING, OVER CURRENT PROTECTION STAGING AND ERECTING OF MATERIALS ALL ELEMENTS OF THE PREVENT ANY DAMAGE TO THE ROOF MEMBRANE WHEN COMPLETE,ALL METAL FILINGS IQ OCP, (FFILIA0 SUN EDISDN,L-`121320 RESER R9 EXISTING PROPERTY SHALL BE PROTECTED AGAINST DAMAGE WILL BE DISPOSED OF PROPERLY DIGTRIP 100D pB PANEL BOARD AF ILIATES,ALL RIGHTS RESERVED RESULTING FROM THESE ACTIVITIES PH PHASE 12500 BALTIMORE AVE E74 WHERE CONDUIT SIZES ARE NOT SPECIFIED THE INSTALLATION CONTRACTOR WILL BE PRIMARY ' REQUIRED TO CONFORM TO THE NEC CONDUIT FILL REQUIREMENTS THE MINIMUM PRI BELTSVILLE,MD 20705 i GENERAL NOTES ALLOWABLE CONDUIT SIZE SHALL BE 314° PVC POLYVINYL CHLORIDE (443)SVI909-7200,MD2 1 THE CONTRACTOR SHALL SECURE AND PAY FOR AND FILE PERMITS, E15 THE MINIMUM ALLOWABLE WIRING SIZE WILL BE#12 AWG THE ONLY EXCEPTION WILL BE DC-_ R EXISTING RELOCATED LICENSES,APPLICATIONS AND OR CERTIFICATES FOR THE WORK FOR SIGNAL AND/OR CONTROL WIRING ALL CONDUCTORS SHALL BE COPPER UNLESS RECPT RECEPTACLE UNDER THIS DIVISION OTHERWISE NOTED DC TO AC INVERTER RGS RIGID GALVANIZED STEEL 2 CONTRACTOR SHALL NOTIFY OWNER ONE WEEK IN ADVANCE OF ANY E16 ALL CALCULATIONS FOR WIRING SIZE ARE BASED ON THE ESTIMATED CONDUIT ROUTING ...PAC SL, SKY LIGHT INTERRUPTIONS TO BUILDING SERVICES,WITH AN ESTIMATED TIME OF AS SHOWN ON THESE DRAWINGS SHOULD THE CONDUIT LENGTHS INCREASE DUE TO SN SOLID NEUTRAL THE INTERRUPTION RELOCATION OF THE SOURCE OR REROUTING OF THE CONDUITS,THE WIRING SIZES MAY SW SWITCH NEED TO BE INCREASED SWBD SWITCHBOARD 0 WEATHER STATION T, TELEPHONE E17 ALL GROUNDING TO BE INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL TERMINAL BLOCK CODE ARTICLE 250 TEFC TOTALLY ENCLOSED FAN COOLED E18 ALL ELECTRICAL WORK RELATED TO THE SOLAR INSTALLATION SHALL FOLLOW THE TYP TYPICAL NO DATE REVISION DESCRIPTION �I, o NATIONAL ELECTRICAL CODE ARTICLE NO INVERTER# V VOLT(S) a #:2.1/15 ra¢MINAR1 STRMITSI#N i STRING# VOLT AMPERE(S) I_ E19 ALL WIRE AND CABLE AMPACITIES INDICATED ON DRAWINGS ARE BASED ON INSULATION -�� VA VENT TO ATMOSPHERE TEMPERATURE RATING OF 90°C ALL LUGS,BREAKERS,SWITCHES AND OTHER SOLAR PANEL � VTA TERMINATIONS SHALL HAVE A MINIMUM OF 75°C TEMPERATURE RATING IC L'LtJIIaS'�" WH WATT HOUR aS 9 '-a W WATT(S) E20 POWER CIRCUIT WIRING SHALL NOT BE RUN THROUGH CONTROL CONDUITS OR TO FV WRING WP WEATHERPROOF 56- CONTROL TERMINAL BLOCKS,SEPARATE POWER TERMINAL BLOCKS AND CONDUITS SHALL o COMBINER BOX# BE PROVIDED FOR POWER CIRCUITS XFMR TRANSFORMER E21 GROUNDING LEADS TO ELECTRICAL EQUIPMENT MUST BE SIZED IN ACCORDANCE WITH 1600 AMP FRAME/400 AMP TRIP -- NEC 260 BUT NOT SMALLER THAN#4(AL)OR#6(CU) 1600AF/400AT 1600AS/400AF 1600 AMP SWITCH/420 AMP FUSE C.) O 1- E22 ALL CONDUCTORS SHALL BE NEATLY BUNDLED INTO GROUPS WITH THOMAS&BETTS TY-RAPS',OR APPROVED EQUAL,IN A MANNER THAT WILL PERMIT THE REMOVAL OF ANY —GAS UNDER GROUND GAS LINE PROJECT. CONDUCTOR WITHOUT UNDUE INTERFERENCE WITH ADJACENT CONDUCTORS U UNDER GROUND DUCT BAN WCONDUIT 1,123.2kW(DC),781kW(AC) E23 UNLESS OTHERWISE NOTED OR DIMENSIONED,LOCATION OF GROUND RODS AND EXACT O LOCATIONS SHALL BE DETERMINED IN FIELD BY THE CONTRACTOR,AND GROUNDING E OVERHEAD UTILITY LINE RAISED GROUND MOUNTED O - CONDUCTORS ARE SHOWN ON THE GROUNDING PLAN DIAGRAMMATICALLY PHOTOVOLTAIC SYSTEM LLE24 UNLESS OTHERWISE NOTED,GROUNDING LEADS TO NON-ELECTRICAL EQUIPMENT AND SUN EDISON(NY-12-0028) Z STRUCTURAL MEMBERS MUST BE#3/0(CU)AWG S H LANDFILL 5 E25 BURIED GROUNDING CABLE CROSSING METALLIC STRUCTURES,SUCH AS CONDUITS OR 6155 COX LANE 9 PIPELINES,SHALL BE SEPARATED A MINIMUM OF 12°FROM SUCH STRUCTURES = SOUTHOLD,NY 11935 E26 DO NOT USE PIPES AND EQUIPMENT BODIES AS A EQUIPMENT GROUNDING PATH SUFFOLK COUNTY O (.0E27 BURIAL IN IRREVERSIBLE OR CONCRETE GROUNDING TCONNECTIONS MECHANICAL GRIOUNDING 910CK I las 175 2 - CONNECTIONS THAT USE BOLTS TO MAKE CONNECTION ARE NOT PERMITTED FOR DIRECT CO BURIAL GROUNDING CONNECTION _ SCALE AS SHOWN IJ41b15T W RiATDATE 92.1/15 U E28 ALL GROUNDING CLAMPS AND CONNECTORS SHALL HAVE(SILICONE BRONZE)HARDWARE 1vr stINED1s0N 2 A ALL SURFACES SHALL BE CLEANED TO BARE METAL BEFORE MAKING GROUNDING DRASNBY FE, 'IEI CR CO CONNECTIONS B APPLY ELECTRICAL JOINT PASTE A UNDER FITTINGSCDRAWING � C PAINT EXPOSED SURFACES OF ALL PRESSURE CONNECTIONS WITH ZINC CHROMATE TTTLE- C E39 ALL CONNECTIONS AND LUGS SHALL BE RATED FOR USE WITH BOTH ALUMINUM ANDNOTES AND SYMBOLS ✓ COPPER CONDUCTORS v DRAWING NO N T-101 SNEETNO: ' THE COPYING OR REUSE OF THIS DOCUMENT,OR PORTIONS THEREOF,WITHOUT THE WRITTEN AGREEMENT OF WHITMAN IS PROHIBITED,COPYRIGHT 2015,WHITMAN DO NOT SCALE THIS DRAWING 2 OF 20 3'MIN f 1-6" -1 A MN z CONCRETE AND REINFORCING STEEL NOTES: c PIPE a I T FENCE POST ■M■■■■■■Mull...■MM■MMM■MM■M■■ 1 ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH THE ACI 301 #4 BARS 12"0 C EACH WAY 9'MI W/BASE PLATE D-101 DANGER ■M■■■■■M■M■■■■MM■■■■M■■M■■■MM AND ACI 318 (NP•) MAXNON-SHRINK"T 5,000 P S I GROUT ■MM■■■■■■MM■■■■■M■MM■■MMM■MMM (3)#a BARS(ALL SIDES) MAX 1 1!2"THICK) HIGH VOLTAGE WITHIN ■■■■■■■■■■■■M■■M■■M■MMM■■■■■■ -I„ WHITMAN ■M■■MM■■■■MMMMMM■■■■■M■■■M■■■ 2 ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH 3/4"CHAMFER(NP) KEEP OUT m MM■■M■■■■■■■■■■■■MMMM■M■■■■MM OF 4000 PSI AT 28 DAYS,UNLESS NOTED OTHERWISE (4)#4 BARS(CONT) — Envuoarnl• •Gaoled•nl.Civil MMM■■■■■■■■■■■■■M■■■MMM■IINIM■M swcnrzal.Mecluwnl.Elccmnl ■MM■■■■M■■■■■■■■■MM■■r7■IMM■■ 3 REINFORCING STEEL SHALL CONFORM TO ASTM A 615,GRADE 60, �� E1/ST/NG GRADE I 47 PLEASANT HB L ROAD ■■■■■■■■■■M■M■■MM■■•MMM■1111•■■ DEFORMED UNLESS NOTED OTHERWISE WELDED WIRE FABRIC ,���� �_ C7tANBl1RY,N1o8512 MMM■■M■■MM■■M■M■■M■■■I1■■1111■■■ SHALL CONFORM TO ASTM A 185 WELDED STEEL WIRE FABRIC < TYPE A SIGN TEL(7321390-5858 ■MM■■■■■■■MM■■■■MM■■MI■••1111■■• UNLESS NOTED OTHERWISE SPLICES SHALL BE CLASS"B"AND ALL �° _ FILTER FABRIC TenCate FAX(732)390-9496 1 MM■■■■■■■■■■■■■■■■■■■11■■1111■■■ HOOKS SHALL BE STANDARD,UNLESS NOTED OTHERWISE Wane X-Senes OR EQUAL NOTE I r. reh •r •r •!.•• ••• • •r 1r •• ••• J. 1 CONTRACTOR TO GRADE AS REQUIRED4 THE FOLLOWING MINIMUM CONCRETE COVER SHALL BE PROVIDED a ! o O .,�i.N•••-a •�••,• • •,4-#4.'404041 CONTRACTOR TO VERIFY MINIMUM I SEAL. Ali REINFORCEMENT FOR REINFORCING STEEL UNLESS SHOWN OTHERWISE ON •t: ss •", ••5S% •..••s•+a5 •!..S S%/•-•!Ps3000 LBS/FT'BEARING CAPACITY w ,o Vara 1 #4@12"0 C DRAWINGS' /fl �� �-We,,,, OF EXPOSED SUBGRADE N CONCRETE CAST AGAINST EARTH. 3 IN ; ! • 95% • • •r a COMPACTED SOILTO MIN CONCRETE EXPOSED TO EARTH OR WEATHER • u • MODIFIED MAX DENSITY PER m CONCRETE INVERTER SLAB PLAN #6 AND LARGER .. . ..21N ,Atte• • • • : 111' TRESPASSING ASTM D1557 METHOD CD-101 SCALE NTS #5ANDSMALLER8WWF.. .. . 11/2INM� CONCRETE NOT EXPOSED TO EARTH OR WEATHER OR NOT CONDUITS 12"THICK CONCRETE SLAB CAST AGAINST THE GROUND (TYP) SEE SLAB AND WALL . . .. .2 IN NOTE 1 6"LAYER OF 3/4"CLEAN 1 SLAB SIZE BEAMS AND COLUMNS . ..... . 2 IN STONE TYPE B SIGN LOCATION A B 5 A 3/4"CHAMFER SHALL BE PROVIDED AT ALL EXPOSED EDGES OF A CONCRETE SLAB SECTION DETAIL INVERTER 30'-9' 12•_g• CONCRETE,UNO,IN ACCORDANCE WITH ACI 301 SECTION 4 2 4 D-101 SCALE NTS 3%0" DRAWING NOTES TRANSFORMER 11'-0' g'-0' 6 INSTALLATION OF CONCRETE EXPANSIONANEDGERNCHOR,SHALL NOTE BE PER MANUFACTURER'S WRITTEN RECOMMENDED PROCEDURE 1 USE CONDUIT WINDOW ONLY AS INDICATED ON PLANS ALL OTHER AUTHORIZED PERSONNEL ONLY 1 IF THIS DRAWING DOES NOT CONTAIN THE CUSTOMER SWITCH 10'-9" 7'-6" THE ANCHOR BOLT,DOWEL OR ROD SHALL CONFORM TO ORIGINAL SEAL OF THE PROFESSIONAL MANUFACTURER'S RECOMMENDATION FOR EMBEDMENT DEPTH OR CONDUIT PENETRATIONS SHALL BE STUBBED UP THROUGH SLAB ENGINEER,IT IS NOT A VALID DOCUMENT CUSTOMER METER 5'-0' 5'-0• AS SHOWN ON THE DRAWINGS NO REBAR SHALL BE CUT WITHOUT 2 REFER TO SHEET E-110 FOR CONDUIT WINDOW DIMENSIONS Sun Edison q INFORMATION AND NO LIABILITY IS SHOWNSSUMED FOR THE PRIOR ENGINEERING APPROVAL WHEN DRILLING HOLES IN 3 PROVIDE 1"FIBER EXPANSION JOINT ALONG ADJOINING CONCRETE •motr..,.,o= UTILITY METER 12'-0" 5'-0" SURFACES 2 THIS DRAWING HAS BEEN PREPARED AS A CONCRETE FOR INFORMATION CALL 888-786-3347 'D'SIZE DOCUMENT DO NOT SCALE THIS NOTE FOR EMERGENCY CALL'911 DRAWING IF IT IS PLOTTED AS ANY OTHER 1 EQUIPMENT SLAB SIZE SHALL BE VERIFIED WITH FINAL EQUIPMENT SIZE SUBMITTAL PRIOR TO POURING TYPE C SIGN I- ,o'-0.0 C 1 12'-0" TYPICAL WOVEN WIRE FENCING NOTES: 3 SIGN DETAILSlir Sun Edison" r o p prl (INSTALL FENCING PER ASTM F-567,SWING GATES PER ASTM D-101 SCALE N T S , I Bsoh, F-900 IC),2010 SUN oDISON LLC AND ITS `•:- ♦���� I ,•...,•► _ 47 -4..I r....- 7;4: v•♦♦♦♦• ♦♦♦♦•♦♦��n -- ♦♦♦♦♦♦• ) AFFLL WTES,ALLRIGHT6RESERVED♦♦♦� TENSION WIRE ♦♦♦♦♦♦ ♦♦♦♦♦♦♦♦ •�♦♦♦♦♦� ♦♦♦♦♦�!i♦�' .♦♦♦ ♦♦♦♦♦��♦ ♦♦♦♦♦♦♦♦ NOTES ♦♦♦♦ ♦�♦♦. � 1♦t-♦ ♦♦♦♦ 1 GATEPOST,CORNER,OR PULL POST4"0 SS 40 1 SIGNS'A'AND'B'MUSTBELOCATEDATEYELEVEL 12560 BALTIMORE AVE �I1Jf( ♦♦ 7 GA ♦♦♦♦♦�♦♦♦j♦j� ♦♦♦♦♦♦♦ ♦♦♦��`♦' 1♦♦�♦♦�! ♦♦♦���♦� ♦•♦♦♦ ♦♦♦♦ BELTSVILLE,MD 20705 ♦♦ ♦♦♦♦♦♦, ♦♦♦♦ - ♦♦,� ♦♦♦, ♦♦�� ♦♦♦♦ ♦♦♦ FOR GATE WIDTHS UPTHRU6FEETORI2FEETFORDOUBLE AND LOCATED ON ALL GATES AND PERIMETER ♦♦♦♦ TENSION BAR ♦♦♦jj♦�I ♦♦♦ ♦♦♦♦ ♦♦♦�i ♦♦♦♦♦♦— �Q♦�♦ ♦�♦j♦♦ SWING GATE PER ASTM F-1083 (443)909-7200 ♦.♦ FENCES DISTANCE BETWEEN SIGNS MUST NOT.♦ 15/8"0 MIDDLE ♦j♦♦♦� I�(I ♦�♦♦♦.. ♦♦�♦♦ ♦♦♦i' ♦♦♦ ,__ � � __ j2 LINE POST 2"0 SS 40 PIPE PER ASTM-F1083 EXCEED 50' III: ��♦♦♦♦♦ BRACE RAIL ♦♦♦♦�;'u ^._ i��� ���4I ♦♦ ♦♦ 2 AFFIX APPROPRIATE COMPANY OWNER NAME AND nI y♦�♦�♦�♦ ��♦♦♦�i�,,n �'.__ ♦♦♦♦ ♦♦�� ♦♦♦ ♦♦♦♦ ♦♦ 3 GATE FRAME 2"0 SS 40 PIPE PER ASTM-F1083 4 ' BASE PLATE AND ♦�♦• ♦♦♦♦ ♦♦ .1- ♦♦♦♦♦ ♦♦♦ - �♦ CONTACT INFO DECAL TO BOTH SIGNS'A'AND'B' Ilr - � TENSION BAND ♦♦♦♦♦♦r,II CONCRETE BALLAST ��•• ♦♦♦/i ♦♦♦♦♦� - ♦♦♦♦�i \ - ♦�♦�� 4 BRACE RAIL'1-5/8"0 SS 40 PIPE PER ASTM-F1083. SIGN'C'MUST BE 111 @ 15'O C ♦♦♦j♦♦♦♦♦VIII ASSEMBLY �O♦♦', ♦♦♦♦•� ♦�♦♦ �•� ♦,��♦♦♦ ♦♦♦♦♦ 3 LOCATED ON ALL GATESED AT EYE LEVEL AND C♦♦♦♦♦ ♦♦♦♦♦'I ♦�♦ ♦1 t♦ ♦��♦�i •♦♦♦♦ ♦�♦ ♦♦♦ ♦♦♦♦♦♦♦♦♦♦♦ CUT MESH 2" ♦♦♦♦♦♦♦♦♦♦♦-w ♦♦��♦ ♦♦♦♦♦♦♦♦ ♦♦♦♦0����I ♦♦♦O♦♦ ♦♦♦♦♦���^ . 5 FABRIC 6 GA CORE WIRE SIZE 2"MESH,CONFORMING TO — M ♦♦♦♦♦ ♦♦♦♦♦ ♦♦ ♦♦♦ ♦♦♦♦ . _ _s�- ♦♦♦ ASTM-A392 ♦ ,4' CLEAR OF ♦♦♦♦♦♦♦♦♦♦�',Y ♦♦♦♦♦ -y _ - __ ___ _ _ _ , ♦♦♦♦ NO DATE REVISION DESCRIPTION �� BALLAST 11 D-101 N ! r ♦♦♦ 6 TIE WIRE MINIMUM 6 GA GALVANIZED STEEL AT POSTS AND ♦♦♦♦♦♦♦♦ FINISHED GRADE •♦♦♦♦♦ �� ♦♦ �� ♦♦ RAILS A SINGLE WRAP OF FABRIC TIE AND AT TENSION WIRE o mrsai5 RE JiGHaR1 s eaa,loN p • 3 BY HOG RINGS SPACED MAX 24"INTERVALS 4'i0° 1-1/2"MAX CLEARANCE DOUBLE GATE-PERIMETER FENCE 7 TENSION WIRE 7 GA GALVANIZED STEEL ° ` ° RFROM GRADE d a H-18" ° " NOTE IO 1 SEE"DOUBLE GATE-PERIMETER FENCE'FOR TYPICAL DETAILS S GATE LATCH 1-1/4"0 SCHEDULE 40 PLUNGER ROD W/ ° a ° a wTYPICAL FENCE PANEL-PERIMETER FENCE MUSHROOM TYPE CATCH AND LOCK,WITH FULCRUM LATCH , r 0 0 4 I CORNER,GATE, 9 GATE HINGE*INDUSTRIAL OFFSET HINGE(IOH) Ev 8 w ° L 4:, ti - END.OR PULL POST © r 9'-0= "i tO.HEIGHT=7'-0"VERTICAL DIMENSION d d �I • � '0 !`_ ° ° PROJECT ► - - -.:-.4- SIGNAGE •• ° a 1-1/2: d a ♦ D101 �o �►�_%;-==3r��� 11 FENCEFRAMEWORKTOBESS40HOTDIPPEDGALVANIZED 1,123.2kW(DC),781kW(AC) ♦ TENSIONWIRE7GA ♦♦ - IIIi!ii ♦ ♦ ♦� �� 6 GA TIES @ 12" STEEL10'x10"x1/2"p j ♦ ♦♦♦♦♦ TENSION BAR 4"0 GATE �! �5 ���i ♦�� ���♦�i ♦♦♦♦ RAISED GROUND MOUNTED cl ♦♦ POST(TYP. ♦♦ � • tl,�♦, -- ♦♦♦♦ O C (TYP) BASEPLATE 3-1/2"!Q15/60 MIDDLE BRACE ) jQl ♦♦ ;ji�.4,, ,, ♦♦♦ 12 GATE TO BE EQUIPPED WITH A KNOX-BOX 3200 SERIES 3o scH 4D GALV. PHOTOVOLTAIC SYSTEM ♦ ♦_.; ♦0FIRE DEPT BLACK RAPID ENTRYSYSTEM(OREQUAL SUNEDISONRAIL GATE HINGES, ♦ ��j ► ( ) ) 1/4I� PIPE (NY-12-0028) � 3 REQ'D EACH ♦4 ♦ O� ♦� ♦� �[►��♦ KNOXOVED SOUTHOLD LANDFILL ♦ TENSION 6110[ICm R1 O C OKNOX-BOX (4)5/80 x 4"MIN,1 ♦ ♦ ♦ ♦ ♦ EMBED HILTI KB-TZ 6155 COX LANE II p q CENTER 8 NCI.__ ♦ 2'O D GATE EXP S S. Jo ,.♦�♦,"4 BASE PLATE ASSEMBLY.' 1i BOTTOM ♦��; •.: Ir• - .� -� I-it_ SDUI'HDLD,IVI'11935 ! ♦ ♦ ♦♦ TOP,BOTTOMBti IIik •�� i ♦ ♦ I. SIDES IPI' ° d SUFFOLK COUNTY i TRUSS ROD STRETCHER ♦�i ♦♦ ♦ ♦♦ ♦ 4 a °6GA2"DIAMOND i- ° LI I ° ° a a ° BLpCX 1 � ns0) � • i4R AND♦ ii A`fi. cV?BLY ♦♦♦ii,— ♦♦1 '�♦♦♦ -^ ♦♦♦ ♦♦ ♦♦♦ 2 ♦♦♦ • 4. ♦ MESH °p , �♦, � ♦♦♦ GALVANIZED d scpte �s sRowN Jxo�ecTrwo Luwlrrrn lll�y ♦:♦: GATES .P SET I - , �♦ ♦♦�\ ♦ " ♦♦ vcoroA•re. 9n.U15 arvu� SUNEDISON • �♦�♦�♦ GATE STOP SET I1 L ��♦.j��,, �� ♦♦♦^ /�♦♦♦ •♦♦♦�� 11.►♦♦ FABRIC DRAM/Br Bwevrael cx w CONCRETE ►♦ I , 2 FINISHED GRADE � A -_ , .( dth4 - 444( tY44;_ al 1.- . .• vE 0 4 FENCE BALLAST DETAIL DRAWING T77LE 1-1/2"CO MAX CLEARANCE ° . - •° D-101 SCALE N T S 9 e FROM GRADE SITE DETAILS CORNER, GATE, END OR PULL POST- DOUBLE GATE-PAD MOUNTED FENCE NOTE 1 BASE PLATE ASSEMBLY IS TYPICAL FOR PAD DRAW/NG NO• PAD MOUNTED FENCE MOUNTED FENCE. 2 CHAIN LINK FENCE DETAILS D-101 t- D-101 SCALP N T S SHEET NO r 3 OF 20 THE COPYING OR REUSE OF THIS DOCUMENT,OR PORTIONS THEREOF,WITHOUT THE WRITTEN AGREEMENT OF WHITMAN IS PROHIBITED,COPYRIGHT 2015,WHITMAN DO NOT SCALE THIS DRAWING CU RENT DEVICE AND ELECTRICAL NOTES FOR NEW PHOTOVOLTAIC 22 ALL LV AC WIRING SHALL BE TYPE THWN2RATED AT90DEGREES C XHHW2ISANAPPROVED 5 EQUIPMENT DIODES SHALL BEH ASPHOTOVOLTAIC SOURCE HOTOVOLTAIC SIDE OF THE PHOTOVOLTAIC S DISCO BLOCKING GENERAL NOTES FOR POWER-ELECTRONICS HEC-UL AND HEC-UL+SERIES GRID ALTERNATE THIS NOTE WILL BE THWN-EDED BY ANY INVERTER SPECIFICATIONS REQUIRING LV AC DIODES SHALL PERMITTED ON THE PHOTOVOLTAIC OF DISCONNECTING TIE PHOTOVOLTAIC INVERTERS: SYSTEM: WIRE TO MEET HIGHER VOLTAGE OR INSULATION STANDARDS MEANS 1 THIS PROPOSED SOLAR ELECTRIC SYSTEM IS INTENDED TO OPERATE IN PARALLEL WITH POWER 23 USE MEYERS(OR APP EDU)HUB LISTED TO PROVIDE MOISTURE PROTECTION FOR CONDUIT ENTRANCES 6 MEANS SHALL BE PROVIDED TO DISCONNECT EQUIPMENT SUCH AS INVERTERS BATTERIES,CHARGE RECEIVED FROM THE UTILITY SERVICE PROVIDER IN ALL APPLICABLE LOCATIONS AS REQUIRED BY NEC 314 15 CONTROLLERS,AND THE LIKE FROM ALL UNGROUNDED CONDUCTORS OF ALL SOURCES IF THE 1 SYSTEM GROUNDING MEANS THIS INVERTER IS INTENDED TO BE INSTALLED EQUIPMENT IS ENERGIZED FROM MORE THAN ONE SOURCE THE DISCONNECTING MEANS SHALL BE AS PART OF A PERMANENTLY GROUNDED ELECTRICAL SYSTEM PER THE 2 THE INVERTER FOR THE PROPOSED SOLAR ELECTRIC SYSTEM SHALL BE IDENTIFIED FOR USE IN SOLAR 24.PROTECT WIRE FROM SHARP EDGES WITH UV RATED SPIRAL WRAP.EDGE-GUARD,OR SPLIT LOOM GROUPED AND IDENTIFIED NFPA 70/NATIONAL ELECTRICAL CODE(NEC) AN ENGINEERED GROUND WHITMAN /r /� l�T PHOTOVOLTAIC SYSTEMS ALL EQUIPMENT SHALL BE UL APPROVEDV V 1 MA1 TO THE EXISTING FACILITY POWER SYSTEM AT A SINGLE POINT, 25 MODULE LEAD CONNECTORS SHALL BE INSTALLED SUCH THAT THEY ARE EASILY ACCESSIBLE AND 7 A SINGLE DISCONNECTING MEANS SHALL BE PERMITTED FOR THE COMBINERS C OUTPUT OF ONE OR CONNECTION FORL L CACODEAND) AN INVERTER BE INSTALLEDD 3 THIS SYSTEM IS INTENDED TO CONNECT PROTECTED FROM EXPOSURE TO DIRECT SUNLIGHT OR RAIN THEY SHALL NOT BE INSTALLED WITHIN MORE INVERTERS IN AN INTERACTIVE SYSTEM-PROVIDED EACH INVERTER ASSOCIATED WITH THE AND CONNECTED TO THE UNIT AS DESCRIBED IN THE P-E¶SMTHWO5DI Environmental•Geotechmeal•Civil POINT OF COMMON COUPLING(POCC) THIS CONNECTION SHALL BE IN COMPLIANCE WITH THE NEC TUBING,CONDUIT OR MODULE GAPS DISCONNECT HAS ITS OWN INTERNAL AC DISCONNECT HEC-UL&HEC-UL+HARDWARE AND INSTALLATION MANUAL'THE AC AND DC Environ e•Mechanical•Geot •Eleaneal ' ARTICLE 70512'POINT OF CONNECTION BARS ARE CONNECTED TO THE MAIN INVERTER ENCLOSURE AND 26 THE STRING SOURCE CIRCUIT WIRING NEEDS TO BE SUPPORTED ADEQUATELY IN LENGTHS NOT TO 8 DISCONNECTING MEANS SHALL BE PROVIDED TO DISCONNECTA FUSE FROM ALL SOURCES OF SUPPLY IF A GROUND B BUS BA FUSE A IC CONNECTED AND THE INVERTERI IS 7 PLEASANT HILL ROAD 4 ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION FOR TESTINGEXCEED 24' THE MODULE TO MODULE INTERCONNECTION LEADS NEED TO BE SUPPORTED AT A MINIMUM THE FUSE IS ENERGIZED FROM BOTH DIRECTIONS AND IS ACCESSIBLE TO OTHER THAN QUALIFIEDPEASANT,IRO2 ISOLATION OF 12 FROM THE J-BOX AND THE MODULE TO MODULE CONNECTION POINT PERSONS SUCH A FUSE IN A PHOTOVOLTAIC SOURCE CIRCUIT SHALL BE CAPABLE OF BEING DISCONNECTED FROM THE GRID IN THE EVENT OF A GROUND FAULT RFI-(7321,NJ9051 DISCONNECTED INDEPENDENTLY OF FUSES IN OTHER PHOTOVOLTAIC SOURCE CIRCUITS FAX.(7321390-9496 5 ALL DISCONNECTING COMBINERS SHALL BE SECURED FROM UNAUTHORIZED/UNQUALIFIED PERSONNEL 27 POLARIS TAPS AND BLOCKS ARE NOT TO BE USED TO CONNECT CURRENT CARRYING CONDUCTORS 2 SYSTEM NEUTRAL REQUIREMENTS P-E HEC-UL 8 HEC-UL+INVERTERS BY LOCK OR LOCATION B ALL DISCONNECTS AND COMBINERS SHALL BE SECURED FROM UNAUTHORIZED AND UNQUALIFIED 28 MODULE TO SOURCE CIRCUIT CONNECTORS MUST BE OF THE SAME MAKE AND MODEL AS THE MODULE PERSONNEL BY EITHER LOCK OR LOCATION SHOULD NOT BE CONNECTED TO THE NEUTRAL CONDUCTOR OF THE LV B ALL DISCONNECTING COMBINERS,PULL/SPLICE BOXES,AND ENCLOSURES SHALL BE LISTED FOR ITS TO MODULE CONNECTORS THE CONNECTION TO SOURCE CIRCUITS MUST BE PER THE MODULE TRANSFORMER WINDING.THE XO SHOULD BE LEFT UNCONNECTED P-E PURPOSE MANUFACTURER AND CONNECTOR MANUFACTURER INSTRUCTIONS CONTRACTOR TO VERIFY THAT THE REQUIRED SAFETY SIGNS AND LABELS: INVERTERS ARE DESIGNED TO AUTOMATICALLY DETECT THE GRID VOLTAGE SEAL: 7 EQUIPMENT SHALL BE INSTALLED IN A SECURE AREA INVERTER PERFORMANCE MAY BE AFFECTED IF STRING CONDUCTOR DIAMETER IS COMPATIBLE WITH THE STRING CIRCUIT HOME-RUN CONNECTORS REQUIRED SAFETY SIGNS AND LABELS SHALL BE ETCHED PLACARDS PERMANENTLY ATTACHED BY ADHESIVE, BASED ON THE VOLTAGE AND PHASES ANGLES BETWEEN PHASES INSTALLED IN DIRECT SUNLIGHT OTHER MECHANICAL MEANS LABELS SHALL COMPLY WITH ARTICLE 690 OF THE NEC OR OTHER DAMAGE PROTECTION: APPLICABLE STATE AND LOCAL CODES SEE LABELS AND MARKING PAGE FOR MORE INFORMATION 3 UTILITY SIDE ISOLATION TRANSFORMER P-E HEC-UL&HEC-UL+INVERTERS 8 CONDUITS AND CABLES SHALL NOT ENTER THE TOP OF ANY OUTDOOR ENCLOSURE WITHOUT WRITTEN 1 THE ELECTRICAL CONTRACTOR SHALL CONSIDER THE WEATHERING OF EQUIPMENT OVER TIME AND APPROVAL FROM SUNEDISON PROJECT ENGINEER AND ENGINEER OF RECORD ELIMINATE THE POSSIBILITY OF DEGRADATION DUE TO CORROSION,WATER ENTRY AND UV EXPOSURE WEAR PERSONAL PROTECTIVE EQUIPMENT(PPE)APPROPRIATE FOR THE HAZARD INSULATED GLOVES WITH ARE MATCHED WITH A CUSTOM CLOSE-COUPLED HIGH EFFICIENCY MEDIUM AS A RESULT,THE USE OF UNISTRUT OR SIMILAR MOUNTING SYSTEMS IS REQUIRED TO MOUNT PROTECTORS,INSULATED MATS AND TOOLS VOLTAGE 3 PHASE STEP-UP TRANSFORMER AS PART OF THE INVERTER WIRING AND WIRING METHODS: ENCLOSURES,PULL BOXES,LOAD CENTERS,FUSE BOXES,OR OTHER EQUIPMENT ASSEMBLY THE LV WINDING CAN BE DELTA OR FLOATING WYE THE HV 1 ANY SWITCH,FUSES,OR CIRCUIT BREAKERS THAT CAN BE ENERGIZED IN EITHER DIRECTION SHALL BE WINDING CAN BE DELTA OR WYE THE OUTPUT TRANSFORMER IS USED FOR ALL WIRING METHODS AND INSTALLATION PRACTICES SHALL CONFORM TO THE NATIONAL ELECTRIC CODE, 2 ALL NEMA 4 BOXES SHALL BE EQUIPPED WITH LISTED DRAIN PLUGS INSTALLED TO ALLOW WATER TO LABELED AS FOLLOWS VOLTAGE MATCHING TO THE UTILITY VOLTAGE APPLICATION THIS LOCAL STATE CODES,AND OTHER APPLICABLE LOCAL CODES DRAIN INT I ANY MODIFICATIONTEDRATINGS TO AS-MANUFACTURED EQUIPMENT SHOULD BE DONE IN SUCH A WAY AS TO PROVIDES A BALANCED THREE PHASE CURRENT SOURCING INVERTER AND MAINTAIN ALL LISTED ELECWARTRICAL 1 EXPOSED PV SOLAR MODULE WIRING WILL BE PV WIRE OR APPROVED EQUIVALENT,BE DEGREE C,WET ELECTRICAL SHOCK HAZARD DO NOT TOUCH TERMINALS ONLY OPERATES WITH THE PRESENCE OF A STABLE UTILITY VOLTAGE RATED AND UV RESISTANT ALL EXPOSED CABLES,SUCH AS MODULE LEADS SHALL BE SECURED WITH 3 ALL NEMA 3 BOXES SHALL BE EQUIPPED WITH A WEEP HOLE OR LISTED DRAIN PLUGS INSTALLED TO TERMINALS ON BOTH THE LINE AND LOAD SIDES MAY BE MECHANICAL OR OTHER APPROVED SUN-LIGHT RESISTANT MEANS THE USE OF PLASTIC ZIP TIES IS NOT ALLOW WATER TO DRAIN ENERGIZED IN THE OPEN POSITION 4 CONDUITS AND CONDUCTORS'ALL INTERCONNECT WIRING AND POWER AN APPROVED METHOD TO SUPPORT OR ATTACH WIRE TO A STRUCTURE 2 WIRE COLOR SPECIFICATIONS 4 ALL OUTDOOR ENCLOSURES REQUIRE AN APPROVED MEANS OF DRAINAGE AND VENTILATION 2 THIS PHOTOVOLTAIC SYSTEM WILL BE EQUIPPED WITH DC DISCONNECTING COMBINERS WHICH WILL BE CONDUCTORS INTERFACING THE UNIT MUST BE IN ACCORDANCE LABELED AS FOLLOWS NFPA 70/NATIONAL ELECTRIC CODE(NEC)AND ANY APPLICABLE LOCAL AC CONDUCTORS 5 ALL ELECTRICAL CONDUIT,EQUIPMENT AND COMPONENTS MUST BE ADEQUATELY PROTECTED FROM REQUIREMENTS LARGE GAUGE WIRE MUST CONFORM TO THE DRAWING NOTES DAMAGE AND VANDALISM BY THE USE OF BOLLARDS,SHIELDS,GUARDS OR OTHER ACCEPTABLE MEANS PHOTOVOLTAIC MINIMUM BEND RADIUS SPECIFIED IN THE NEC ARTICLE 30034 CONDUCTOR 277/480 volt 1201208 volt DISCONNECTING COMBINERS 1 IF THIS DRAWING DOES NOT CONTAIN THE Phase A BROWN BLACK 6 ALL CIRCUIT BREAKERS INSTALLED THAT ARE SUBJECT TO REVERSE POWER FLOW SHALL BE LISTED AND BENDING RADIUS KEEP ALL WIRE BUNDLES AWAY FROM SHARP EDGES TO ORIGINAL SEAL OF THE PROFESSIONAL LABELED AS BACKFEED COMPATIBLE 3 THIS PHOTOVOLTAIC SYSTEM WILL BE EQUIPPED WITH AN A C DISCONNECT WHICH WILL BE LABELED AS AVOID DAMAGE TO THE WIRE INSULATION ALL CONDUCTORS SHOULD BE ENGINEER,IT IS NOT A VALID DOCUMENT PhaseB ORANGE RED FOLLOWS MADE OF COPPER AND RATED FOR 90 DEGREE C MINIMUM FOR OUTDOOR AND NO LIABILITY IS ASSUMED FOR THE Phase C YELLOW BLUEINFORMATION SHOWN Grounded Conductor GRAY or WHITE WHITE ALUMINUM CONDUCTOR INSTALLATION NOTES: PHOTOVOLTAIC INSTALLATIONS,ALL INTERCONNECT CONDUITS AND FITTINGS MUST NEMA-4 Grounded Conductor GREEN or BARE GREEN or BARE 1 MINIMUM WIRE SIZE FOR CURRENT CARRYING CONDUCTORS WHEN IMPLEMENTING ALUMINUM AS A DISCONNECTING MEANS AS REQUIRED BY THE NEC Grounding Electrode Conductor GREEN W/ORANGE GREEN W/ORANGE CONDUCTOR SHALL BE 1/0 AWG STRANDED,COMPACT ELECTRICAL GRADE AA-8000 SERIES ALLOY A C DISCONNECT 2 THIS DRAWING HAS BEEN PREPARED AS A DC CONDUCTORS 2 ALUMINUM POWER CABLE,WIRE CONNECTORS,AND INSULATING AND CODING TAPE MANUFACTURERS 4 A MARKING SPECIFYING THE PHOTOVOLTAIC POWER SOURCE RATED AS FOLLOWS SHALL BE PROVIDED 5 INVERTER ENCLOSURE P-E HEC-UL&HEC-UL+INVERTERS ARE 'D'SIZE DOCUMENT DO NOT SCALE THIS SHALL BE APPROVED BY SUNEDISON AND ENGINEER OF RECORD PRIOR TO USAGE AT AN ACCESSIBLE LOCATION AT THE DISCONNECTION MEANS FOR THE POWER SOURCE INDOOR/OUTDOOR RATED IEC GRADE NEMA 3R STAINLESS STEEL DRAWING IF IT IS PLOTTED AS ANY OTHER (e)FROM MODULE (-)FROM MODULE CONSTRUCTION WITH CORROSION PROVED POLYMERIC PAINTING C3 SIZE Floating Ground-Array Red wire or Black woe with red Yellow wire or Black wire vnih 3 WHERE BOLTED CONNECTIONS ARE NOT POSSIBLE,MECHANICAL SCREW STYLE LUGS AND OPERATING CURRENT CONSTR CTI OIS09223 Conductors markings,WHITE NOT yellow marking,WHITE NOT TERMINATIONS ARE APPROVED ONLY WHEN USED IN CONJUNCTION WITH A LISTED COPPER PIGTAIL OPERATING VOLTAGE PERMITTED PERMITTED COMPRESSION ADAPTOR(SOLID CORE PIN ADAPTERS ARE NOT ALLOWED) MAXIMUM SYSTEM VOLTAGE DC Negative Grounded or DC Positive Grounded orSHORT CIRCUIT CURRENT 6 ENVIRONMENTAL CONDITIONS P-E HEC-UL&HEC-UL+SERIES INVERTERS Negative Grounded Hag of Positive Grounded Half of 4 USE OF A-ONE-SHOT CRIMPER OR"DIE-LESS CRIMPERS'WILL NOT BE ALLOWED COMBINER ARE DESIGNED TO BE INSTALLED IN EITHER AN INDOOR OR OUTDOOR Ilit.Sun Edison" BI-Polar Inverters BI-Polar Inverters 5 COMPRESSION STYLE LUGS AND TERMINATIONS SHALL BE RATED FOR THE MAXIMUM DC end AC VOLTAGE LOCATION THE UNIT MUST BE ANCHORED TO A LEVEL CONCRETE FLOOR OR swpidymg solar OF THE SYSTEM MARKINGS: STEEL PLATFORM ALLOWABLE OPERATING TEMPERATURE RANGE FOR THE (C),2010 SUN EDISON LLC AND ITS Ungrounded Conductor (0)FROM MODULE (-)FROM MODULE 51 MUST BE PRE-FILLED WITH OXIDE INHIBITOR 1 ALL INTERACTIVE SYSTEM POINTS OF INTERCONNECTION WITH OTHER SOURCES SHALL BE MARKED AT UNIT IS-20 DEGREES C TO 50 DEGREES C THE INVERTER UNIT USES (CLAFF 201 S ALL RIGHTS RESERVED Red inre or Black wire math red Yellow mar or Black vnre with 52 WIRE STRIPPING AND BRUSHING OF CONDUCTOR IN ACCORDANCE WITH VENDOR SPECS IS REQUIRED AN ACCESSIBLE LOCATION AT THE DISCONNECTION MEANS markings yellow marking FORCED AIR COOLING FOR ALL MAJOR SYSTEM COMPONENTS THE 3-PHASE IMMEDIATELY PRIOR TO LUG INSTALLATION BALTIMORE AVE (-I FROM MODULE (C)FROM MODULE 5 3 OXIDE INHIBITOR MUST BE APPLIED TO EXPOSED CONDUCTOR IMMEDIATELY AFTER STRIPPING AND 2 A PERMANENT ETCHED PLAQUE OR DIRECTORY SHALL BE PROVIDED IDENTIFYING THE LOCATION OF THE INVERTER ASSEMBLIES ARE MOUNTED ON AN INTERNAL AIR-COOLED HEAT 12500 BALTIMORE MD AVE White woe,Graywire,or Black White wire,Gray wire,or Black BRUSHING AND IMMEDIATELY PRIOR TO INSTALLATION OF THE LUG SERVICE DISCONNECTION MEANS AND THE PHOTOVOLTAIC SYSTEM DISCONNECTION MEANS,IF NOT 0705 woe wr h white marking if inverter wire with white marking If Inverter 54 USE COMPRESSION TOOL LISTED FOR USE WITH SELECTED COMPRESSION CONNECTOR LOCATED AT THE SAME LOCATION (443)909-7200 Grounded Conductor is bi-polar,red markings must also Is bi-polar yellow marking must also 5 5 A MINIMUM IT LENGTH OF COLD OR HEAT SHRINK WITH A VOLTAGE RATING EQUAL TO THE 7 OPERATOR INTERFACE CONTROLS OPERATOR INTERFACE CONTROLS ARE - --- -beusedbe used CONDUCTOR SHALL BE APPLIED TO COVER THE CONNECTION BETWEEN CRIMP AND THE CONDUCTOR 3 ALL REQUIRED EQUIPMENT SHALL BE UL LISTED AND LABELED ACCORDINGLY LOERATORCATED NTHEFACETONT CONTROLS OPERATOR TORINTCL0CEC CONSULT BLL CNINGCTTHE AND CORRESPONDING G THE CRIMP 5 B ALL CONNECTORS AND CORRESPONDING CRIMPING TOOLS SHALL BE UL LISTED FOR THEIR THE P-E USER'S PROGRAMMING AND SOFTWARE MANUAL FOR INSTRUCTIONS Grounding Conductor GREEN or BARE GREEN or BARE SPECIFIC APPLICATION AND CODE REFERENCES 3 PV STRING HOME RUNS SHALL BE LABELED ON BOTH ENDS,AT ARRAY AND AT COMBINER COMBINER 6 INSULATING AND COLOR CODING TAPE SHALL BE PREMIUM GRADE PRESSURE SENSITIVE VINYL, OUTPUT CONDUCTORS SHALL BE LABELED AT BOTH ENDS,AT COMBINER AND AT DISCONNECT - HEAT/COLD/MOISTURE/SUNLIGHT/RESISTANT INSULATING TAPE SHALL BE BLACK AND COLOR CODING 8 ELECTRICAL SAFETY FEATURES TAPE SHALL BE FADE RESISTANT A) THE UNIT HAS ONLY ONE MODE OF OPERATION,LINE LINKAGE MODE(GRID 4 LIQUID TIGHT FLEXIBLE METAL CONDUIT IS GENERALLY SUITABLE FOR INSTALLATION IN WET AND DRY LOCATIONS SHOULD IT BE EMPLOYED,SUPPORTS WILL BE NO MORE 12 INCHES FROM BOXES(JUNCTION7 FOR ALUMINUM MV CONDUCTORS,WHERE USED,THE GUIDELINES IN THIS SECTION PLUS GENERAL EXPORT MODE) THE 3-PHASE OUTPUT VOLTAGE AND CURRENT BOX,CABINETS,OR CONDUIT FITTING)AND NO MORE THAN 38 INCHES APART(NEC 35030) REQUIREMENTS FOR MV CONDUCTOR INSTALLATION SHALL APPLY WAVEFORMS ARE SINUSOIDAL WITH LOW HARMONIC DISTORTION PER IEEE-519 HARMONIC STANDARDS 5 THE PHOTOVOLTAIC SOURCE CIRCUITS AND PHOTOVOLTAIC OUTPUT CIRCUITS OF THIS PROPOSED 8 DIRECT LANDING OF ALUMINUM CONDUCTORS IS ONLY ALLOWED TO BREAKERS WHICH ARE B) THE ANTI-ISLANDING TRIP TIME IS LESS THAN TWO(2)SECONDS AS PER NO DATE REVISION DESCRIPTION SOLAR SYSTEM SHALL NOT BE CONTAINED IN THE SAME RACEWAY CABLE TRAY,CABLE,OUTLET BOX, SPECIFICALLY RATED FOR ALUMINUM CONDUCTORS UL-1741 STANDARDS THE INVERTER WILL AUTOMATICALLY SHUT DOWN o 0:/2013 PRFLaIWNt1 311131/1411001 'cr.; JUNCTION BOX OR SIMILAR FITTING AS FEEDERS OR BRANCH CIRCUITS OF OTHER SYSTEMS UNLESS THE W CONDUCTORS OF THE DIFFERENT SYSTEMS ARE SEPARATED BYAPARTITIONORARECONNECTED WHEN THE LOSS OF GRID POWER IS DETECTED GROUNDING: C) TOGETHER INVERTER IS EQUIPPED WITH AN AC CIRCUIT BREAKER ON THE AC OUTPUT SEE ELECTRICAL DIAGRAM AND ELECTRICAL DETAILS FOR MORE GROUNDING INFORMATION D) HEC-UL+INVERTERS HAVE A FUSED DC DISCONNECT CABINET THESE B UNLESS MARKED AS UV RESISTANT,PVC IS NOT IN FOR LOCATIOION IN LOCATIONS SUBJECTED p TO DIRECT SUNLIGHT AND SHALL NOT BE EMPLOYED IN ANY SUCH LOCATION 1 ONLY ONE CONNECTION TO CIRCUITS AND ONE CONNECTION TO AC CIRCUITS WILL BE USED FOR DISCONNECT SWITCHES ARE BE USED FOR ISOLATING THE SOLAR ARRAY SYSTEM GROUNDING(NEC 690UD 42)(REFERENCED TO THE SAME POINT) PANELS FROM THE UNIT FOR MAINTENANCE AND FAULT ISOLATION C 7 LONG STRAIGHT EXPOSED CONDUIT RUNS,100 FEET OR MORE SHALL HAVE EXPANSION FITTINGS PURPOSES AND ARE TO BE USED AS A NO-LOAD DISCONNECTING DEVICE INSTALLED PER NEC 300 7(B) EXPANSION FITTINGS SHALL ALSO BE USED WHEN CONDUIT SPANS AN 2 EQUIPMENT GROUNDING CONDUCTORS AND SYSTEM GROUNDING CONDUCTORS WILL HAVE AS SHORT/ ONLY (U EXPANSION JOINT DISTANCE TO GROUND AS POSSIBLE AND A MINIMUM NUMBER OF TURNS 8 FUSES AND WIRES SUBJECT TO TRANSFORMER INRUSH CURRENT SHALL BE SIZED ACCORDINGLY 3 NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING,NOTING THAT O TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE MAYBE INSULATED BECAUSE OF I= B ALL D C MATERIALS SHALL BE UL LISTED FOR 1000V DC DC EQUIPMENT RATED TO 600V MAY BE USED PAINT/FINISH PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED WITH THE WRITTEN PERMISSION OF SUNEDISON ENGINEERING AND ENGINEER OF RECORD 4 RACKING COMPONENTS AND STRUCTURAL SUPPORTS MUST BE ELECTRICALLY BONDED TOGETHER BY AN PROJECT. E10 WHEN TRANSITIONING UNDERGROUND PVC CONDUIT TO ABOVE GROUND RMC,IMC OR EMT CONDUIT,USE ACCEPTABLE MEANS Ct) 20 MIL PIPE WRAP TAPE HALF-LAPPED FROM 6'PAST TRANSITION POINT ON PVC TO 6'ABOVE GROUND ON 1,123.2kW(DC),781kW(AC) p METALLIC CONDUIT AN EXPANSION JOINT SHALL BE USED IN THE TRANSITION TO ABOVE GROUND 5 MODULES SHALL BE GROUNDED WITH EQUIPMENT GROUNDING CONDUCTORS BONDED TO A LOCATION U CONDUIT WHERE REQUIRED BY NEC 300 5(J) APPROVED BY THE MANUFACTURER WITH A MEANS OF BONDING LISTED FOR THIS PURPOSE RAISED GROUND MOUNTED PHOTOVOLTAIC SYSTEM 11 ANY METAL SHAVINGS RESULTING FROM SITE WORK SHALL BE CLEANED FROM ENCLOSURE INTERIORS, 6 THE CONNECTION TO THE MODULE OR PANEL OF THIS PROPOSED SOLAR ELECTRIC SYSTEM SHALL BE SO Re4Non a 11 Competed 211011015 EL- TOP SURFACES OF ENCLOSURE ROOF SURFACE,AND ANY ADDITIONAL AREAS WHERE OXIDATION OR ARRANGED THAT REMOVAL OF A MODULE OR A PANEL FROM THE PHOTOVOLTAIC SOURCE CIRCUIT DOES SUN EDISON(NY-12-0028) O CONDUCTIVE METAL SHAVINGS MAY CAUSE RUST,ELECTRICAL SHORT CIRCUIT OR OTHER DAMAGE NOT INTERRUPT A GROUNDED CONDUCTOR TO ANOTHER PHOTOVOLTAIC SOURCE CIRCUIT SETS OF SOUTHOLD LANDFILL2 MODULES INTERCONNECTED AS SYSTEMS RATED AT 50 VOLTS OR LESS WITH OR WITHOUT BLOCKING J EQUIPMENT SHALL HAVE A 12 CONDUITS LONGER THAN 200'WITH NEGATIVE SLOPE TOWARD ELECTRICALDIODES,AND HAVING A SINGLE OVER CURRENT DEVICE SHALL BE CONSIDERED AS A SINGLE SOURCE6155 COX LANE Cl PULL BOX OR VAULT ADJACENT TO THE ENTRY POINT INTO THE ELECTRICAL EQUIPMENT CIRCUIT - 13 WHEN TRANSITIONING FROM FREE AIR TO CONDUCTORS IN CONDUfTA LIS7ECJNI7TING SHALL BE SOUTHOLD,NY 11935 7 GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE,INCLUDING BUT NOT LIMITED I=- USED TO PREVENT THE ENTRY OF MOISTURE TO GROUND RODS,GROUNDING LUGS,GROUNDING CLAMPS,ETC SUFFOLK COUNTY O h 14 L AND T CONDUIT BODIES SHALL NOT BE USED 8 ALL GROUNDING CONNECTIONS SHALL BE RATED FOR DIRECT BURIAL(DB RATED),CONTRACTOR IS TO 2 SUPPLY DOCUMENTATION PROVING THIS DURING PRODUCT SUBMITTALS RI OCA 1 171 O 15 ALL COPPER TERMINATION AC AND DC SHALL HAVE KOPRSHIELD OR EQUIVALENT APPLIED STALE 1s SHOWN PROJECT NO tel3 ALL EQUIPMENT GROUNDING CONDUCTORS INSTALLED SHOULD BE COPPER ONLY 14-0,11T O 16 MEGGER TESTING SHALL BE PREFORMED AT 1000 VDC FOR ALL AC CIRCUITS 480 V OR BELOW AND DCPLOT DA TE y/2y/11 C7.IF]vT St1NEDISUN W CIRCUITS 800 V OR BELOW MEGGER TESTING WILL BE PREFORMED AT 1500 VDC FOR DC CIRCUITS IN PLOT DABY pE. C2 21 ED BY TA _ 2 100D VDC SYSTEMS A MINIMUM OF 250 MEGAOHMS RESISTANCE TO GROUND IS REQUIRED DO NOT GROUND FAULT PROTECTION: Z MEGGER THE SOLAR MODULES AS THEY WILL LIKELY DAMAGE THEIR INTERNAL DIODES 1 PHOTOVOL EC INVERTERS SHALL BE EQUIPPED WITH D C GROUND FAULT PROTECTION TO REDUCE FIRE CO THE RACEWAY OR SIGNIFICANTLY CHANGE THE INTERNAL DIAMETER OF HAZARDS IISVERteldRS ARE ALSO EQUIPPED WITH ANTI-ISLANDING CIRCUITRY DRAWING TITLE 17 BENDS SHALL NOT DAMAGE RACEWAY, DISCONNECTING MEANS: 18 SUPPORT CONDUCTORS IN VERTICAL CONDUITS IN ACCORDANCE WITH THE REQUIREMENTS OF NEC 1 MEANS SHALL BE PROVIDED TO DISCONNECT ALL CURRENT CARRYING CONDUCTORS OF THE SUN EDISON NOTES .p- 30018 PHOTOVOLTAIC POWER SOURCE FROM ALL OTHER EXISTING CONDUCTORS p 19 CONNECTORS TO BE TORQUED PER DEVICE LISTING,OR MANUFACTURERS RECOMMENDATIONS 2 WHERE/CIRCUIT GROUNDING CONNECTION IS NOT DESIGNED TO BE AUTOdA71CALLY INTERRUPTED AS DRAWING NO: Ol CONNECTORS ARE TO BE MARKED WITH PERMANENT MARKING PAINT,AFTER TORQUEING PART OF THE GROUND-FAULT PROTECTION SYSTEM REQUIRED BY SECTION 680-5,A H OR CIRCUIT 'REFERENCE SUN EDISON STANDARDS BREAKER USED AS A DISCONNECTING MEANS SHALL NOT HAVE A POLE IN THE GROUNDEDNDEDy�CONDUCTOR M 00 1 20 ALL BARE CU WIRES SHALL BE INSTALLED TO NOT COME INTO CONTACT WITH DISSIMILAR METALS 3 THE GROUNDED CONDUCTOR MAY HAVE A BOLTED OR TERMINAL DISCONNECTING MEANS TO ALLOW L 111 I- MAINTENANCE OR TROUBLESHOOTING BY QUALIFIED PERSONNEL i 21 SPLICES/CONNECTORS SHALL BE INSULATED AND WILL REQUIRE PROJECT ENGINEER APPROVAL UL LISTED ELECTRICAL TAPE ALONE IS NOT SUITABLE AS THE ONLY INSULATION MEANS FOLLOW 4 UNLESS DISCONNECT IS SERVICING A LINE-SIDE TAP THE DISCONNECTING MEANS SHALL NOT BE SHEET NO N MANUFACTURERS INSTRUCTIONS FOR INSTALLATION,AND APPLICATION OF INSULATING PRODUCT REQUIRED TO BE SUITABLE AS SERVICE EQUIPMENT AND SHALL BE RATED IN ACCORDANCE WITH4 OF 20 SECTION 690-17 THE COPYING OR REUSE OF THIS DOCUMENT,OR PORTIONS THEREOF,WITHOUT THE WRITTEN AGREEMENT OF WHITMAN IS PROHIBITED,COPYRIGHT 2015,WHITMAN DO NOT SCALE THIS DRAWING , ' i I - - GROUNDING NOTE FEEDER CONDUITS BRANCH CONDUITS CIRCUIT 1 IRREVERSIBLE COMPRESSION TYPE CONNECTIONS SHALL BE USED FOR ALL DIRECT BURIAL IN EARTH OR CONCRETE I_ ro ro ro SS BOLT CONNECTIONS THAT USE BOLTS TO GROUNDING CONNECTIONS MECHANICAL MAKE CONNECTION WHITMAN ro ^o GROUNDING LUG - ARE NOT PERMITTED FOR DIRECT BURIAL GROUNDING Environmental•Geotechnical.ay)] STAINLESS STEEL\ GROUNDING WIRE CONNECTION Structural•Mechanlwl.Elecmcal , I-- —r SPLIT WASHER \ 7 PLEASANT TEL(732) ROAD ILSCO GBL-4DBTH GROUND TEl 1732)390 sass LUG OR EQUAL FAX L7321390-9496 — — — - CONCRETE TERMINATE WITH ENDBELL OR - ,, BUSHING(DO NOT CEMENT TO I jr p COUPLING)COUPLING SET FLUSH SEAL WITH CONCRETE AND CEMENT 3"---......................„..--A__ _ (\.1 IT \-- STAINLESS STEEL STAR WASHER y�,� ��p�yr�{-� `GROUND LUGGROUNDING JUNCTION BOXES STAINLESS STEEL NUT BUSHING TYPICAL DISTRIBUTION PANELBOARDS PVC CONDUIT TORQUE AS PER MANUFACTURERS NEW CONDUIT INSTALLATIONS ONLY REQUIREMENTS 35 IN-LBS 1 TYPICAL METAL CONDUIT GROUNDING DETAIL E-010 SCALE N T S 2 GROUNDING LUG DETAIL 3 SLEEVE AT SLAB E-010 SCALE'NTS E-010 SCALE NTS DRAWING NOTES _, 1.IF THIS DRAWING DOES NOT CONTAIN THE ENGINAL SEAL OF THE PRO NEER,IT IS NOT A VAL DFESSIONAL DOCUMENT AND NO LIABILITY IS ASSUMED FOR THE MODULE FRAME INFORMATION SHOWN -- 2 THIS DRAWING HAS BEEN PREPARED AS A 'D'SIZE DOCUMENT DO NOT SCALE THIS 1/4"x 3/4"SS FLANGE BOLT DRAWING IF IT IS PLOTTED AS ANY OTHER SIZE ri SMI) , - TORQUE AS PER MANUFACTURERSIIP - Sun Edison REQUIREMENTS 8 FT-LBS MIN vmp)Jymg solar ' (C),2010 SUN EDISON LLC AND ITS AFFILIATES,ALL RIGHTS RESERVED 1/4"SS FENDER WASHER12500 1I BALTIMORE AVE 20 05 j j ZEE WITH (443)909-7200 L , RAISEDED HOLES ' FE\N_ 1/4"SS FLANGE NUT GRADE-\ GRADE---\ NO DATE: REVISION DESCRIPTION I ( S 2 MODULE MOUNTING DETAIL V/ 7/0j/ / /�\ SCAMS ➢BDHmARTSnBMSSIO" W F- E-010 SCALE N.T.S. V/ /. V/47kW IRREVERSIBLE COMPRESSION ~f R 8„ GROUND GRID CROSS CONNECTOR6" GROUND#3/0 BARE COPPER • • c BURNDY TYPE YGL-C#YGL29C29 , CONDUCTOR Iii 0 FRONT VIEW SIDE VIEW EXPLODED VIEW USE EXISTING HOLES IN BUS (NO rz DRILLING OF EXISTING BUS WITHOUT 1/2. SS NUT BELOW GROUND USE TYPICAL GROUNDING WIRE APPROVAL). BOLTS USED SHALL BE / GROUND WIRE IN PROJECT ACCORDANCE IRREVERSIBLE COMPRESSION TO BUILDING COLUMN, N COMPATIBLE WITH EXISTING HOLES , 1/2" SS BELLEVILLE WASHER WITH RESIGN GROUND TAP BURNDY TYPE EQUIPMENT,ETC SIZE AS 1,123.2kW(DC),781kW(AC) (STAINLESS STEEL FASTENERS ONLY). SPECIFIED RAISED GROUND MOUNTED o /1 IliIl[ COAT BOLT THREADS WITH ANTI—SEIZE YGHC-C#YGHC29C2s COMPOUND AND TORQUE TO 1/2" SS WASHER PHOTOVOLTAIC SYSTEM 0 ,I i MANUFACTURER'S SPECIFICATIONS. SUN EDISON -12-0028 -BUS BAR COPPER GROUNDING CONDUCTOR SHALL BE ) GROUND ROD INSTALLED IN BELOW GRADE/4"PVC CONDUIT WHEN NOT 6" SOUTHOLD LANDFILL TERMINAL SHALL BE TWO HOLE LONG _TERMINAL COPPERWELD 6155 COX LANE o --I BARRABL I° COMPATIBLE WITH5/8"0x10'-0"LONG SOUTHOLD,NY 11935 t BUSSI�a� f7 sTtRaDUCTOR MATERIALS.y 1/2" SS FLAT WASHER 6 GROUND TAP DETAIL SUFFOLK COUNTY E-010 SCALE*NTS Li, BLOCK , MDlIT a � UL LISTED CRIMP RA )P 1/2" SS BOLT •- C)Lu 2000VOLTS. USE MANUFACTIMEWS 5 GROUND ROD DETAIL SCALE AS SHOWN ,PROJECT NO ,4.�,n ELOTOii 9,24/0 C'LL SUNEDISON APPROVED CRIMPING DEVICE OR4Y�1� 1 z AND CRIMP PER MANUFACTURER'S E-010 SCALE NOT TO SCALE y INSTRUCTIONS. USE-12" LENGTH OF ' TORQUE AS PER MANUFACTURERS ORAnuar PE REVIEWED BY L•it COLD %RINK TO COVER THE RECIiIREMENTS TORQUE MARK DRAWING TITLE: CONNECTION BETWEEN CRIMP AND f� BOLTCONNECTIONS FROM NUT TO o CONDUCTOR BEGINNING AT THE BOLT THREND. CONDUIT ANDGROUNDING STRAIGHT SECTION OF THE CRIMP. - DETAILS 1 I Co DRAWING NO: 5 TYPICAL DC BUS CONNECTION DETAIL �-+-010 g E-010 SCALE.NOT TO SCALE F— SHEET NO THE COPYING OR REUSE OF THIS DOCUMENT,OR PORTIONS THEREOF,WITHOUT THE WRITTEN AGREEMENT OF WHITMAN 15 PROHIBITED,COPYRIGHT 2015,WHITMAN DO NOT SCALE THIS DRAWING 5 OF 20 I NOTE PROVIDE EQUIPMENT GROUNDING CONDUCTOR BETWEEN PV ARRAY AND OTHER EQUIPMENT IN ACCORDANCE WITH NEC 250 110 WEEB-LUG-6 7 ASSEMBLY ON SOLAR MODULES RACKING PURL/N WHITMAN THIRD PURLIN FROM BOTTOM (TYP) (TYP.) Enwonme•c 1•Geol«hn,e,l•Civil Structural•Mechanical•Elecmcal TO CONNECT TO EQUIPMENT ' GROUNDING CONDUCTOR 7 PLEASANT HILL ROAD COMBINER BOX CB 32)390-5858,NJ 2 TEL FAX•(7321390-9496 • 01 I SEAL TO COMBINER I BOX SUPPORT O I l; n > 5 ) ?; 9 >;miry), 5 > i 1` r POSTI LUGUGWITH WITH U UL LISTING FOR yr- APPLICATION CONNECT MODULES TO RACKING VIA RAISED PURLIN WHERE LOCATED OR WITH WEEBS 11 5 LUG(MINIMUM OF 1 PER MODULE)(TYP) DRAWING NOTES 1 IF THIS DRAWING DOES NOT CONTAIN THE I I #3/0 BARE COPPER #3/0 BARE COPPER ORIGINAL SEAL OF THE PROFESSIONAL CONDUCTOR GROUNDING CONDUCTOR FOR ENGINEER,IT IS NOT A VALID DOCUMENT AND NO LIABILITY IS ASSUMED FOR THE 1 O #6 GREEEN INSULATED AWG(CU) CONDUCTOR(GEC) EQUIPMENT BOND INFORMATION SHOWN I (TYP.)O SEE SHEET E-210 2 THIS DRAWING HAS BEEN PREPARED AS A 'D'SIZE DOCUMENT DO NOT SCALE THIS I AC-EQUIPMENT GROUNDING 03 SEE SHEET E-200&E-201DRAWING IF IT IS PLOTTED AS ANY OTHER CONDUCTOR REFER TO MV _ SIZE SYSTEM EINFORMATIONGNINEER,AVOCA TYPICAL ah I ENGINEERING,FOR W = —— —— __ __ __ CSun Edison' umetrl Sng solar I I _-__— - _ _ _-_ (C)2010SUN EDISON,LLC AND ITS AFFILIATES,ALL EDISON, RESERVED INVERTER I )! jl (�, --,-1 I 12500 BALTIMORE AVE 1 I I TRANSFORMER _ =_:. I� (BY OTHERSTRANSFORMER -1 ; IV 1,1,:___;_i _ ;�I. BELTSVILLE,MD 20705 ---- ill #2 AWG BARE COPPER —71 (443)909-7200 - I CONDUCTOR TO PAD REBAR - _� O t VIA IRREVERSIBLE �I ,` --------- — -- -- — r COMPRESSION GROUND 1 I I;`\ _ i GRID CROSS CONNECTOR I —�fl!� i,_ i BURNDY TYPE YGL-C 1 1 #YGL34C29(TYP) l 1---- li #3/0 BARE COPPER . _ —_ CONDUCTOR GROUNDING - CONDUCTOR(GEC) ,/ (--1 I` NO. OARTE REV15 ISION IIIINARN DESCRIPTION N W 1/ \ #3/0 BARE COPPER CONDUCTOR FOR n #2 AWG BARE COPPER• 1 \ EQUIPMENT BOND 2 INVERTER AREA GROUNDING DETAIL 4 CONDUCTOR TO PAD REBAR VIA IRREVERSIBLE E-011 SCALE NOT TO SCALE S COMPRESSION GROUND \ W GRID CROSS CONNECTOR — —— —T—— BURNDY TYPE YGL-C —— — —— O #YGL34C29 0 j / \ PROJECT K a © \ RAISED GROUND MOUNTED O IRREVERSIBLE TAP(TYP) / GROUND ROD(TYPICAL 1,123,2kW(DC),781kW(AC) U E oto I NilipOF FOUR) PHOTOVOLTAIC SYSTEM SUN EDISON(NY-12-0028) 5 1 j SOUTHOLD LANDFILL _ O 6155 COX LANE SOUTHOLD,NY 11935 —— ---�-—— —— —— — — —— SUFFOLK COUNTY 0 CO RLOCKz I MI FILS 0 SCALE ♦S SHOWN FROJECTAO, 14...IST (13 W . PLOT DATE 9R•VIS C7� SIINEDIJON 2 Di VrrY p,E, REVIEWED BY CR Z 17 h TITLE TLE o _ GROUNDING DETAILS a 1 GROUNDING SCHEMATIC o E-011 SCALE:N.T.S DRAWING NO•E-0 11 ti SHEET NO• THE COPYING OR REUSE OF THIS DOCUMENT,OR PORTIONS THEREOF,WITHOUT THE WRITTEN AGREEMENT OF WHITMAN IS PROHIBITED,COPYRIGHT 2015,WHITMAN DO NOT SCALE THIS DRAWING 6 OF 2l) likieNfr NOTE ALL MATERIALS ARE ALUMINUM AND STAINLESS STEEL ( _ I 3 5 _�'\ WHITMAN E-012 E-012 r —7 j )`( ` `( I ` I E-012 NOTE: Strucnual.�idmnmuw.neaD�i1 ( = �� f REFER TO MANUFACTURERS INSTALLATION MANUALS ( FOR EXACT CONNECTION LOCATIONS AND MOUNTING 711 PLEASANT HILL ROAD 1 20 I .... ....../.......% ! I \`\ REQUIREMENTS cTANBURY.NI 08512 `� I FAX(732)390-5858 `� FAX(7321390-9496 I ii __. 4, r , I 1 IiI SEAL Air= 1 11--1 i t-t I I-1 11-1,I-11 t 1—I 1 t-t 1 f-t�ti-f�—I 1 •rt•�t-1•i r—.1; l I-1 I ISI I I-I -_-_-17---I I I I I1 l _ 1 I 1 ROW-TO-ROW HOMERUN E-012 SCALE NTS. - DRAWINGNOTES . _ 1 IF THIS DRAWING DOES NOT CONTAIN THE - ORIGINAL SEAL OF THE PROFESSIONAL ENGINEER,IT IS NOT A VALID DOCUMENT AND NO LIABILITY IS ASSUMED FOR THE INFORMATION SHOWN 2 THIS DRAWING HAS BEEN PREPARED AS A ' 'D'SIZE DOCUMENT DO NOT SCALE THIS DRAWING IF IT IS PLOTTED AS ANY OTHER SIZE `�� 0 �.. . E-012 � Sun Edison- , Z`( I E-012 �( I I s,mpldymg solar `.o.. F. �\ f AFFWATES.N EDg HISRESERVED (C),2010 SUN EDISON,LLC ANO RS �! I �1 12500 BALTIMORE AVE `�`( - ��`( BEL(443)909-7200 4 31)909-7 000705 • .. .. _ • •...... •• - 1-1 11-11 11+r1II l 1 I 1 E-1•i•r—•1 i I-I I I-I I i'i I•'-0I I—I I I I -I I —I I 1-111-111- = I-111-111-1 l — . NO DATE REVISION DESCRIPTION `_—, N - o OM4R5 PRF101PIARl SUBMISSION IL I-• — ,a - 2 ROW-TO-ROW STRING JUMPER v E-012 NTS I r S - > W2"PVC WEATHER HEAD p 2"SCHEDULE 80 PVC I' ADDITIONAL SPACER STRUT �--^— j USED FOR CONDUIT STUB-UP - -- ---.- — PROJECT II-- P1001 UNISTRUT USED FOR SUPPORT(TYP) 2 COMBINER BOX ATTACHMENT .(�. / 1,123.2kW(DC),781kW(AC) p �' 2"LIQUIDTIGHT FLEXIBLE BACKSIDE OF Z-PURLIN - - -- - JUMPER WIRES RAISED GROUND MOUNTED p `) ;�.I�� coNoulT }_� _ PHOTOVOLTAIC SYSTEM COMBINER BOX ����` 1 BACKSIDE OF SOLAR 2"PVC WEATHER HEAD a l�'- ` MODULE i JUMPER WIRES I IjI �I SIJNEDISON(NY-12-0028) n `; STRUT CLAMPED TO1= 11 COMBINER BOX _11. PVC FITTING APPROVED SOUfHOLD LANDFILL ( MOUNTING STRUT AND 1�1 FOR WET LOCATIONS(7YP.) O —'ll `� PURLIN SUPPORT •• • CONDUIT STRAP- _ • 6155 COX LANE BEAM 1�t •i CONDUIT STRAP 2 ^ ( 2"PVC SCHEDULE 80 2"LIQUIDTIGHT FLEXIBLE 1 ILill SDUTHOLD,NY 11935 ti PVC FITTING APPROVED FOR �. p WET LOCATIONS �� .•`;4' RACKING POST CONDUIT FOR ROW-TO-ROW CONDUIT Ilk SUFFOLK COUNTY II STRING JUMPERS ROUGH GRADE RLocA a Z SCHEDULE 80 PVC q — -- — _ UNDISTURBED Iico SCHEDUT E 80 PVC I LS 1u CONDUIT " :It EARTH ROUGH GRADE SCALE ASS INVN �NECINO. I.ub.IST W 2'X1'X1'CONCRETE- • ® r F CONCRETE BLOCK a IIs CU.- :• • n e ®�� 0LOrDATC SUNEDISON I 2 BLOCK - - , ORAR%RY pg REYIFIrEDR1 CR CO 1 I—I 11-1 1 — Ni—IT 1 1 1 1 I 1—I T I— 1 1 1I —1 I I- 1-111—_111-1 --4"-L-41-M- ".—`�–�- 11i_111—I .1 -- - DRAWING TITLE trl•o CONDUIT DETAILS 1 6 DRAWING NO 3 COMBINER BOX INSTALLATION DETAIL 1 ROW-TO-ROW STRING JUMPER DETAIL 5 COMBINER BOX DETAIL E-012 i E-012 SCALE N T.S SCALE NTS E-012 SCALE:N T.S. SHEET NO NTHE COPYING OR REUSE OF THIS DOCUMENT,OR PORTIONS THEREOF,WITHOUT THE WRITTEN AGREEMENT OF WHITMAN IS PROHIBITED,COPYRIGHT 2015,WHITMAN DO NOT SCALE THIS DRAWING 7 OF 20 I '— W WHITMAN PROPOSED CONDUIT ' WEATHERPROOF UV RESISTANT RUBBER PIPE SUPPORT STRAIGHT CONDUIT RUNS GREATER • STRAP(TYP) Environmental•Geot«hmcal.QvIl COMPRESSION OR EQUIVALENT(BY INSTALLATION THAN 50 FEET MUST CONTAIN Structural•Mechanical•Elecmcal FITTING CONTRACTOR)ON 3"OF GRAVEL TO CONDUIT EXPANSION FITTINGS. PROPOSED CONDUIT 7PLEASANT HILL ROAD FIXED AND/OR_ REQUIRED HEIGHT ABOVE GROUND INSTALL QUANTITY AND BARREL / QUANTITY AS NEEDED(TYP.) CRANBURY,NJ 08512 TERMINATION SETTING IN ACCORDANCE WITH NEC TEL(732)390-5858 POINT FILTER FABRIC TenCate SECTION 352.44 AND NEMA � 1� ' PIPE SOSED UVRT OR EQUIVALENT(BY FAX(7321390-9496 r Mlrafi®XSenes OR GUIDELINES •'� INSTALLATION CONTRACTOR)ON I EXISTING EQUAL I GRAVEL TO REQUIRED HEIGHT ABOVE seAc' GRADE ,G� JN GROUND I ���� ov-„e f =N PROPOSED FILTER FABRIC N, ng- ,�,q,..,.>,,,,�, a„•.+,-,..r,: z-s/. x+rsa; .r, coCY� $-"q'11i� F g�_ TenCate Mlrafi®X-Senes OR • s ,4' Q¢27 EQUAL L 4. P���c . •• m= Com!' 3 FTr 10 FT 10 FT 4 FT 3 FTyi_ erg r ',�I# ---- ---4.74...-*,�.. , ' ALL MATERIAL SHALL BE WEATHERROOF AND LISTED FOR OUTDOOR INSTALLATON - "- ' PVC CONDUIT NEC 2008 ARTICLE 352 ©CONDUIT SUPPORT iGiv SCALE N.TS. DRAWING NOTES. SUPPORTS FOR PVC 1 IF THIS DRAWING DOES NOT CONTAIN THE ORIGINAL SEAL OF THE PROFESSIONAL TRADE SIZE MAX DIST BETWEEN NOTE - ENGINEER,IT IS NOT A VALID DOCUMENT SUPPORTS CONDUIT SUPPORT DETAIL FOR ROW TO ROW JUMPERS AND NO LIABILITY IS ASSUMED FOR THE AND MEDIUM VOLTAGE CONDUIT INFORMATION SHOWN , 1/2"-1" 3 Ft 2 THIS DRAWING HAS BEEN PREPARED AS A 1 1/4"-2" 5 Ft 'D'SIZE DOCUMENT DO NOT SCALE THIS DRAWING IF IT IS PLOTTED AS ANY OTHER 2 112"-3" 6 Ft SIZE 3 1/2"-5" 7 Ft 6"AND LARGER 8 Ft VSun Edison- (( =Minutia, 1 TYPICAL CONDUIT SUPPORT PROFILE VIEW AFFILIATss,ALLOISONLRE3ERVED E-013 SCALE*N T.S 12500 BALTIMORE AVE BELTSVILLE,MD 20705 I (443)909-7200 L NO DA7F REVISION DESCRIP71ON 0 000+05 YRL11A1QlARI SI1BiLLSS10N W ' I. h tb c• 0 • (U • W 0 1 U O PROJECT - I— CO 1,123.2kW(DC),781kW(AC) c°3 RAISED GROUND MOUNTED PHOTOVOLTAIC SYSTEM aSUN EDISON(NY-12-0028) - 5SOUTHOLD LANDFILL 6155 COX LANE o - SOUTHOLD,NY 11935 O SUFFOLK COUNTY -"I 0 BLa•R I LOT 17 i O STALE AS SHOWN PROIECJNP 14dbIR CO WPLOT'DATE 9//24/IS SUENZ SUNEDISON i j DRAWN B) RE. - REVIEWED BI CA DRAWING T77LE h - o NOTE CONDUIT DETAILS COORDINATE ALL ELECTRICAL DESIGN 0 ELEMENTS WITH APPLICABLE ELECTRICAL I DRAWING NO DRAWING AND NEC REQUIREMENTS E-013 ti - SHEET NO N - THE COPYING OR REUSE OF THIS DOCUMENT,OR PORTIONS THEREOF,WITHOUT THE WRITTEN AGREEMENT OF WHITMAN IS PROHIBITED,COPYRIGHT 2015,WHITMAN DO NOT SCALE THIS DRAWING 8 OF 20 6" 6' PLACARD AND MARKINGS LEGEND(O,O,O) 0 PHOTOVOLTAIC SYSTEM 0 CUSTOMER OWNED A PLACARD FOR BREAKER IN PV-1(1 TOTAL) B PHOTOVOLTAIC MAINTENANCE DC DISCONNECTING -.7 1 INVERTER SAFETY PARALLEL GENERATION PLACARD APPLIED TO DISCONNECTING COMBINER BOX WHITMAN SA1-1 THRU SA1-12(12 TOTAL) DISCONNECT MEANS C PLACARD REQUIRED AT ALL DC EQUIPMENT E2womnental•Geotechmeal•Clod Strucnnal•Mechmueol•Eleuncal UTILITY SAFETY INCLUDING INVERTERS,COMBINER BOXES, -7 PLEASANT HILL ROAD eSunEdisson° PV-1 a RECOMBINERS,ETC(QUANTITIES AS REQUIRED) CRANBURY,N1085)2 -,.., N TEL-(732)390-5858 DISCONNECT SWITCHFAX(732)390.9496 AC DISCONNECT RATINGS: ` D. 12(SA-1THU BE1-12)EACHCOMBINERBOXTOTALOF 12(SAI-1 THRU SA1-12) 1 OPERATING CURRENT: 1492 AMPS OPERATING VOLTAGE: 360V AC E PHOTOVOLTAIC GENERATION METER GENERIC SEAL. PLACARD(1 PER METER) MAXIMUM CURRENT: 2500A/POLE •Su—...on F PLACARD REQUIRED BY UTILITY TO FIT ON OR NEAR MAXIMUM VOLTAGE: 360V AC THE XXXkV SWITCHGEAR(1 TOTAL) G PLACARD REQUIRED AT INVERTER TOTAL OF 1(PV-1) , - H PLACARD REQUIRED AT WEATHER STATIONS AND SEEDS MONITORING CABINETS(AS NEEDED) O PV-1 I SOLAR PHOTOVOLTAIC i - INVERTER - 800kW DRAWING NOTES 1 IF THIS DRAWING DOES NOT CONTAIN THE 6 /+ ORIGINAL SEAL OF THE PROFESSIONAL EO PHOTOVOLTAIC DISCONNECTING AND NO R,IT LIABILITY IS AVALID SSUMED FOR THET I AND NO LIABILITY IS ASSUMED FOR 8 ❑ 6 1/2" COMBINER BOX INFORMATION SHOWN - - 2 THIS DRAWING HAS BEEN PREPARED AS A 'D'SIZE DOCUMENT DO NOT SCALE THIS DRAWING IF IT IS PLOTTED AS ANY OTHER - MAXIMUM RATED POWER—POINT 139.5A , O SIZE • LABEL AND MARKINGS CONSTRUCTION CURRENT: ' SPECIFICATIONS MAXIMUM RATED POWER—POINT 671.4V DAS 3 t • PV SYSTEM PLACARDS •Sun VOLTAGE: PLACARDS WILLBEETCHEDWITH WHITE Edison GRAPHICS ONTO 1/16"RED PLASTIC PLACARDS s•cPNYon8 solar ° I MAXIMUM SYSTEM VOLTAGE: 937.30V , - DATA ACQUISITION SYSTEM APPROPRL IATEWILL BMATTACHED NCLOSU (C)2010 SUN EDISON LLC AND RS AFF2IATES,ALL RIGHTS RESERVED APPROPRIATE COMPONENT ENCLOSURES IN L MAXIMUM CIRCUIT CURRENT: 185.40A FOR SOLAR PHOTOVOLTAIC CONSPICUOUS PLACES USING TWO PART 12500 BALTIMORE AVE BELTSVILLE,MD 20705 ' SYSTEM it • VINYL WARNING LABELS: (443)909-7200 ' LABEL REQUIRED TO BE UV STABLE FLEXIBLE VINYL WITH ACRYLIC LAMINATE, I 5" I OPERATING TEMPERATURE OF-40°F TO 175°F AND A MINIMUM APPLICATION TEMPERATURE OF 50°F UL969 LABEL TO CONTAIN ORANGE HEADER BACKGROUND, OCA Ii T I ® N WHITE BODY BACKGROUND,AND BLACK TEXT FONT SIZES, THEANSSI25354M2EET1STTHAENDARD. TS OF— NO DATE REVISION DESCRIPTION 0 WRL9 NuELIIIDU\sn0403IaNN Lai RISK OF ELECTRICAL SHOCK. WHEN THE PHOTOVOLTAIC ARRAY IS VINYL CONDUIT LABELS ul EXPOSED TO LIGHT, A DC VOLTAGE WILL BE SUPPLIED TO THISLAMINATE,LABEL REQUIRED TO BE UV STABLE R EQUIPMENT. OPERATING TEMPERATURE OF-40°F TO 175°F AND A MINIMUM APPLICATION — o {{ TEMPERATURE OF 50°F UL969 LABEL UI 6" 1 SHALL BE RED WITH WHITE TEXT O ti SUB—ARRAY COMBINER ALUMINUMLABELLE REQUIRED REQUIRED TO BE SCREEN PRINTED,UV cl STABLE, 063"THICK,BAKE ENAMEL ALUMINUM PROJECT: CC `; SIGN SPECIFICALLY DESIGNED FOR OUTDOOR co BOX #SA 1-X USE WITH MINIMUM OF 15 YEAR LIFE.LABEL - 1,123.2kW(DC),781kW(AC) z :1REQUIRED TO CONTAIN BLACK HEADER , 01 BACKGROUND WITH WHITE TEXT INSET IN RED, RPHOTOVOLTAIC SYSTEM c y WHITE BODY BACKGROUND AND BLACK TEXT. a SUN EDISON(NY-12-0028) 5 I 4' I SOUTHOLD LANDFILL GENERAL NOTES FOR LABELS AND MARKINGS 6155 COX LANE O O ® PHOTOVOLTAIC 1 REFER TO MEDIUM VOLTAGE ENGINEER,AVOCA SOUTHOLD,NY 11935 FROM UTIILENGINEERING,FOR ITY TO INVERTER LABELING OF EQUIPMENT SUFFOLK COUNTY o GENERATION METERB(OCR 1 = 113 2 2 LABELS AND MARKINGS SHALL BE APPLIED TO THE APPROPRIATE COMPONENTS IN SCALE OS SHOWN FROIEC-1'NO. ,,,,,1ST =1 ACCORDANCE WITH THE NEC. O ?LOT BATF. WAR, Q.lEAP ]UNEDISON W 2 3 SOLAR MODULES ARE SUPPLIED FROM THE DRA0NBY 5,E. REY/F,IVFDBY CR. CO - MANUFACTURER WITH MARKINGS PRE-APPLIED DRAWING TIME: I' TO MEET THE REQUIREMENTS OF THE NEC cIn EQUIPMENT TAG SCHEDULE 1 PV SYSTEM PLACARDS DRAWING NO. Loy E-020 NOT TO SCALE E-020 sxz SHEEI'NO: N - THE COPYING OR REUSE OF THIS DOCUMENT,OR PORTIONS THEREOF,WITHOUT THE WRITTEN AGREEMENT OF WHITMAN IS PROHIBITED,COPYRIGHT 2015,WHITMAN DO NOT SCALE THIS DRAWING 9 OF 20 N PLACARD AND MARKINGS LEGEND (O,O,O 1._0" 5" 1 J LABEL REQUIRED AT ALL ELECTRICAL EQUIPMENT DISCONNECTS,COMBINER BOXES,INVERTERS,METER SOCKETS,ETC PER NEC 11016 LABEL REQUIRED TO SOLAR FIELD ON COX LANE IN SOUTHOLD CONTAIN ORANGE HEADER BACKGROUND,WHITE BODY WHITMAN O 1, `\ W4RN1NG O SYSTEM SIZE 1,123 2kWDC(781kWAC) BACKGROUND,AND BLACK TEXT LABEL FONT SIZES, lv i 1 V 1 AC&DC DISCONNECTING MEANS LOCATED AT INVERTER PAD WORDS,COLORS&SYMBOLS MUST MEET THE Environmental•Geotechmeal•Crvil � Structural•Mechanical•Electrical A - 1 -_n REQUIREMENTS OF THE ANSI Z5354-2011 STANDARD F - , I' (AS NEEDED) 7PLEASANT HILL ROAD _. _ - , CRANBURY,NI 08512 I I I K LABEL REQUIRED AT ALL EQUIPMENT DISCONNECTS, TEL/732139x5858 ARC FLASH HAZARD. i COMBINER BOXES,RECOMBINERS&INVERTERS LABEL FAX(732)390-9496 REQUIRED TO CONTAIN ORANGE HEADER APPROPRIATE PPE REQUIRED. i '�ACCESS DRIVE BACKGROUND,WHITE BODY BACKGROUND,AND BLACK --- I I I TEXT LABEL FONT SIZE,WORDS,COLORS&SYMBOLS SEAL• FAILURE TO COMPLY CAN RESULT MUST MEET THE REQUIREMENTS OF THE ANSI IN DEATH OR INJURY j I ( LI\ 25354-2011STANDARD(ASNEEDED)REFER TO NFPA 7O E• I I L CONDUIT RUNS FROM STRINGS TO INVERTER(AS L__-__ - — — J—� I 1 — — I NEEDED) I 5" { I `S M NEEDED)CONDUIT RUNS FROM INVERTER TO TRANSFORMER(AS —� PSE&G LI PMH-3 I( i mitt/ PAD-MOUNT UTILITY CT/PT ENCLOSURE I \ of N ALL 120V CONDUIT RUNS(AS NEEDED) , NARNING UNDERGROUND 13.2kVENCLO LINEIi[ 0 1.__—_--__—__7 UTILITY METERING ENCLOSURE 1 0 ALL DC CONDUITS(AS NEEDED) PAD-MOUNT 15kV SWITCH PAD-MOUNT CUSTOMER METERING 1 P 1116"PRINTED ALUMINUM CONTACT SIGN REQUIRED AT DRAWING NOTES / ENTRY GATE,RISER POLE&PAD MOUNTED ELECTRIC SHOCK HAZARD �' TRANSFORMER PAD-MOUNT 800kVA ` TRANSFORMER(AS NEEDED) 1 IF THIS DRAWING DOES NOT CONTAIN THE ih INVERTER PAD-MOUNT 800kW I ORIGINAL SEAL OF THE PROFESSIONAL DO NOT TOUCH TERMINALS. __-_ ENGINEER.IT IS NOT A VALID DOCUMENT Q SIGNS TO BE LOCATED AT EYE LEVEL ON ALL GATES,50' AND NO LIABILITY IS ASSUMED FOR THE TERMINALS ON BOTH THE LINE ` FROM EITHER SIDE OF CORNER POSTS,AND 100' INFORMATION SHOWN #.0".. ` ' RISER POLE MAXIMUM SPACING ON LINEAR FENCE RUNS AND LOAD SIDES MAY BE ENERGIZED POINT OF INTERCONNECTION 2 THIS DRAWING HAS BEEN PREPARED AS A DC ROAD CROSSING R SIGNS TO BE LOCATED AT EYE LEVEL ON ALL GATES 'D'SIZE DOCUMENT DO NOT SCALE THIS IN THE OPEN POSITION. 1 DRAWING IF IT IS PLOTTED AS ANY OTHER V A RAY� - SIZE � �� � 1 LABEL AND MARKINGS CONSTRUCTION iSPECIFICATIONS ilgSun Edison- 1 VINYL WARNING LABELS •— — — — PV SYSTEM PLACARDS simplifying solar PLACARDS WILL BE ETCHED WITH WHITE E-021 NOT TO SCALE GRAPHICS ONTO 1/16"RED PLASTIC PLACARDS AFFILIATES,AL RISHTSRE RVEO — THE LABEL WILL BE ATTACHED TO THE APPROPRIATE COMPONENT ENCLOSURES IN 12500 BALTIMORE AVE CONSPICUOUS PLACES USING TWO PART BELTSVILLE,MD 20705 ' EPDXY (443)909-7200 — • VINYL WARNING LABELS LABEL REQUIRED TO BE UV STABLE FLEXIBLE VINYL WITH ACRYLIC LAMINATE, 6" I OPERATING TEMPERATURE OF-40°F TO 175°F AND A MINIMUM APPLICATION TEMPERATURE OF 50°F UL969.LABEL TO CONTAIN ORANGE HEADER BACKGROUND, L 1000 VOLTS DCI N WHITE BODY BACKGROUND,AND BLACK TEXT LABEL FONT SIZES,WORDS,COLORS& NO DATE. REVISION DESCRIPTION oSYMBOLS MUST MEET THE REQUIREMENTS OF o pDViy pRF1pIRJMI S,BNLS ION W THE ANSI Z535 4-2011 STANDARD O 360 VOLTS AC 3 j 3 • VINYL CONDUIT LABELS I-- ',(1.0 NLABEL REQUIRED TO BE UV STABLE PRINTED ALUMINUM SIGN FLEXIBLE VINYL WITH ACRYLIC LAMINATE, W TEMPERATURE OF-40° E-021 NOT TO SCALE 1075EF ANID NG A MINIMUM APP)CAT ONF TO l O 120 VOLTS AC Z w TEMSHALL BEPERATURERED OFWITH 50°WF UL969.LABEL HITE TEXT • ALUMINUM SIGNS LABEL REQUIRED TO BE SCREEN PRINTED,UV PROJECT: 2 1,123.2kW(DC),781kW(AC) uI STABLE, 063"THICK,BAKE ENAMEL ALUMINUM 0 14" SIGN SPECIFICALLY DESIGNED FOR OUTDOOR 3'-0" USE WITH MINIMUM OF 15 YEAR LIFE LABEL OQ RAISED GROUND MOUNTED ZC O 4 O _I I REQUIRED TO CONTAIN BLACK HEADER PHOTOVOLTAIC SYSTEM LL PHOTOVOLTAIC POWER SOURCE iN BACKGROUND WITH WHITE TEXT INSET IN RED, SUNEDISON(NY12-0028) z ��� Iw' AUTHORIZED PERSONNEL ONLY WHITE BODY BACKGROUND AND BLACK TEXT 5 `V A 1 Y E�R SOUTHOLD LANDFILL 6155 COX LANE O 61/2" \�OLTA®G E o SW]Edison' q GENERAL NOTES FOR LABELS AND MARKINGS SOUTHOLD NY 11935 HIGH Ifioptiar r- 1 REFER TO MEDIUM VOLTAGE ENGINEER,AVOCA SUFFOLK COUNTY o co AUTHORIZED FOR INFORMATION CALL 888-786-3347 ENGINEERING,FOR LABELING OF EQUIPMENT RI DCK. I L•OPP I7 0 PERSONNEL ONLY FOR EMERGENCY CALL:911 FROM UTI O INVERTER SCALE AS SHOWN PROIECTAO NAN-1ST CO � — O 2 LABELS AND MARKINGS SHALL BE APPLIED TO PLOTDATF 0/24/10Ch-MOM SIINEDISON j THE APPROPRIATE COMPONENTS IN i I- 2 VINYL CONDUIT LABELS ACCORDANCE WITH THE NEC DRAWING TITLE- RFifFivmer c.R u-, SOLAR FROM THE i E-021 NOT TO SCALE 3 MANUFACTURER W THDULES ARESUPPLIED MARKINGS PRE-APPLIED v TO MEET THE REQUIREMENTS OF THE NEC EQUIPMENT TAG SCHEDULE 0 DRAWING NO• N--. z E-021 SHEET NO- N THE COPYING OR REUSE OF THIS DOCUMENT,OR PORTIONS THEREOF,WITHOUT THE WRITTEN AGREEMENT OF WHITMAN IS PROHIBITED,COPYRIGHT 2015,WHITMAN DO NOT SCALE THIS DRAWING 10 OF 20 KEYED NOTES(0,0,0,Q) ' ELECTRIC DESIGN SUBJECT TO FINAL APPROVAL FROM UTILITY IN THE EVENT OF DEVIATION BETWEEN THESE PLANS AND UTILITY 1 PROVIDE NEW TRANSFORMER-REFER TO DRAWING E-200 FOR SIZE AND REQUIREMENTS,THE UTILITY REQUIREMENTS SHALL GOVERN 11,41 ' _ QUANTITIES 2 MNI POWER CENTER,5kVA TRANSFORMER AND LOAD CENTER REFER TO E-200 I IITMAN - DRAWINGS FOR ADDITIONAL INFORMATIONEnvironmental•Geotechnlcol•Civil Structural•Mechanical•Electncal 3 POWER ELECTRONICS INVERTER REFER TO E-200 SERIES DRAWINGS FOR 7 PLEASANT BILL ROAD ADDITIONAL INFORMATION ! CRANBURY,NJ 08512 1 TEL(732)5905858 1 FAX 17321390-9496 4 PROVIDE NEW SEEDS NETWEORK ENCLOSURE SEE SHEET E-031 FOR ADDITIONAL ' INFORMATION SEAL O TRANSFORMER O 800kW INVERTER DC DRAWING NOTES: 1 IF THIS DRAWING DOES NOT CONTAIN THE ORIGINAL SEAL OF THE PROFESSIONAL ENGINEER,IT IS NOT A VALID DOCUMENT L 4--— AND NO LIABILITY IS ASSUMED FOR THE AC' V INFORMATION SHOWN , © 1 2 THIS DRAWING HAS BEEN PREPARED AS A I 'D'SIZE DOCUMENT DO NOT SCALE THIS IT--- 1 1 DRAWING IF IT IS PLOTTED AS ANY OTHER I .• 2 SIZE 1 1 I SunPEdison- ifymg solarI I IC)2010 SUN AFFILIATES,ALL RIGHTS RESERVED ( LLC AND ITS 1) HIELDED- 12500 BALTIMORE AVE CAT5E BELTSVILLE,MD 20705 (443)909-7200 1 2#12+1#12 IN 314"C I NO DATE REVISION DESCRIPTION 0 0:/24/15 PRELDIINARI SIIBMLSION ` 00 . W O In , SI O ' 4 O L Q J , DW w , 0 I K SIGNAL PROJECT z 1,123.2kW(DC),781kW(AC) 0 UNTED g RAISED GROUND PHOTOVOLTAIC SYSTEM u. 010SUN EDISON(NY-12-0028) 5 �® Actor SOUTHOLD LANDFILL 0 6155 COX LANE 0 `_`� SOUTHOLD,NY 11935 O 01** BLOCK SUFFOLK COUNTY �� 17.5I COCO SCALE AS SHOWN PROIECTNO 14-ObliT 0 1 W PLO.2A4F_ 9/24/I5 CLIENT SUNEDISON Z DRAUW BY P E REVIEWED BY CR h DRAWING TITLE- ,r) TYPICAL PHOTOVOLTAIC 4 SYSTEM MONITORING 1 PHOTOVOLTAIC SYSTEM MONITORING SCHEMATIC SCHEMATIC N DRAWING NO: E-030 SCALE NTS E_030 ti _ SHEET NO N THE COPYING OR REUSE OF THIS DOCUMENT,OR PORTIONS THEREOF,WITHOUT THE WRITTEN AGREEMENT OF WHITMAN IS PROHIBITED,COPYRIGHT 2015,WHITMAN DO NOT SCALE THIS DRAWING 11 OF 20 1 ImW,e 00-1005 endow. Q DETAIL B NOTES: - - W 7:7 © 1 CONTRACTOR TO TERMINATE ALL SENSOR O O AND POWER WIRES 117761 E 2 RTD LEADS ARE NOT POLARITY SPECIFIC GENERATION METER r" """°S,� ALL OTHER SENSOR LEADS MUST BE �7`rHITMAN I _ CONNECTED AS SHOWN _ 0 slEwu O I 3 W-300 WEATHER STATION INPUT POWER USE I L`. , ! Envv°nmencil•Geotechmcai.Gvil G-500 18-AWG Structure].MeehmucDl•Elee[ncrl bAII. 4 SENSORS LEADS MAY BE EXTENDED TO A 7PLEASANT HILL ROAD SEEDS 4 0 MAXIMUM OF 100 METERS USING 18-AWG, CRANBURY,N108512 T o 0 ® we A..Y.e 2-CONDUCTOR,TWISTED-PAIR,SHIELDED TEL.(732/390-5858 V Q " CABLE FAX.(7321390.9496 11 I 5 CONDUIT NOT REQUIRED FOR SENSOR ,ice' LEADS WATER TIGHT STRAIN RELIEF Ilk'Se- FITTINGS SHOULD BE USEDController __�_ W-300 ;;=;"'•-I-C,7 WEATHERII"� '_ IMMIllagfim 3STATION =iiECall /III` tiltiwirmlApgMIC DC r0-,- o Os"-Fi I- •-' INVERTER _DisconnecU �III 1111111IIIII�.e w � �I� — 01 Recombiner ' 61111 ' Il 000. . 111�� ■i 1 ii 1 'i�l�� Il i , ,I . . . . ...r. t____A....-- a • . IN _ - Transformer 1 DRAWING NOTES- HS ARS. DET NTAIN THE I I I ORIGINALIFTDR SEAL OF THES PROFESSIONAL UPS nw ENGINEER,IIT IS NG NOTOA VALIDCODOCUMENT 1 AND NO LIABILITY IS ASSUMED FOR THE m, INFORMATION SHOWN 12000 .N POWER SOURCE c. 2 THIS DRAWING HAS BEEN PREPARED AS A 4.04 C NOT USED 'D'SIZE DOCUMENT DO NOT SCALE THIS A SEEDS MAIN ENCLOSURE-INVERTER PAD B WEATHER STATION E-031 scale NTS SWING IF IT IS PLOTTED AS ANY OTHER E-031 Scale NTS E-031 Scale NTS DETAILS A NOTES: DETAIL E NOTES: TBI 700 001 ' Sllri Edison - 1 ETHERNET CABLES MAY BE PLUGGED INTO SWITCH IN ANY ORDER 1 PRESSURENACUUM GAUGE(26)HAS TWO m amplifying solar THAT IS CONVENIENT � IGi zOm SUN EDISON LLC AND ITS SETS OF CONTACTS TERMINALS 53,54,55 F==�- ® �� AFFIL RTES ALL RIGHTS RESERVED 2 MULTIPLE ETHERNET CONNECTIONS TO INVERTER NOT SHOWN ARE THE VACUUM SWITCH CONNECTIONS �[� - 0®® _ •• '5 y'' fel 3 LOCATION AND NUMBER OF CONDUIT RUNS MAY BE MODIFIED AS TERMINALS 50,51,52 ARE THE PRESSURE o�� �..a5.�m, e . -- „tI 12500 BALTIMORE AVE REQUIRED FOR SITE CONDITIONS SWITCH CONNECTIONS _ se ANTENNA „ HERNET BELTSVILLE,MD 20705 2 LIQUID TEMPERATURE GAUGE(13)HAS TWO _ sERwL Dc "o""� (443)909-7200 SETS OF CONTACTS.TERMINALS 11,12,13 m ARE LOW TEMP SET POINT.TERMINALS 8,9, PI m er.imw-„, o,Ledn. I 10 ARE HIGH TEMP SET POINT. (TYPICAL [.S - J SETTINGS:LOW TEMP SET AT 70 DEG C.HIGH I�' o os N ,„ .�(� .N TEMP SET AT 90 DEG C) i!o ” 3 ADAM-6060 MODULE IS LOCATED IN SEEDS `el�'�minL�w 1001010070.002115 ENCLOSURE .II i, LAI 0. 4 18 TO 20 AWG,4-CONDUCTOR SHIELDED CABLE IS RECOMMENDED FOR =itl Mortara SUC DETNM1 INTERCONNECT BETWEEN ADAM MODULE NO DATE REVISION DESCRIPTION c AND TRANSFORMER SWITCHES ADAM,. 0 09/14115 9RELAII4ARl S1IBSILSION I- O °e vO a F MODEM DETAIL 'o E-031 Scale NTS UI crrr-rrzr W -o ° NOT USED E TRANSFORMER MONITOR Er Scale NTS E-031 Scale.NTS __� PROJECT E-031 real.each wmna sheen for "'' Y .._..__.,, �� ATTENTION! ---*:�+s ,x`���.,'•� ^•�-�- I 1,123.2kW DC 781kW AC CO Y to SOCK reference.e I Mom Own me Iia;mfi - ( ), ( ) :.nno m type Is , ''i q;. i RAISED GROUND MOUNTED U T .FRONT SIDE OO I EXERCISE EYIREYE MOON. "shown hereI 2" r , C' -. =1 PHOTOVOLTAIC SYSTEM LL f*�- ,� '�, SUN EDISON(NY-12-0028) °z °". .— e 3 GENERAL NOTES: . e : 1 UNLESS SPECIFIED OTHERWISE,ALL FIBER . . — -. �'� � z.1't-,© -I SOUTHOLD LANDFILL 0 CONNECTIONS USE ST TERMINATIONS .11.1=1��' „„ „ - -.,j l 6155 COX LANE 2 2 SEEDS EQUIPMENT PROVIDED BY SUNEDISON.ALL '[[]] '��]] d giw - t- SOUTHOLD,NY 11935 ASSEMBLY,MOUNTING,AND WIRING SHALL BE `, `t d "ti tM xr © r -' ��_ _ y DONE IN THE FIELD,EXCEPT THE WEATHER FRONT SOE [..��11 [[..11 e : Is SUFFOLK COUNTY k1 ; STATIONS AND UPS. E 1 A tJ BLOCK I LOP ea .0 nfo 00 0 21 FOR W-300,COMPLETE STATION(SENSORS, 1 1 7 G t;, - A. '"'1 A U' SCALE AS SHOWN PROIEL NO 14-0bIST ADAM UNITS,AND ENCLOSURES IS Y W ) FUSES Mill I an m: ;. . ^•K f- PLOTD4TF 9/24/IS CLIENT SUNEDNON 2 PRE-ASSEMBLED FIELD CONNECTIONS SHALL z AYP ,�f�-ei a __ ER CO BE MADE FROM TERMINAL STRIP TO DC POWER A t At DRANK HI. pE REVIENEDHY A 9 ••u...'-.0-,.I,.;;?!.,-:• .-g .<- AND GATEWAY M�� IM�� �i ,.T' y DRAWING TITLE Y Gia:_ ,:":7:'—*:,L's r 2 2 ALL SENSORS USE CONNECTION WIRES 71 c�I �, . 3'� 4D PROVIDED BY THE MANUFACTURER WIRES N N . '• , :�J rrt METERING&MONITORING 0 MAY BE COILED BUT MAY NOT BE EXTENDED G„r 1+.s_ :-��. ,.._4._'- __ • DETAILS 2 3 SEE E-032 FOR MOUNTING DETAILS v Z DRAWING NO- E-031 • G NOT USED ” GENERATION METER E-031 Scale NTS E-031 Scale NTS SHEET NO NTHE COPYING OR REUSE OF THIS DOCUMENT,OR PORTIONS THEREOF,WITHOUT THE WRITTEN AGREEMENT OF WHITMAN IS PROHIBITED,COPYRIGHT 2015,WHITMAN DO NOT SCALE THIS DRAWING I2 OF 20 a- AMBIENT TEMPERATUREW- SENSOR , 411111W WEATHER STATION AMBIENT TEMPERATURE ENCLOSURE SENSOR WHITMAN — 3vSnm,,12I•ural•MechanicalGootFII•Cm!Ammon- (2)SECTIONS OF HORIZONTAL �_ rical 7PLEASANTHILLROADP1000H3 UNISTRUTti—ij ����� CFA.(321 9094912 TEL(7321390-5858 FAX.(7321 390-9496 j (2)SECTIONS OF VERTICAL iL P1000H3 UNISTRUT +•i 3!4"CONDUIT WEATHER STATION = ��IsEnL- ENCLOSURE Q ,11 SS NUT AND BOLT U D`\ dirk., I11111161 (2)SECTIONS OF VERTICAL �•I') ,-t UNISTRUT APPLIED AT EACH PIECE / ) OF ELECTRICAL EQUIPMENT FASTEN TO HORIZONTAL TO SEEDS BOX TO PYRANOMETER AND UNISTRUT WITH CONE NUTS TEMPERATURE SENSOR DRAWING NOTES ( O 1 1 IF THIS DRAWING DOES NOT CONTAIN THE [ O - Bei - - ESSIONAL - ENGINEER,ORIGINAL T IS NOT AEAL OF EVALDFDOCUMENT • ° ° AND NO LIABILITY IS ASSUMED FOR THE Z ° INFORMATION SHOWN • RACKING POST OR 3"0 •° GALVANIZED FENCE POST IN 3000 ° ° ° • °° ° 2 THIS DRAW NG HAS BEEN PREPARED ASA 'D'SIZE DOCUMENT DO NOT SCALE THIS EMBEDMENT) 1'MIN I PSI CONCRETE(MIN.24" • • 2'MIN • DRAWING IF IT IS PLOTTED AS ANY OTHER I SIZE 3000 PSI CONCRETE FOOTING A WEATHER STATION DETAIL Q fig,Sun Edison- E-032 Scale NTS SECTION A-A �t1-1-aphipas u AFFILIATES N EDRIONTS CAND ITS 12500 BALTIMORE AVE BELTSVILLE,MD 20705 (443)909-7200 MODULE RESISTANCE TEMPERATURE DETECTOR TO BE AFFIXED DIRECTLY TO THE CENTER OF A CELL ON THE BACK OF THE MODULE,HALFWAY BETWEEN THE CENTER AND SIDE FRAME,WITH SUPPLIED TAPE PYRANOMETER TO HAVE DIRECT LINE OF SIGHT TO SUN-TOP OF PYRANOMETER SHOULD BE ON THE SAME PLANE AS MODULE SURFACE-ENSURE NO DATE REVISION DESCRIPTION N F]AR1 NOTHING WILL REFLECT LIGHT ONTO OR SHADE 0 01,205 PROl1ASIIHM1SSION W ONTO PYRANOMETER I- BOTTOM OF MODULE u) Ib ..94! SOLAR CELL S r-------______ �"` S \ ,, 0 O —` P1000H3 GALV UNISTRUT ATTACHED TO RACK FOR ✓ PYRANOMETER MOUNTING 2 TO WEATHER STATION� ,, ' \ ! _ '. _AO 1,123.2kW(DC),781kW(AC) fp 1111110.11111RAISED GROUND MOUNTED c3 PHOTOVOLTAIC SYSTEM ` _ SUN EDISON(NY-12-0028) ,E SOUTHOLD LANDFILL o i \fie, _ 6155 COX LANE ID ..* , _.\\_ _ C PYRANOMETER MOUNTING DETAIL SOUTHOLD,NY 11935 ' It E-032 Scale NTS SUFFOLK COUNTY I,\yI1I f. BLOCK I La 17,1 0 u SCALE ASSHOWN PRO3£LTNO 10-00,11T W ,+ , }(.� f PLOT DATE J/!J/IS CLfFIYT SVNFDISON Z ✓`- ^..°.s DR 411W BY pE, REVIFWFA9Y fA t 1 14 , Yj i I DRAWING TITLE CII • Ni- TEMPERATURE E MOUNITNG DETAILS iJ .t _ ��y ,t �-yam DRAWING NO ....9,--.c,i"Nr.m.C>i Z B MODULE RESISTANCE DETECTOR DETAIL _ E_O32 E-032 Scale*NTS SHEET NO 1`1 THE COPYING OR REUSE OF THIS DOCUMENT,OR PORTIONS THEREOF,WITHOUT THE WRITTEN AGREEMENT OF WHITMAN IS PROHIBITED,COPYRIGHT 2015,WHITMAN DO NOT SCALE THIS DRAWING 13 OF 20 17 98' TOP OF BACKPANEL 15 98' B TOP OF BACKPANEL 82 8 54' .�. i l� II„ p lI �11g1 \ a '''''''.'''''°.‘ ��\ \\ ' I WHITMAN D y4. _ :„.....\„.,. O _:,.I O>;—.m�aa®.a._.4. �i \ :I V 1 'I 11 1 I I I,I \ ,:� \. \ ' Envlronmenell•Geocechnlcal•Cthl - O ° © r" \ 1 1 II 1 I I- Swcmral•Mechanical•Elecmcal �JII t �,wvv II I 1111. I �I m Q ca' I Qo 11' Q° I •-!I I I \\\\\4\ ,1'�-, I 1 1 ',I� v 1.' V 1 I I,I- f° 7 PLEASANT HILL ROAD "I \ \ 1 1 1 I 1 I,11,- ,- CRANBURY,N108512 I �_��. 11111/1 1 1 \\\\\\\ % e�1 1 I / �,'I I I I J I TEL.(732)390-5858 FAX(7321390-9496 O 1 �♦ l `\\ '� 1 I I I i i I t I o I E ‘,1 I I to (.— IBI h n O1D �' G/' % 1 — I 9 @ v ° I [i --111 I�I p \ '' _1:77,,,,,\,.\\ U/ II co I' I IJ .I SEAL I 111111 I I I or I, , �J B O° O° 1 I - SECTION A-A SECTION B-B 6125' H IO ° --t I 1 Cho @ 0 0 0 I [ISI II I) w i-.l ` aaa�aa— ..C1111.....,....„___o 4.o. — a � 0, 73' 1691' A— 5 63'--Y6' i (°P7—_—_—====—_---7-7:1, ®9t__ 1 . ®B!., IS'� I 1 O O I 0000��,Jl 0 DRAWING NOTES III 0 1 IF THIS DRAWING DOES NOT CONTAIN THE ORIGINAL SEAL OF THE PROFESSIONAL ENGINEER,IT IS NOT A VALID DOCUMENT AND NO LIABILITY IS ASSUMED FOR THE _ 0° INFORMATION SHOWN I I 1 I II II 9 94' 7 94' TOP OF BACKPANEL IIII Et, I A I I III II 2 THIS DRAWING HAS BEEN PREPARED AS A r TOP OF BACKPANEL to IIII O° N I N I I III II 'D'SIZE DOCUMENT DO NOT SCALE THIS SIZE / B —� I r I "el el. I I ,, IQ 7°1 I I I DRAWING IF IT IS PLOTTED AS ANY OTHER 9I, ,iit a I♦ ,I^ 2 25 !J II O I + I I III I I Ii I`' I I I I I III II Nillir 1 u n III Sun Edison' I!1h1 , I, I n II I II �� it II I �° I °� I C(IIIIIemplJlmg molar I I I I 11 II IC12010 SUN EDISON LLC AND ITS AFFILIATES,ALL RIGHTS RESERVED 1 Il I oi,IiiD ii i I111O 3 06' p l - 12500 BALTIMORE AVE IIiI " c� I M—v� ooBELTSVILLE,MD 20705 � e;_Ir� I • i_.TrNCOMrBNr i I! it •rr7611"::#111,1%;l ,',��B —� �-JI II II II I1 l'�`' (ari)sosa200 i -----"'---- , ° SECTION A-A SECTION B-B I A — 12' 14' r A WEATHER STATION ENCLOSURE(10x8x6) B SEEDS ENCLOSURE(18x16x10) E-033 Scale.NTS E-033 Scale NTS 18' 18'8X 00 17 THRU 12' NO. DATE REVISION DESCRIPTION n1 1 s' M B 6' u MAVIS MIELI MINARI SUBMISSION W f4)2)-"-TO c H\ ritKI!— �4 e o a n`a 1� gill "'I 1i"1l II i aj '11 I li - In ,IIII ItHI I I; QC°080 = �-- [ a ;1 li I Ili O A[ o I IIi I in AID iv.,1] ' 9, I I� ) „- NSI lI U m I5,,_______,____ °, ° NN I j 7 N il l 0 IC a II IL PROJECT CC 2 0 ,j o o ~r 0 m II 0 1,123.2kW(DC),781kW(AC) e i I I li a RAISED GROUND MOUNTED o U Q, r®Fue o III i IIII II I I.I� m PHOTOVOLTAIC SYSTEM i SUN EDISON(NY-12-0028) .__..j MIPAIIIMA 1. .... r _ _, o I 19 s 27 77' —6 14' 6 BOTTOM VIEW 1s 13' _ r SO6UTHO D55 XNY 11935 z I 2s 76' SUFFOLK COUNTY y 24 01' 24 01' 2 TOP OF BACKPANEL TOP OF BACKPANEL /./t O BLOCK I LO yT 17.5 - CO YI1� iIt� [I - A f� S ^1 ••• I�0—lb SCALE AS SHOWN PROJECT NO- IJAbIUr W ���a-W `I,h�-_ : kms-'r�tEas������1-i�lT,l_. '1 _ PLOT DATF y24115 CLfEAT SDNEDISON •1 'p DRAWN BY PE REITER�FDB1.CA � I r ( o m � F--- 15 93' —I 1— en_ .I - 55/ DRAWING TITLE lal o 1 I+ I _ '// SEEDS MOUNTING DETAILS e V i11i ---_-.n Baj .1 4 L�� ----- 7.4_ D SEEDS G-500 GATEWAY v E-033 Scale NTS N SECTION A-A SECTION B-B DRAWING NO E-033 z C SEEDS ENCLOSURE(24x24x10) SHEET NO 3 8-033 Scale NTS N THE COPYING OR REUSE OF THIS DOCUMENT,OR PORTIONS THEREOF,WITHOUT THE WRITTEN AGREEMENT OF WHITMAN IS PROHIBITED,COPYRIGHT 2015,WHITMAN DO NOT SCALE THIS DRAWING 14 OF 20 - I :7 4 ..1 -,2•-•--- , - \ • ''''= „ _ _ ' \ ' - „ , . . ' ---4 . . , _ _ TRUE ilfir N - -.- • .., ---,, .c.---:__.............. ,•., . . _ . _ . • , „ ., .: .. . ...... • -- - • ,..) ,./,'„ •., ,;-•, „ , --,,,,,I. :,,i;t;...,(7,, ii,,,,- VAT , • •,i) ;/ (o., ,,, , ,._ ....... , . , • . . , • , ; , _ •,,,,,,„• ,,, / -. • ,, ,. ••-,,,, \ I,/, - , ,_ " , , NATIA[IrrmAN ..„ _ _,..,.... - ,- - ,... .• ,_, , .. __ •, , , - -- -•,.„ •., - _ ..• .• • .• ,,, _. ._ - / r, / lo , I ? • • , ••\ -.Ss... , „ __ .... .,. _.. , 1- I; „ Envuonmental•Geolechsucal•Civil . t. ,. , - .1-----.. _,.., _... __-- -,,/'T : , ilk ,, _L., Structvral•Mechamcal•Elm:meal SOUTH Nikki ,- i , ... , .,,,•_... , - _.4-- - _. .,, • , ; • •• • 1 --- -'' _ - -^'.:,, ! I 1 i'7, I ,) 7 PLEASANT/DLL ROAD 1, , i • --- , I -* •,.. . _ ; -•'. -< '4.••:---•• -_:- ,• ' --- -- ,•, . . ;,.-‘'. , - - - . r,,,..•--A. rr F../ %, ;,, ,,,i . , ,A I., k , CRANBURY,NI 08512 TEL:(732)390-5858 FAX•(7321390-9496 .."1'.:,. -. 1,./.--, -: ... .• • --• ' i• r / - - -_ , 1 P 4.__ ..-.,.. -,. ,,,,t ), ‘, 1 1/f7 • ......%-..,..,. - ,-- '''' .., TRUE Ali --, ..,,,..., , . ,. 1 ‘1 , _ -=',....,. ,...„...z I ' '- s .. - ''.--•-•:-.' - *--`,-.-- \ -.7:".'',-.,-,.-- --2.r.-7-"-.7;--Z-_.--- --:-.-, >?',6;:-, / i '.1, 1, i :a MODULE , e:•,„ , _ ,••_`,...s.... -:„4,....., ,./1, _ , ./- - -- - • ' / ///,' / / SEAL: . . — AZIMUTH \Li , , - • /1‘• 2 ' ' 1--J1 .; ! NB01 , , •,.. - •-", ' . 1 q l' I p i ,. , , ,, ,‘ „ 1 • • -- -- _______ ____ _ _ - iiz; -;-- - . -• -. . -• -,---,„: -- -,,-. , ,• ... ,...,..„ --- _..,,-,.... _._._ --,,,,,,,,, .:_-__--- , / • - ---,„„...__,_ , .-‘. • _ , -- --- - - -- -. ,,, . ......, _ ... -- ---1) 1-\ \ :11'11[L-'21. • ,:l ,,,,,,........ -,-,..., ...„... ...„... • . g_..._ ___ ; .,„ •, ., _ __, .... ._ _ • • I --, \ --.. „ N •• -...'.-.-.- .....-' , ,.. \ . . N -,,...‘,".„,-..,. v----..,.--., ___..4....„,,,,,,.. ''''''..'-. / '+:- ,^`,_)- -.C., ' — -- ' \-. ' ''-'''''' --'' ''''.- --- -\'`•'t / ''''` I."-/-"..:' - ,1::7 / - . i - '' ' • \ \ • - '''-"'.....,1 Z:',---•::.--:-:----.1„---- ...,_ _ _ ___ s , - s , , \ , \. •:'\'‘, • <------- -- s•-•:-,--,- .-"'-,Z,N,:s.-:-.-:,--------'•- _... , il '.:.."1- -48 ' - - , „ ss . • • „, ,,N.,,' It ' \ ,,---."- -1 ,, ...„,-,1/4... - ',.. ,. ', ' \ • s '.. •-•',-.• 1 "-',":1'7'..-....----,.• - ---- --."7---- q 1 ' , 3 -i.--; ,-, -, ...„ , ',„ ., k •,,..„..,.., ' ---'-'s,'•:-. ) •. '-' . ' \ ' ' k ': , -.,„ ..., - -, -..... ---,_— • •-•',----,-,:;,,,...,*:-.....':-.„_-.:, -_ ------- „......" • ,,,,,,,,', , : , ,-, ,..--LI fil .I ' - , • •• -, N, N - „ --' -- -....'4 - , ,, I ,ik r r.-...-- pi ,../ /I " , \ , , , ,/ ' • , - --- -- s'!..,,, % 1 il- ; . - - -- , \ . -• , ''------.:-.:..-:- \,•.--.- -1-.:- --•• - .1, • 'c 11 s,-1 -..-, 11,: , ••,- , . • , „ _ , . •, . - - , „-,• ,,, -. -,-_- __"------, , ------..f,-,-•:.-,,z-z- -._--- -.--.. /;11; I,. fi /-5, '-':-I if / , . _ F 1 all\ PROPOSED DC CONDUITS _- - - / '' -" , \ ", " ...._ -,N-• ," - • -- , - \ / (/ DRAWING NOTES: NV, ON SUPPORTS(TYP.) , '1 " - --- , ., , „, ,. .----*_S4-,„ ... "._ ,, . , , ' -) / ,,,- • .1111.1111.4111.,111.1111..11.1111 i. Ill1..111 till All.11 ill all 111,1111 4, . ', .--, .1.311:'..1112,1.111.'..1111 Ill II .1,111.`.111 1:111.:111-,-111.!,,...c.,..'..i.........,.......i..,...,, , N s, •., , • , -.„. •:_-_, _,.. _ .,,. 'Z;ss- '' ,--- -- '. ' '1 , .,./1 1 IF THIS DRAWING DOES NOT CONTAIN THE . \ ...,;,.._. A ; . .4, 1_ / , ORIGINAL SEAL OF THE PROFESSIONAL fr7,• — ENGINEER,IT IS NOT A VALID DOCUMENT ( r (., I ) i I _1-"-- -- - -_, . --- _ •__- , __ c,- •s•r•/ ‘k: ,1 / AND NO LIABILITY IS ASSUMED FOR THE ) 1 \ '-' , ,.' , '-- ------ 1111„.111 1111011 1111 1111 0114111.111.111.1111 01111111.111 011,1111 sill ill.11 III.11 1111, ., s, , - --- , ......,--_-,_...--..---- / 1 --. ,1-111.1.111:1-111.1111.t111.-111...111 t111.:111.:111-111.-111,1-111:1111_!.11L/.114:111.1.11..:11,,..11__11,..111.` „,.., '5 „.z, „,.... ... ,, 1 - INFORMATION SHOWN / -- --- --- --- --- -- - - ---• ' 5, ................„:„ ....,,, il , • -- ,Iill iill,Ina.)i11.1111,1111 011111111111111111 111111 111111111111 111111 111111 1111.111 i111 1111.411.1 11..11 111,..11 1111,s ", -..'--‘,,i7,--..-- -..--{,L _ ,,/....--.0 : AMIIIMMINOIM. . • •.,, \ -'"-- 7,...:1\4.,.,. .... \ /..---- " / / ,.., ...., /- --- :,..111'..!:1111:1-111:'llin.111-t111'_111111111111111111111111111111111111111111/111111111.•111.*A11:1111Z:111.11L"_11.1.11.1.11.1111 „ „,.. \ -...,,,,,,.....-Z-, -----. _ , 7, •I -' , ---- 2 THIS DRAWING HAS BEEN PREPARED AS A • -/ --__ .. .--' i • 1 , s, . \ • \ \ • • ,'''‘,S.-',,S--.-- - •"-41,, ff -.,.. • \-- \ ' ' \ / \ r' ' 1 . . .. ts ---. ,...„,.,,,.....i.Eill till..iin um,Aim lino'mu mu,mu,Am'',mt....him.1,...........,...i.., , • • -.-2,-. ---,,,,,,\, • ,- ,,_ , _ —,...-; N IF SIZE DOCUMENT DO NOT SCALE THIS • • ,„, .,,, t •-_ t ,,,,, i-r---, I '''..y, , DRAWING IF IT IS PLOTTED AS ANY OTHER ' -... :1.111C-111.1.1112:1112.111.t111.A111111111:111111111111111111111111111111111111 lllll tit..,,.,,,,,..i.,..._.,..tm.,,,,,\ . 5„ „,, ,,„,,,p4,,,,,/ ;----... /1 ' „- . SIZE • \ ,`, , — -- — ' 5 -._ ..."'. \• ' -- \ 7` , '‘..,',.• '.'e4 5',. ------- AZIMIIMMIMMIIIM • .• \ \ ( \ , ., •f 1 I '•' i N.. '." '4<: )' * , - \ ,, • ,111„111 011...,,,...,,.....liml 111111 mill Illsii unit rm. inni"...inn till''...'In...." ' I \ / I;);1 1 I,)1 ' '' /,i.-r'' \-- - /-t'- I ' , . •-,_ \I - ' ., \, , - N „ • _ -, ----- . ,-- \ --- -„, , , ---- __.4111.:1111.!.1111:U111.I.M.:111,'111111111111111111111111111111111111111E/1111 11111111111111111.1.111.1.111-,.111.1111.1. i 1 I r ,„ "'-. •„„. ---__ — IMMEMISIME = , / 0 ,,,,...... , I , ; 1. N , '.. . ''...'--c- Ca / ,' / ___,c...,... 47, .. ,„. .-::-...,' .,•-• \ — _ ....,.......i„.„,„„,,„,„„,ii„„,111111111111111111111111111111 11111 1111 All 11114 I , I 1 ,„:, '„, 1!1,/ Sun Edison' k•.. ‘ • --c:;:.,) -,A -- . 1 - --- - . . , ..-111:011A111.111111.1141111111111111111111111111111111111111111111111111111111111111_',111.-%111-t / / / _ . , --Lr • o , -.. ,,, (f i .,.., , ,..„, i _. , •,, -\ 1 . •-- $ --- , - 's umgdynw. / \- s, „ , , ..., , \ % S. : 1,- -,.. --..---:\ ,iii„In 4111.1111.,III all11111i11111111 111111 1111H 11111111111 1111 1111,111.1 , ,./ ///,' ' .:4,,,./.. ..,- ,. `„ 1'-', ."'.- -- ---i__ ,z4111..?111.1.11111.111_1.111n111111111111111/11111/11111/11111111111111.1-11r;111.1.; ;1, ,///if//Is/1/111 i,/ .,.,w „,,;`,1, Tk,.C, :‘.- ' kvic,/,,,201,,,TE0%U.%ED,.R1SO.TN ILF,E0 AN.0‘,EITS0 11' '' ( '' :--' '• -- - 1111..111 TIlt,1111 1.111 till 111,11.1111 1 ', \\ \ (..74, ... .. .. , k. \ • • ..,‘ , :..111.1111,A111::111 VIII.t111,.-11n11.:;11.!,.. , 1 -- -.., -'17,•., - .1111.1111..111 1111°111 1111,11 1.1111,1111 i 1114,11.1 1111.... / 'i/1//,„IT, ...„1.111:,.11111111.111:1:111.111111 r:1111.1.111,•111n111.'.111... '' . ///y, , ... .. ,NN "<';'..' 12500 BALTIMORE AVE PROPOSED COMBINER BOX m,rm till,.. ,,Ill 4111 1,..,..v,11.:, \ , , , ,-...,,,_ „ — — ---- --- ---• / /11. I;j, i , . „ . • - 'i, •-' , / ;-7-,. '., ' - ..,..,•_ BELTSVILLE,MD 20705 -• ,1,1..".:,,, , ',... ' ..--- , ......"`: -- /, // / ,,! ,•it ;i, i , . IN,L111...111-`311,1-(111.1111411-11 tin-1-,, s \ .„ \ - '-'1,7 ,..„--- __ ,4111):111 oil vt!:!,111 !II:I'll , / i / 1,1/1/1,1,, 1.,., ,,i .,,,,, 0 y ..., ,..„, -., .,..., .., CrYP) s.,-.',.` N '- --r.S. N j N . , (443)909-7200 - ,,„„)-1.-.)„ _ ____ iii._iii_iii....lik:ili..liL.:ii..ii..ili.. , /, / i, , , . ,,,, , .C.--)N„ , ...,_v- v-5 'vv-.- N 1 111.11111 11;1111111 1111 111,41 11171.1 1114.".:.,_ „ ,,,, •,C.--., --- -,--- / ' I/ 'ii,WIT \ / P, / ;" ) , -,,,, --. -.., --‘„, -- -- 11i:(11111111111111;IN:Ai:UW.1W! .:. •• \ . • ' • / ' // / •Air . ,i 1, -- -.., - / IN....... 7.•••••. - - / / /WI Iii„/;;, P, -.\-- • ----, ,••,-.... ..„,_ -... '‘.. •,-: -.:.••:. .•.-_,' .:::: ,---, .•-•...„.-----, -- -........ . - mi.,111.ill T1111111111111111 111111 11111 1111.111 IM1.111..111 till,1114, . .,1111::111-1.111.7-1111111111111111 11111111111.1.111,1_111,:111.All ,,,, in...H., 1•1/4,-,,,,---..-,- ___-- -- --- - -__ __:, .., ' , i 4,/./',./ a/ , •),,. j 'N.,/ ,, - -- •,... -.. , • --.. - . '••• s --... ',,,, ..,,-,,,..1. - i• . -. , •, ..,,„,.., ., , '' •', \t/ . -.. \ ' ih• \ ' \-4,,, ,,-,..- -_-- ---- - — -` / ,,"/,',' ,/, ••••••••....„,,1 I;.' f ;. -•- . , --, ,_, „, 1111,1111111:'.111.1.111,!;1111 111111111.1.111'1111.1.111.t111.1,11W,111,1111..-11 1.11!.111.1.. .„ \ 7.".:;,1=,.. - ___ _ -- - , 114/;. , ...„'',; ' - —,1:-=ci,,,, '' "•-• ,-'- g '• ' .N..„-.. • .., ". :-::- ' . ..-- . AliniMEMINIMMINEIP ". • \ ', -', -- _ - --- — i• , 4 //, / ..-__ llll ti , •• ("N ,:-....:,--,..- „ •, - __,_,.. ,11,1.1.1{,,,lit:itilitlilLt.1=1:::11111:111:11:111:11:11::::ji:::!.1::,...:::!,,:::..., \ ' ‘, \ ,-- --\,,. — -- ,-- / ‘,5 /1,,p ''.---, NO DATE REVISION DESCRIP770N / ' s Ii t, .1 .' ,,/ 1 I Ank PROPOSED 7'TALL ' . •,-,7'.:, ' •••••• ::: '- • -:.• :,', ,,,.,. , •,‘-_ - •NN-: -- •--- - ' -i -- -._. 1 -• „ , , : ',•- 7_7._ -- - - • ',.//J11 il ,',/ '••-- — - 7 ,A I , 2 BALLASTED CHAIN LINK '. •F",:-.^:i:•2” *"'''.‹,-,,:--".•. ',Nr.•-• ‘ , ......„\ 4 ..1, .1 m r111 1111 iiii,m1 11111111111 111111111111 111111 11111 1111.1111 r111.1111 t,' \ '• ‘..„'„: .1/4'.,,...:, ......,',•;.„._ ,,,,,',7Z.,,,,,,:,-,,., ,*:_., -, - -,. ,^„....• 4,.._ .t.111:1.11.1Z1:1111.1111:.111,11111111111.11111111111/111111,1111/111.1111.'.:1.11:t111.:. i). \\• ,s,\ ":-7.- -- " '//JP',Iii'41 //I. ii; 1 i /. '`, .-/ ri Mr FENCE(TYP) ' -,--4.4) -...,:‘ S......37-,t' -7'...,' •--..S.'„-, ,, ,,:„, '' , •....., 4-, '- -__ --- --. f----• / 1 ‘' • \ \, 1 i\ \\ \.'",.,:'''.\\ :-----\-:-'-:---------,''1111//,''Ill- -/ ti 1 ;'''i Z tc- i 7-,--'''''' '''‘, '1 , , I ,' , ---- - --. ---- , , •. VT ,-_, .. .., _. _ ,iii„mit um!iffill 11111 MI WI 1111 1111..11i.,ill All 1111.1 ‘., ,, \ 1 „`„I,'/,, Plit. I' il -.. . , 1 , :-s Ank PROPOSED 7'TALL -._., 72,-;• ..",,,„,), . . , -- nmi.m.um!All....ill:11111111111/11111/11111111.(111.Ail...1111'.111.:111..,111...iii.: i\ ‘\\\.-',/' r i ' i / ! , '••• •••,,/ , I / .--• A 9 BALLASTED CHAIN LINK 5,Z:---4,..:,-,.\ -- ,,,„„ I, -_-=',.-/ 1// , 7 A ..„ , NW FENCE DOUBLE GATE "zE"- \\,:-,':-,, s.F.,-"5-=- -"- f `/- -...„ , ES (TYP OF 2) t-//,`-:.--4:3' • "\- I'''--.:.': '..' '''.."-:' '''''' '''''''Zil,4,"7.' - :-''''."--- .2 .-2*........ ..1.(•.c,•--.1%.".---•„,„:-. -..t111.•_11::111:...'iii.1.11L11:411::111111111,11:11iNICL:11:41:1.1:11:1.1. ..". 1, 2 il 1 ‘I/)/I y I I A: 1 -' ' N'A.; ‘'.._ ''`..- ..,>-- `'....--. '',..„', -•, -• .' \1/2: — ..„. ---- •, ____ •." I " \ i e I r , r 1 FOR SYSTEM DESIGN FROM UTILITY („k„,",----.,-,--..:.:, .--,' ,/, / IL - )t,',,,t-• S.:4.,:". -, - , -- iildill,,,Ill,111.111/41111111111111111 HMI 111111 1111,1111111 I 1/ i,'1,./i//, , \ TO TRANSFORMER REFER TO ---,-0. ,--,-,,,•:--.1,,,;.--,-,1-.--, ,C.5 .-.7.:-. ,.-----;-',..;::•r,-.=-, -• -..;‘,... f, -\I .._-•:".--,-..'',,,,::<,..,",•-, -_ --.. -,."- 7......,...,4• -- _ Jill.tilli.:111.:111.:1111.LIIT11111U1111t11111111111111111A111.t1ILL , II / 'i .', , , .'------ „ „ , /` DRAWINGS BY MEDIUM VOLTAGE 0 -,;•e_. \ 5.:,.(rif-',"-,,:,'7. -1, ... ,1-- -' ::',..'-.. NN '. ,'''s,'-'---`... , '-., ' •.s ( -.-- N / ENGINEERS,AVOCA ENGINEERS I l I/• -11 \ C 41114111111114 111 1111-11111111111 11111111111111 4111,!111 i, \ I , /,,f, , , r. '-` ,_. ,r) t",-,, ,,• • '.-= C: Irr-N-.,,:c.,\\ , .`,, "...,„ , -7”,;.,-",„-,- -- s.s,„ ,: „...,---...- ..:111.1111-.111.1111.1_111.11111111111/1111.111111111-....111-.111.1 ,, (--' ” .,.1 \•-••..., r ,., .. s .."k`•;:.„....6,,,..., N ' ' I, \ - — ", /, ,/,if /4/ ., , ' (' ./ ( '-"\N\ -,..-----,- ‘ C) ,,, , ••4 ''='-' ,',„ 1111..111.1111.1111.1 111.1111 1111.111,111,111111'I, r,, / 1„ /1 • ..,,,,--..--.'. / . PROJECT: '.•, '‘‘, ,..._ -1111.tlICt111-1-111W-11W-111,111.,11.,.11.,"`"ii-t; i ii,'.... ,,,/.• / / ./: --,,‘, 7'. PROPOSED INVERTER AREA illik 2 -=?..\,,._,. .,,,,,,A i N.,..., _...,-,,_ ---' ' t I , /A ••-':4/7' „.-' ,,i,..% ,,,,,,,,y";:l'':.-• 1,123.2kW(DC),781kW(AC) o ,. , ., ,,\ -............., , :111,%11111.'.11121.1111'.111:1., / , I,1' ,,,, ,3,"/I?, --- •:,..„....,...i.,-!,-,,,, • RAISED GROUND MOUNTED --.„ ej(),-oz,1A0 . .„, .,• .:) /, i 1////'-'-';0'.4 - / /D- - .=-,--C"\\• `---s. PHOTOVOLTAIC SYSTEM / (2 ‘' M 4. '/-..,-/f,,,y-, .;,..=;.--1.3„,:„ .:•,-,‘,..', s., •.. o .\',..i.i/1 \ ( ---•* .' • 7t,...\ s.-... ..., ,s,'--., , SUN EDISON(NY-12-0028) z . NielJ \ \- , likv.'\\h ."114N ..2..,‘„ 71,...-, , -, ^ \'' - - •., f\ I-)) --;q . PROPOSED WEATHER"Ilk SOUTHOLD LANDFILL 9 / i _( .'- )) 1 . 1"--4'1.-- :-...`-:'•--A...,:.:- .;::.... ,- .. __ , ,,', / , •!,.2.5.• „,e ,,,„,,,,,,:„.,„, ,,i„ - ..•:„ ••., -. -, -- , „ • - , )'I/4'14 / ;. STATION y e' NW 6155 COX LANE A___/ / , --.- , ,N - ( -4. c- - , - -4) ',I','%:g, /0,-,.. I CV;';, --r1 / ------,,..., -,.. -, • SOUTHOLD,NY 11935 - — '-z N-.•-.:.:, ---- -7,/,-- ,if ,1'pi'• tk', / .,-^ /I /,'%/A' ,\___---\,,--:> ,1 --„' • 7:-...11,- ,t-,-‘--- 4,a•-‘ '.\ '-- - 4-. /- - / / -'• ;/-4:.';''''‘ `i'-‘ \'`i ,"/.741'4,/':. :,. SUFFOLK COUNTY co ) / I\ -',,,--..Y' / ',/•',,-.';'''‘' •-•'" ? ,o''''://A". : USE EXISTING CONCRETE ROAD BLOCK I LOP 17.11 0 1 OVERALL ELECTRICAL LAYOUT PLAN , /,.e. •„•;,;,;,.... ,,,,1 ,,,,--; .'- ,, ,,,, .,fiii ; BLOCKS FOR CHAIN LINK FENCE SCALA AS SHOWN PROJECT NO. 1.1-06-1,T r4 L- \ .-N,'":-. ".-` ‘... •...% \ --''4:'.. ' \• .1 V- -",,,,z,,,,,-, • , ,...'4'/, i ri';''' ..' '.''bil,.';'' '1,(7 , ° E-100 SCALE 1"=50' .„2..„._-..,..-_,.- , ""--•-„,../ I / , -. , „ ',....„..-(., ALONG EASTERN ACCESS DRIVE(TYP) Lu ,a,, , /4_;.„.,,,,,,,,„,.,/ ..„ I ") :'.,...-2". ' '' ' i;,•• ., .2',. r ,'/,,.I a , Pw—LUat. 9/241S CUONT SUNED1SON GRAPHIC SCALE '-',5,•. r • 4",:: ., ,,, ,/•".; t VI,1,7,,7.• . DR A IVN BY pz REVIEWED 133,Cit. '3 ',, ,,4.5,, •, ,, ,Id. / p 00 50 0 25 50 100 200 .• f" ..,'.•,\„..` .....,":.°, "- .."--; . `,/,i; ,.; 1-- ----___ ,-7.,;-• • ' ,-.:, DRAWING 777LE ,r) ---- ---, 55 -1,. ••. .‘...•-7-•-'••,.,2•e..-<'...-- trin .IIMIIIMIMMIMIMI --1 c\..,•:-.,:-- .:,-,-.'.00",.„ ,.o, , , , i •'-', /,m•/,' / ' -, 6 -,,-„„•'`.•:',,' :,-,•',....„,--;-:,--z„-_,-,,-------- -'"-',"-•j•"" 1,- ‘,, \ OVERALL ELECTRICAL 0 (IN FEET) ,,I,r-,-.---\\c\\ - -- ":-. .--,.... .,,'- -,------....,-- ---------...:— ,.-- , \,. 1\,‘‘. :\A , ";' ', ;,',4,: /,' 4 1/ k‘c...7,-;',,,, -, ., '• 1 INCH=50 FT. --. •-.-: -.',- ( - -•"`".."'i-•..,Z,-.„1- `,,'''..,:;=":-'....- ,- -..-_:- -" , '''',...:,S ...- , ‘.. •.... ",,,,,.__-,,/•: ,•,,,,':',;,,. ,' N LAYOUT PLAN -;•-z---- • - ---'zlz-- __ - -'-•• ; ' ,\.. — --- %• , ,'P, ,, •-• ---"*„.....-ks, :,,,--71`;':.•-,--- •.,:" - % o -- "••,---,;:: •`.:,-...` .z-:--: --- •:-._ - DRAWING NO ,•`.,-.., \•, ....„,"•.,•\,--,,,..:., 2':._ ,, -",,,,,,,. --,,,,,,,,,,,,,,-,••••' -, -••-. :'•.:' --, ,-..-,----:, //', ' - :'•-„::::.•„'s '•-.:_F-,,.. _-_-.,1-----1 ., '.. •-;-,....,. ,,i .;''• -.,-...,•,%;.,,.*, ;' "\',.,--N=`‹7:7-",-,'„ : ,- ' i":•„'''..Nz-- :: 7-,----:=7-,:- - ,' -,, , s'--. „ ,--::;;•i'c'----?'.,•,,, • ils E-100 ._ ,.., ....,...,„„.....,-,N..., __ ,_ . „..... _ _. ___ -__,,,,,,:\ ,a -------- / N -. :. e SHEET NO• N THE COPYING OR REUSE OF THIS DOCUMENT,OR PORTIONS THEREOF,WITHOUT THE WRITTEN AGREEMENT OF WHITMAN IS PROHIBITED,COPYRIGHT 2015,WHITMAN DO NOT SCALE THIS DRAWING 15 OF 20 , i i TRUE 1 loik NORTH CONCRETE BARRIER W �I TM AN , (0) „ BLOCK ALONG ACCESS oreI. E]h.cal•avl ROAD(TYP) Structural O 7 PLEASANT HILL ROAD TRUE „ TEL(32)390-5858CRANBURY,NJ 2 SOUTH \/ FAX(732)390-9496 (180 I ' SEAL• MODULTRUE 1(40) E - 7,:',2,---'-',---,47, AZIMUTH Jf_r'- - ail _ c,.i.a� :,. __ _rT_ _ o _ _ _ _T_ F=z _s_�._T_:i"_-•-r, %' ,.i' r,YT.'.---;-,77,1---,_•i,. -�.', :_' rI•cq:`'t .�_ i--_,. �__ _ _'"S- >^ - I'^.. Lam' `- ':f. ' %,-':',,Y2,,-' 74-,,' -L-': - •-1`- 'v3: ✓ -;•---,•••-• .`�=t , - - -':. i _ - -�_, 1 T”n �_ _,r-•'- ' ,, L,;rF_I ) %k,"--,t, 1 ,,_ 1 .� ( •, ` ��•� % 0"- >2� `1% - ;',..-4.-',2-2,'„7.3_,Z -:C„' _!" - ,_ -yf r __ .29'.{^ ,:t�, -l`sv 4 __ t - -e } - !• �� -'f - - - - "�' `P _! 1 >- - -( '.f r-L \ - T 2iL YC, `A ',,- '"�_ V' „C.l..'l-' , s`')- •--',' JSr - .\._ \°�\-h 1'" ^.{ \V ,•- •,t,6,-8" l.~ rr, (,;r- 1�.•=n •:1' J "( ,. - fl ... ( ` - , _;,.)'', ,7 c /'-` - i!^ t-Yo�::w � � - •\� . ,�, _ �' 10'=61/2': ••�,-=1 ,� ''"rV a _ -''{- -.n - K; �r S- -._ i ,+,. �'' Z• :•r. 9'-8 1/2 <� Ir' \...o;'�r ,-;',%-...,:`- `3'-0n•}�`-ti 1_„3 { KEYED NOTES(C ,0,0) 1. 18 MEMC 325W PANELS WIRED IN SERIES EACH MODULE INCLUDES 2#10 AWG OUTDOOR AC WIRE AND CONDUIT SCHEDULE TAG LEGEND W , RATED QUICK CONNECTS FOR MODULE INTERCONNECTION DO NOT REMOVE THE QUICK CONNECTS OTHERWISE THE MODULE WARRANTY AND THE UL LISTING MAY BE ' -SYMBOL ,,,,. - _ , , �CDESCRIPTION . - _ „ . INVALIDATED - LOCATION. -VOLTAGE 5 .:.: .- -- `-WIRESIZE&TYPE. - - CON- - 7- -: NOTES,, _ - - WHITMAN A ON DRAWING DESIGNATION SEE TABLE 1 2 STRING WIRING CONNECTORS TO MATCH MODULE MANUFACTURERS SPECIFICATIONS a 360V 6 SETS OF 3#600MCM+350MCMG 6 312 REFER TO WIRE/CONDUCTOR NOTE#1 ON DRAWING E-210 _ l ( ) () O Structural•Mechanical.Eleemral PROVIDE CONDUIT FOR ALL EXPOSED DC STRING WIRING AND PROVIDE SUPPORTS AS 0 KEY NOTE DESIGNATION PER CONDUIT SUPPORT DETAIL AND NEC REQUIREMENTS.A MAXIMUM OF 18 a 360V 2#10+#10G1N 1" REFER TOWIRE/CONDUCTOR NOTE#2 7 PLEASANT HILL ROAD CONDUCTORS(9 SETS OF STRINGS WIRES)MAY BE COMBINED INTO ONE CONDUIT. �� CRANBURY,NJ 08512 CONDUIT SHALL BE SIZED WITH A MAXIMUM OF 40%FILL REFER TO WIREICONDUCTOR NOTES FOR CONDUCTOR REQUIREMENTS [ A 1 DC WIRE REFER TO TABLE 1 ON DRAWING E-210 TEL(732)390-5858 �.� FAX(73213909496 3. #6 AWG GREEN INSULATED TRUNK LINE WILL BE USED TO CONNECT THE METAL - RACKING AND MODULES TO THE COMBINER BOXES USE APPROVED UL LISTED LAY-IN a AC WIRE SIZE REFER TO TABLE ON DRAWING E-200 GROUND LUGS(ILSCO GBL-4DB OR APPROVED EQUAL) USE STAINLESS STEEL SE4L- SERRATED STAR WASHER OR OTHER APPROVED METHOD TO CREATE A DISTINCTIVE WIRE/CONDUCTOR NOTES - , SEPARATION BETWEEN DISSIMILAR METALS 1 AC CONDUCTORS SHALL BE 2000V COPPER CABLE-XLPE 4 BENTEK 1000V DISCONNECTING COMBINER BOX MODEL#BTK1O-UTS-G-1615-D200-FB INSULATION ENCORE PV WIRE OR APPROVED EQUAL REFER TO TABLE 1 ON E-210 FOR NUMBER OF STRINGS PER COMBINER CONTRACTOR SHALL FURNISH AND INSTALL CONDENSATE DISCHARGE OUTLET IN EACH COMBINER 2 600V AC AND 24V DC CONDUCTORS SHALL BE 600V COPPER CABLE BOX RITTAL#2459 000 OR APPROVED EQUAL THWN-2 INSULATION-SOUTHWIRE'NO LUBE OR APPROVED EQUAL - 5 TYPICAL FREESUN POWER ELECTRONICS 830kW INVERTER(MODEL#FS0830CU-360V 3 ARRAY STRING WIRING FROM MODULE TO COMBINER BOX SHALL BE WITH DISCONNECT CABINET(MODEL FSDK 12 L3 3 N S 1 E) #10 COPPER 2000V PV WIRE-SHOALS OR APPROVED EQUAL-RATED AT 90°C FOR EXPOSED,CONCEALED,WET OR DRY LOCATIONS,AND 6 REFER TO TABLE 1 ON DRAWING E-210 FOR MODULE AND STRING QUANTITIES SUNLIGHT RESISTANT APPROVED IN ACCORDANCE WITH THE 0 ' FOLLOWING RATINGS. 7 MINI POWER CENTER WITH 5kVA 360V PRIMARY/240V SECONDARY TRANSFORMER UL SUBJECT 4703 PV DRAWING NOTES (Z%5 5)WITH 20A PRIMARY OVERCURRENT PROTECTION AND 30A 2P SECONDARY UL 44/RHH-2/RHW-2(2000V) + PROTECTION AND(6)120V BREAKERS(10KAIC)FOR MONITORING EQUIPMENT POWER. SUB ARRAY#COMBINER /N, / 1 IF THIS DRAWING DOES NOT CONTAIN THE TRANSFORMER AND PRIMARY CIRCUIT BREAKER SHALL BE CAPABLE OF HANDLING 4 DC CONDUCTORS(CURRENT CARRYING)FROM COMBINER BOX TO BOX# I I--( r-( I--I ORIGINAL SEAL OF THE PROFESSIONAL PULSE WAVE FROM INVERTER OUTPUT AND SHALL BE APPROVED BY INVERTER - INVERTER SHALL BE 1000V PV ALUMINUM CABLE,XHHW-2 OR RHW-2 TYPICAL ENGINEER,IT IS NOT A VALID DOCUMENT 1111 AND NO LIABILITY IS ASSUMED FOR THE MANUFACTURER INSULATION-SOUTHWIRE OR APPROVED EQUAL INSTALLED IN 00 O INFORMATION SHOWN CONDUIT 5 EQUIPMENT GROUNDING CONDUCTORS FROM COMBINER TO 2 THISSIZE DRAWINGOCUHAS BEENNOT PREPARED IS A INVERTER SHALL BE 1000V COPPER PV CABLE,XHHW-2 OR RHW-2 p D' IFUMS PLOTTED SCALEYTHIS INSULATION-SOUTHWIRE OR APPROVED EQUAL INSTALLED IN 15A B DRAWINGTZE IF IT IS AS ANY OTHER CONDUIT. ' O 1 , 6 0 O Sun Edison- 15A n + vmple)Ngs•lar / IC)L2010IAT SUN EDISON LLC AND ITS 0 1 AFFILIATES,ALL RIGHTS RESERVED I^ ^ ^ 12500 BALTIMORE AVE REFER GI lull BEL(4 3)BELTSVILLE,MD 20705 MV SYSTEM ENGINEERS 1O (443)909-7200 DRAWINGS FOR CONTINUATION ' G • 20A O7 - GROUND O 2P 0 TERMINAL MINI POWER C, , CENTER SUB ARRAY#COMBINER /1 + BOX# r 1 r, r, rl ,EIMIMI NO DATE REVISION DESCRIPTION TYPICAL - iiiii o mrsols rx¢u1wAR�srBHtscloR P4 30A W 2P O O 0 `,o o . to TO MONITORING v o e 0 0 o s . O 0 O z OO INVERTER +DC BUS O © 15A ^ + PROJECT FUSE 400-0 ( I 1 ES ® IF--- 1 1,123.2kW(DC),781kW(AC) 0 _ - '—' ^ RAISED GROUND MOUNTED Alll PHOTOVOLTAIC SYSTEM 2 I TO SUN EDISON(NY-12-0028) - 5 - I COMBINER SOUTHOLD LANDFILL 9 Q INTEGRAL AC DC--- I • o BOXES G B O 6155 COX LANE O REFER TO �, O - I SOUTHOLD,NY 11935 MEDIUM VOLTAGE BREAKER --o ,� ©400A 0 ENGINEERS AVOCA ? u °1 0 ® II SUFFOLK COUNTY co ENGINEERING DRAWINGS I 1 BLOCS cDr ❑s FOR CONTINUATION I GROUND SCALE O {S SHOWN PRNBYTNO 14-06-IST h L J -DC BUS TERMINAL W - r� Q R 7"6-... E. 904/19 rL1E Z I O I ORA WNBI' p, REVIEWED BI�-NEDISON x. CO h (AC t/ DRAWING TITLE oL 1 GBUS DC ONE LINE DIAGRAM o E� GROUND 1 PHOTOVOLTAIC SYSTEM ONE LINE DIAGRAM DRAWING NO N FAULT E-200 SCALE N T S. E- 00 Alk - SENSING GEC G f CIRCUIT E-01I SHEET NO N - THE COPYING OR REUSE OF THIS DOCUMENT,OR PORTIONS THEREOF,WITHOUT THE WRITTEN AGREEMENT OF WHITMAN IS PROHIBITED,COPYRIGHT 2015,WHITMAN DO NOT SCALE THIS DRAWING 17 OF 20 TABLE 1: DC ELECTRIC SCHEDULE . �' PANEL!SUN EDISON 1326 'STRING SIZE 1 18 WHITMAN Vmp 37.3 Imp 8.72 . Environmental•Geotechnical•Civil jVOC 46 lic 9.27 Structural•Mechamcal•Elncu,cal O O - 7 PLEASANT RILL 0D CRA 82OO TEL:(732)3905858 " - - _ ,-� ,I _ _ FAX(73213909496 - FrEc 690J!{Bj(Ixh) tlEt�o ye je) _ _WIRE SIZE(DC)CoABlNER-BOX 7D DISCONNECT IN INVEREIER OPEN CO2CUiT- =RAT#'G• _ 2 CURRBiT CONO3INER-BOX•'"NU603ER OF:_ SNORTCIRCUT MAX POWER AMPS ;'MA7(_POWER� _ - -- . _ - _ -_- ;r ' '• -T07AL, sEAI.. '....FRYER. VOLTAGE(Vot)rt CONTU JJOUS AMPERAGE WIRE y ` ` Q' S7RIN(i5' AMPS(Ise)-- (Infp):' MP. VOLTAGE Wm) (AI6PS) fCCHilNti0U5- G- EQUIPMENT "- ' 1-; V-''-- T _- CURRENT - BFUSE SIZING I_ WM' - CONDUCTORS' GROUND. 'CONDUIT(S) SETS LENGTH VD% 8se x 126) „8x z 1611) ' s .(CCP?EFq ;-_ ' SA11 16 148.3 139. 937.30 671.4 185.40 . 231.38 250 200 350 . 4 ' 2" 1 523 1.324 2.07% , SA12 16 148.3 139.6 '937.30 671.4 185.40 231.38 250 200 350 4 2" 1 641 1.36% 2.11% • SAI3 16 . 148.3 139. 937.30 671.4 18540 231.38 260 200 . 350 4 2" 1 480 121% 1.96% , SA1.4 16 148.3 139. 937.30 671.4 186.40 231.38 260 200 350 4 2" 1 457 1.16% 1.90% ' SA1-; 16 148.3 139. 937.30 671.4 186.40 231.38 250 200 350 4 2" 1 424 1.07% 1.82% , PV-1 SA1-6 16 148.3 139. 937.30 671.4 186.40 231.38 250 200 350 4 2" 1 380 0.96% 1.71% SA17 16 148.3 139.5 937.30 671.4 18540 231.38 250 200 400 4 2112" 1 599 1.32% 2.07% _ SA1.8 16 148.3 139. 937.30 671.4 18540 231.38 260 l 200 350 4 2" 1 477 1.20% 1.96% , SA1-9 16 148.3 139. 937.30 671.4 18540 231.38 260 200 360 4 2" 1 477 1.20% 1.96% DRAWING NOTES. SA1-10 16 148.3 139.5 937.30 671.4 18540 231.38 250 200 350 4 2" 1 580 1.46% 221% 1,IF THIS DRAWING DOES NOT CONTAIN THE -SM-11 16 148.3 139.5 937.30 671.4 185.40 231.38 250 200 400 4 2112" 1 626 1.38% 2.13%- ORIGINAL SEAL OF THE PROFESSIONAL SAI-12 16 148.3 - 139._ 937.30 671'A 186.40 231.38 250 200 400 4 2112" 1 689 '1:51%e 2.27% ENGINEER IT A D000MENT _ AND NO LIABILITY Y IS S ASSSUMEUMED FOR THE - TOTAL'VD INCLUDES VD FROM TABLE 2 INFORMATION SHOWN • 2 THIS DRAWING HAS BEEN PREPARED AS A , 'D'SIZE DOCUMENT DO NOT SCALE THIS DRAWING IF IT IS PLOTTED AS ANY OTHER SIZE TABLE 2: DC STRING SCHEDULE �B CURRENT MODULES,;IN r CARRYING, Sun Edison CONDUCTOR-LOCATION • .Is`c-(A) --,"Imp1(A)'- _Voc•-(VDC) _Vmp;(VDC) ESTIMATED•'ONE WAY LENGTH, yD% ''- sMPl�tr�e�I� STRING` . CONDUCTOR k-. _ _ t _ -•. T- ., _ - `.. - "-- "��.--_ - _ _ . SIZE +, ...!` (AFFF'ILIAATES,ALLDRi(71TSRESERVED 325 MODULE TO COMBINER BOX 18 9.27 8.72 828 671 225 #10 0.75% 12500 BALTIMORE AVE REFER TO WIRE/CONDUIT NOTES ON E-200 SERIES DRAWINGS FOR STRING WIRE REQUIREMENTS BELTSVILLE,MD 20705 (443)909-7200 - NO DATE REVISION DESCRIPTION 0 W PB a usvms E]LIWARYSBBMISSIDN I- ' ,c2. I . v 0 W O �U PROJECT. z 1,123.2kW(DC),781kW(AC) c°5 RAISED GROUND MOUNTED PHOTOVOLTAIC SYSTEM o SUN EDISON(NY-12-0028) g SOUTHOLD LANDFILL 9 6155 COX LANE ' o SOUTHOLD,NY 11935 o . SUFFOLK COUNTY - to BLOCK. I Lor 17_5 C0 - SCALE AS SHOWN PROJECT NO- 14-06.1R WPLOT DATE 924/15 JjAM SUNEDISON Z DRAWN BY p,E, REV/EIVED BI CR CO h DRAWWG 777ZE• uS a , - ELECTRIC SCHEDULES p - DRAWING NO E-210 iSHEET NO N THE COPYING OR REUSE OF THIS DOCUMENT,OR PORTIONS THEREOF,WITHOUT THE WRITTEN AGREEMENT OF WHITMAN IS PROHIBITED,COPYRIGHT 2015,WHITMAN DO NOT SCALE THIS DRAWING 18 OF 20 TRUE /A . W NORTH) WHITMAN -IrEBYIIDN11CDml•Geotechnical.CMI TRUE Structural•McchamcCl•Eleeclnl _) SOUTH 7 PLEASANT CRANBURY�L 8512 OAD (1 - TEL.(7321390.5858 FAX 17321390-9496 i i TRUE MODULE AZIMUE SEAL: TH (180') \ y, \ \ N '-„,, N 0 I ♦ fil■i■icamG7■rttuF] il'C■Gil■■■fill■■Gilro%o . — ''-'-' ` r P ' rl>yry wi r r n DL,11.1. 3` \ ` \ - __-_ M1 `fir 111■■■1111.■■1111■Lm.... ■ilii■■■ilii■■iiilL_:al OLO ' ■1U1e1-��')..�� '\ \ . \- , - \A ♦��. 111■■■1111■■■U11■t,u�� o, ■1111■■■1111■■IIII r,;,fi�;-1 D �1 � - -- / Dl n: o q -- - , \ �., 1 ♦♦ LJ■■■L-J■■■L-2■6---��CEJ■■■GJ■■LJL__a� – _ !� c \ \ \ '. `50 – __ - \ i C8 \ \ . 1 \ `` 5 - DRAWING NOTES. `♦♦ \\ f \ J } \ PROPOSED COMBINER BOX SA1-1 \ O \ \ \ N • \ `� r- ` 1 IF THIS DRAWING DOES NOT CONTAIN THE n n -- ro i■ n II rr -.L-11...4i■ n • rr pg pi f- r{� n PI is I \ .-rte ` ` ORIGINAL SEAL OF THE PROFESSIONAL `♦♦ --- 1■■3■1111■■■1111■Ll�i�':0 ■1111■■■1111■■■Ili:'}` "nil■■■Ilil■■■Illi■■eg u niu■■1111■■■unLL1�--. ■■Ilii■■■1111■■■IL::1m– 1■■1111■■1111■■IIIILIl }�I\ , i - `� ` TC 'NMI:11.••11111.1 ".. ■1111■■■1111■■■111'--. 1■■■1111■■■IIIIi■t•,". 1111■■■1111■■■11111--"' ■■1111■D■1111■■■It',"–. 1■■111!■■1111■■IIIIr--"' ` ENGINEER,IT IS NOTAVALID DOCUMENT -_ _ olmol _ — - Us_tvS.1t} 1. ,.}y<–„.t _ Us,_}iy OSFF-4Dt� _ [arae-sci, \ • �, \\ �'` \` _\- 1 AND NO LIABILITY IS ASSUMED FOR THE s. ~- INFORMATION SHOWN \ — 5— _/ / PROPOSED COMBINER BOX SA1-2 �, �.\ 2 THIS DRAWING HAS BEEN PREPARED AS A aS' i i■■�ii■■Mill■r-•=-`. tri■■�ril■■■Iri•--7 i1■■■■Iiil■■■■fiT--ril■■■■i iVEME■Uir--. II ill■■■blit--:- ■■bil■■■iril■■■G –� -1■■Iiil■■fill■■IrrlP--' 'D'SIZE DOCUMENT DO NOT SCALE THIS .""•6',0 •A. LL Ia�J liNu't l'1 Lal}vetl ILV�I-SCI LLL}]�'!i7 ILSFFv iii [,L:f},3J ` ` 1■ii'li■IMIII■L_..-,�MII■■■w111■■■111 _��111■■■■illi■■■■IIIL___�illIEM■■IIII■■■■111L_ 1111■■■■1111■■■1101L__..iiM■■1111■■■1111■■■iL:l_� i11■■1111■■1111■■Ii IIL_ ,..1\ DRAWING IF IT IS PLOTTED AS ANY OTHER ...AV', 1■■■MIENUMBI■r-"" MI■■■B111■■■111'-,–. IMEMENi111■■■■I11I-,�. Ili■■■■IIII■■■■ill�--. Ili■■■■1I11■■■I111r ag ■■1111■■■1111■■■1! 1■■1111■■1111■■IIIIr--"' �, ` SIZE : "J■■ii■iii■L___ ii■■SJ■irk •.Imo]'-© .- uv}I;ry .. eu.}2�i1 p ttt}v kJt� uiaFf \ l' ]l`i'`A _r iii■■■■WAMMCOLi __ANA■■■r.LAMM MML'i___ULA■■■■iAMMM6�6__ UMEMINAMMEMM■■■L'____.J■■6AME6J■■1maL__..0 ,\ •.- �.30` .0/ -(-PROPOSED COMBINER BOX SA1-3 \ 1 •..., ♦ fii�■■Foes■■fiilr�r�.��■ Pi ■■■ PI ra 11 1, - m■ it 1 11 ■ 1 ,1 1 1 P P -- •• P rr - SIligun Edison W4}]i 7 k}va:7 l ly}I a 1 l9,k}]letl U,t}1D Ul s}v tG1 l i vSv/ 11:■■I11r■■I11:L_...: Glill■GCiill■■■111.___ Ili■■■■111i■■■■iIIL___ III■■■■1111■■■■IIIL___ Ili■■■■illi■■■■illL___.111■f■1111■■■Illi■■L..:._ 11111■■1111■■■I111L__... \ �q,fYNs `♦ 11�■■1111•■■IIIisr–"" ■1111■■■1111■■■111'--.,, Ili■■■■illi■■■■I11r--� 111■■■■1111■■■■IIII Ili■■■■1111■■■■illi -, III■■■1111■■■IIII■■rwmm, 1111■■■IIII■■■111IFD1.wS,5u3 i w. ♦ mmSBtA) i:Fty a 14.,wi ➢ mGf}�IfT Lill .. D� IN I _ - , ♦ , \ 10)2010 SUN EDISON,LLC AND ITS 1 - _- _- .-- -_ i i AFFRIATES,ALL RIGHTS RESERVED ♦ _ - — — PROPOSED COMBINER BOX SA1-4 I •\ 12500 BALTIMORE AVE `♦♦ __ 1 Iii II PI �.- PI i PI II 1,.. .,./1 11 'I 11!_}v[lilii I it o- .._ 'I 1 ..„,.. _..P H rr lq„4„:.D RI - 1i ( BELTSVILLE,MD 20705 e lue■■enlee■n1uL':...._ ■un■r.■un■■■ul.'___. u■■■mu1■■■■1iuL___. u■■■iiul■■■1nlLiii■■■■;in■o■■iiuL___-liu■■■un■■nin■L_.... ■un■■■.0 i (443)909-7200 111■■■u11■■■u i.ri7.•” ■iiue■•illi•■■n1•--. I I■■■■i111■■■■IIII!- - I i■■■■illi■■■■iillr--- Ill■■■Illu■■■1111r--. )u■■■1111■■■1111■r ... -••' 9■■!11 _ _ I ,Lv1� __ __ ___lli.F id,) • lii_}�Ll,� •• V_}]tell,) L- •LmL�iL1- liSalt�}7 UIIls}]u'(j _ .— ' I I i ♦♦ I 1 N rr r■ /\ -- r■ 1• 1■ 11 II II 11 / 1 II -- pg pi I ♦ \ l9*}}vS�➢ Ll 4 li lel�+}v.IIU� liyh]Lt9] 11-,.}]moi,;] ) _ ♦` �; 'II!■I/1111■■■1111■L_.... ■Ifa■■■Ilii■■■IIL�� lit■■■■illi■■■■.111L__i ii/■■■■1111■L■■1111 L'___.Ii1■■■lilll■■■illi■L_L... ■IIII■■■111I 111■■■:1.11■■■IIII■ru,}};,,i)�7 ■IIn�■i1111■■■Illi,lnt l�_-!)l■■■■IIII■■■■IIIIrmi,,}u�a���■■_ ■■illi■`■■illirN;,tti,,1•I)i■■■■illi■■■II)I.li.�s�aln uu.}���17■■111 ♦ 5 / ` _ _ - •• I ♦ .. \ PROPOSED COMBINER BOX SA1-51� r r (/ j' / I /! _ - - NO DATE- REVISIONDESCRIPTION • ri r! pi IL n !VIII LI ii ■■liil■■i■lilt-_'- -l■■■■./AUELAME74•-"I11■brl■■■brl lol ♦�'�•- r `,1 111■■■nil■■■1111■C-""1' 01 ■1111■■OIInO■■ilii 0'..': l■■■■Illi■■i■IIIIL---ai1■■■■illl■■■illl■L` ::0 Y■111!■■■IIII i o cams wmomunlsae/nc+mN IA �' – 1 1111■■■1111■■■1111■r a „'ill■1111■■■1111■■■IIR ��,��)l■■■■ilU■■i■Ullruw}v4�1(l■■■■illi■■■IIII■r6�u�i�l li 6i nw:�n7■■111 I LJ...V.J...Iiia.L--��JYY.1:i,...L::i...moi'- _-r.1....I:J....L:iL--i ]C_....J..V� PROPOSED ROW SPACING ♦♦ ) ' i -- / S / / v (TYP.) ��:• \ ---- /" - — PROPOSED COMBINER BOXSA1-6 -' / \ -' -- t •il■■■Gil■■■Gil■r---.7. �I■Gil■■■Gil■■■lie-ava�L _1■■■■Gil■■■riil■r�,;F]I:M,1 ■Gil■■■G�i� / / I� o -- " Il11■■■1111■■■1111■L�....]C■In10■■Inl■■■ill.__,,ail■■■■nil■■■1111■L_'....i111■Inl■■■111 a PROPOSED ROW TO ROW ♦ ; \ 111■■■I111O■e111I1■r r7! ■1111■■■IIII■■■111' y�.;.' 1■■■■1111■■■1111■r . - "7■■111 / / / W JUMPER(TYP) \ L�■■■Vi1■■■L:ia■L =7E■��■■■Nil■■■F 115}v4 `)-.=S-� 1)5-}:'!ll [15.}v_111 / ♦♦` '\\`S __ -� _- _ ` __- — ' / I / / 0I / / / j ♦♦ems rd■■■bd■■■itd■ru_ sH ifrr ril■■■l-r PUnal•.G ■G7■G■11ii1 , Illi■■■1111■■■1111■L_....�ii.illll■■■1111■■■111.-' rMi■Ilii■■■1111 / / / PROJECT: co ♦ --- __ ni■■■nl1■eoi/n■r-•"• npiu■■INi■■■ln'--... - .. i■■n� 1,123.2kW(DC),781kW(AC) co ♦ f © to ma}t lvi ]�eu / / ) U ♦♦ • __ _- -- - __ - _- ,• _ — — ' / i RAISED GROUND MOUNTED PHOTOVOLTAIC SYSTEM o `♦i r - _`` — — - / l I/ ;t SUN EDISON(NY-12-0028) `i♦ _ - --_-- _--_ - /• /. SOUTHO DLANDFFILL 9 � ,.v_, _ ♦i 9 _ _ _ / SOUTHOLD,NY 11935 o `( - _ SUFFOLK COUNTY z 1 PV ARRAY(SA1-1 THRU SAI-6) - BLOCK I LOP 17S coE-300 SCALE'1'=20' SCALE AS SWAIN JRO/ECrNO. 144,o-Pr W GRAPHIC SCALE - a PROPOSED DC CONDUIT pr., e 2 9PAlli CLIENT SUNIDISGN 20 0 10 20 40 80 ROUTED ALONG ALUMINUM ORAWNBI' p.5. REVIENEDBI.Cal -- 09 SUPPORTS(TYP.) In mmwmunme- (IN FEET) 1 INCH520FT PV ARRAY(SAI-1 THRU SA1-6) v --- ~O DRAWING NO z - I E-300 j - SHEET NO sy 19 OF 20 N THE COPYING OR REUSE OF THIS DOCUMENT,OR PORTIONS THEREOF,WITHOUT THE WRITTEN AGREEMENT OF WHITMAN IS PROHIBITED,COPYRIGHT 2015,WHITMAN DO NOT SCALE THIS DRAWING 4 I , I W TRUE t . NORTH M - WHITMAN ' TRUE Eovuenmeufal•Geoleclmcal•Civil I I Structural.Meclumcal•Ecancal - 7 PLEASANT HILL ROAD CRANBURY,NI 08512 (1807 FAX A (7321390.9496 I - - 1 TRUE „ SEAL: MODULE , AZIMUTHa ' ' (1801 \/ PROPOSED ROW TO ROW ' JUMPER(TYP) CP-04 - I T\i' 1 \ \ \ \ \ \ \ \ v V A V 10.44,1i, - ',I�.Itt1...In1.L..,.,. n1•••nul•nu.--... _•HEIN••w \ \ I �0.t. !11�■lr/l•1:anul.r•"'•' ■•u.••nill•••u!'--"• 7.•11.1 \ Li,:�,1 W54v3.1 ltL1kL:SY�7 _-1 \ , - - raT r. r. -- ,. �. n \\ \\.I Li�•1 11•.•11 C!■L°}�':::'A ■1111.•.IIIL..I ILEA.,,,,:11Mi11•�i N. e \ ` ♦•; 4'1'4, x DRAA7NG 110755. ! \ . 1.11�•1111.•.IIIICiral�''a% ■1-11.••1111.••1 l l'uuv3':1• r11f� - \ \ \ \\ �•� �� IIF THIS DRAWING DOES NOT CONTAIN THE asva4 n^ 1 \ \ - \ \ \ \ \ V ORIGINAL SEAL OF THE PROFESSIONAL !_ \ \ \ I ENGINEER,IT IS NOT A VALID DOCUMENT \ ` PROPOSED COMBINER BOX SAI-7�� \ ---• \ AND NO LIABILITY IS ASSUMED FOR THE INFORMATION SHOWN \\ ill..•. ll11••lii-IM ■I:7.t•1i7•�•fiil=,1 ■IreiL.ari' �� \ �I11•••1111.•01111■L......aC•IIUIG,I.1111•.L111w'�:aC•111111••I/11 \ \ \ \ N. \ IIi•••I111•••u11•r-"" ■1111.••IIII•.•IF1'--"' =.„,"4,1•111511 \ \ \ \ 1,* 2 THIS DRAWING HAS BEEN PREPARED ASA N \ tax��f1 uvty-+cl V \ \ \ \ \ \ \ \ ` 'D'SIZE DOCUMENT DO NOT SCALE THIS DRAWING IF IT IS PLOTTED AS ANY OTHER \ \ \ t O J \ \ PROPOSED COMBINER BOX SA1-8 \ �, SIZE . \\ N. lia.■ira..0iiii.r-'=,71C•:im••NInum•..r-'�-ip■rz.L(.■rias•.r�--1r11uuu R•aNrra•r-771 p•5a..io \ , 111•..1111.■•11 t1•L-.... ■111t••G�G!Im••■L:,.- ■IIf1•■■•II••••IL.:-i 111•.•1111•••1111•L-..,,: ■1111.••111 \ PROPOSED ROW SPACING Ill•..illl.••llll.r-7,,„!. ■1111.•.•115�v•.r•"'- ■1111.•••11•••mlr"m. Ill.•.111111.•illl.r- 7..111 \ 6 �'}6'WEI =94:kv.-WWI u.. ..WW LIR,...,7a6 ';f W U N O TYP. \ J...L.:I...LJ.L_�- ■LO...•LiJ1IC7.B_-'-. .L'�....LriJ..LIL-�_ J•■•LJ•••VJ.L_'..�� J••L \ ( ) Sun Edison umpLiying solar \ 1 \ \ (C)2010 SUN EDISON LLC AND RS ` \ r 1 r -- 11 is I ,1 /1 / pi I. r■ r! r C - \ AFFILIATES,ALL RIGHTS RESERVED \ ,,,,„'v:•J ' LL},3)I' C'Snil Lilt Stl I I••••u■•••11•.L-.... •7u1••■ulie••ua___.I1u•111111•••1n1••L:.:._ 11••••un•►�nu1L__... ■•IIII••7n1•aIIII " \ a 12500 BALTIMORE AVE ' il•••."111"."1111 i4: a'C•Illl.•■1111...6111�� lli".Illi...11ll..roiae'.w]CII.....ill•.111111r�---'' Il•.I111••IIII. 1"11�v„},.,,,•.I �\ \ PROPOSED DC CONDUIT ___ ■V:1•••L:J..•�i MMM6WMMM 1::1!••L___ I:iJ•.•Vr•••VidL.. ■•Vi•MWMMMMJ! -_ �, N • \ ROUTED ALONG ALUMINUM CP-04 BELTSVILLE,MD 20705 ` / �� \ --- \ \ _ — ( • \ '- \I b \ SUPPORTS(IYPJ (443)909-720D �+ ` 1\ \ \ PROPOSED COMBINER BOX SA1-9 Y \ \ \ �. is ,. r. r. i. n �� . r1 •i1 i. -- ral••r. ' \ \ US:kv3'11 lu'a11_a,}f LU .,ail la!>•,13 9 • ',„N.'`, 111011•III.�IIII.L,.,,,. Illi C!■••1111••••1,:...- 1I!1••••1111•�■1 I11•••1!!I•••1111•L_...,' ■IIIILI••III �'- 111.M7111.MIIII.' 11111••.1111.•••1"•77 1111••I/•1111•�•1"•--3 111•••1111C••1111•r�"' _••"7•.11IJ \ \ \ + SS - _ uu1; - II mevi_w'-a 1t uv.}ua,:1 Ltan,r.-u1 t}.. W• \ \ \ +\1\ �` e• \ \ cc, \ \ \ I \ \ \ \ \ + ci' / \ r. � 5'\ I■ - I I! r\ OLIO •a] I I I tn.A!•v�l1 I 11 /! u_,111:SO r! r! \ \ \\\ \ ''''''N -1. 4.' 4. �` Ill...11te•..I CAI•L_:... .1111...1 III...IIIL___ I;I•..•IIII....IIIL�� �1111••.1111•••1111•L�.... ■1111•..111 �� 111.••IIIIL.•IItS.r,M ■IIl1.G.li 11.••111 --. !t11•••.1!II...•IiR�,�. III...II11.•.1111.r-"L' 7••111 Na DATE REVISION DESCRIPTION \+ Sg� ! 'u'tvnrl - aua w .:. ® .. Uri 1FF7 �•[3[-i�tn \ `rEIIIEWJ■IIIIWOUL__..IC.VJ•••IrWIIIMML --W6r■•••LAIL..•Ilii.---.111i•••Lil••■WW•L._-.16 ,'••J.•Wil \ .Oy \ \ \� \+ \ \ ` .,R \O r-J \ 0 \ \ \ u 00/11/15 PRF3AI01ARY SOBLILISION 1 \\\ \ \ '\\\36 �` _ \ _ �' _� \ —7 \ \.. \ \ \ \ \ \ \ \ - \ \ \ \ I j PROPOSED COMBINER BOX SAI-10 — \ \ \ J• \ r\ �- v \ \\ \ \ \ I il•••I alimmbil•r--- �l■lil.•.Dl•..•r,---�-rfl �t mil•••.1i7...1iiTLL�L--. jl...lral..•liammw---r��llGil••.aumembor--,--97 \ \ - - o \ \ \ +\ \\ agnow•Inl•■1111•►-....7Y■II11•■■IIJI■••■1,. �Y1111■••61111•••11R&--.jllr•.1111••■Inti:.:._�Yuiimom 7!••nuiL'--.,,.1 \ \ \+ \ — I11\.•Illl.•I111•ro•oy:, !G1111...1111•••.1aux1a,J 1111..12•1111...IIIfo ovnolll.••Illl•••Illl•�' �k1 If1L..I1c1...I111rt,L�m761 \ W \ -` o \\ \ \\+\\ i \ ` � —1 / I \ \ — 1 PROPOSED COMBINER BOX SA1-111 ss 0J P}r.li llRl.,LS9J (]!!kvSrl lJl1ly' f Pi PI \ \it + / / _ 111•••1111•••111LL_...11 ■Iltl••It11••••1,',.-- 1111•.••1111.•••1,.._. I11•••1111•MIKIHM•L....:.` ■1111•••111 I 1 i CC \ \+i}` , .-� 1110s.1111•..IIII.r-"•' ■1111.•.1111.•.•1"'-7 IIII.O••1111.•••I"•-- Ili.••ill!•••1111•�-"" -'" 7•.111 I / I I PROJECT: UlP}I;IJFf ll.)kL3'11 .. Ul1kv3J - V)1lRv3:1 ltl1F]I:,•!1 Z \ \ (,+\ — _ iI / r / o / / 1,123.2kW(DC),781kW(AC) \\ ��,�\ ---.. \ y , _ \ \ ) I ( / / RAISED GROUND MOUNTED \ `+\� \ 1, ,. is is a .. i! / [y?as// PHOTOVOLTAIC SYSTEM 1'I,Iktii'_J 1 L CSD uw-v30 't o \ \ / �'�-. / \ 1 utl••f1n1.•■111LL ■1111..•1111•■■•I:':=4.r1i1u•••Iu1•••.I,',.-- uI1•••l11u■.7nIL�-.•.1 / // SUNEDISON(NY-12-0028) 2 �r, -t 1n.._.nn...iplLrL,,;,;;; , • !! ••• !! ••••1;;:,i.,uu i U•••n;_n.••.1', �-D u11•.•.nu•..n_nr,--,;;r; 1 / / / \/ \ ' t\ _ - - - -- - _ I II i ! l l l/ l l SOUTHO OX LANE O \\ `N 'N \\+'\ _ -- __ \ \ ` / PROPOSED COMBINER BOXSAI-12/ / / /'� SO 155 O NY 11935 \ + _`�•. N. PI t! " a'-.,, r. r. /f Ugr}v3,tl 11 I I1 u t- '• I / / / � / // ._ ` O ) \ ` \ \+\,' \ nu•.u11••un•L'_.... •llu..•uu..i1NL - IIu••liI1•..1IIINL :: ■1111•.•■ / /� ///;/ SUFFOLK COUNTY / f 111..•111I•••1111•r�-y',,'Li ■Illl.11alll..1!ir ,,-�-„, lu••.IIU.•.I!I•ra ..,,� 7 a.N•.■ co 1 PV ARRAY(SA1-7 THRU SA1-12) _ "—�I - \ ' , C — -- \` - / / / / �/ /// •, DT BI. 1 �� 174 - 0 E-301 SCALE 1'=20' \ / / I / I // } / / .if C4L AS SHOWN PROJECTED Icuylsrr ' W GRAPHIC SCALE \ / 1 1 , / //l ,� _ + Ii/9‘'e _ _ I / / * PLOT DATE 9/IA/LS TITER SIINEDISON 2 J 20 0 10 20 40 80 \ I"' • m 1x5ALPT - 12510.09 / P1.xsm.vI\ +\ \ — III / Jrl // / /:',/f. I /I DRARIL'BY PH $E IEWEDBI CA+1. � \ !�, y ,a rt sTRaal . ,,y1_4: LxsTrtlo m x 12 I / // ` i� DRAWING TITLE• (IN FEET) \ \ L . .... ` l / , , 1 / / / // 1 INCH=20 FT _ ! �• 7. / / // / / PV ARRAY(SA1-7 THRU \ \+\ - ��''.a...ra...ra.rQ ■ran..ra..rrar¢„ / / / /// \ \ \ — IIII••■1111•••1111■L ....�C•111L••Illl•.1111L_-...1 -- O \ \ * \ \ 1111...1111...1111.rW Y4i,.,�D�11.1111...111L.1111r�1.{ � / / // //// \ DRAWING NO. \ VJ...VJ...f:J.L�--- Y■VJ►�..f..1..V�iL:_� E-301 iSHEET NO• N THE COPYING OR REUSE OF THIS DOCUMENT,OR PORTIONS THEREOF,WITHOUT THE WRITTEN AGREEMENT OF WHITMAN IS PROHIBITED,COPYRIGHT 2015,WHITMAN DO NOT SCALE THIS DRAWING 20 OF 20