HomeMy WebLinkAbout38766-Z Town of Southold Annex 5/9/2014
1,_����' -=i
P.O. Box 1179
54375 Main Road
+�,
j4,1 Southold, New York 11971
CERTIFICATE OF OCCUPANCY
No: 36901 Date: 5/8/2014
THIS CERTIFIES that the building ELECTRICAL
Location of Property: 10095 Route 25, Mattituck,
SCTM#: 473889 Sec/Block/Lot: 142.-1-26
Subdivision: Filed Map No. Lot No.
conforms substantially to the Application for Building Permit heretofore filed in this officed dated
4/4/2014 pursuant to which Building Permit No. 38766 dated 4/4/2014
was issued, and conforms to all of the requirements of the applicable provisions of the law. The occupancy for
which this certificate is issued is:
electric for exit and emergency fixtures and hood system for a restaurant. (CJ's American Grill)
The certificate is issued to Mattituck Plaza LLC
(OWNER)
of the aforesaid building.
SUFFOLK COUNTY DEPARTMENT OF HEALTH APPROVAL
ELECTRICAL CERTIFICATE NO. 38766 11, 5/7/14
PLUMBERS CERTIFICATION DATED
ORM E 4101
Au ho e. Si_ ature
,iilliflON TOWN OF SOUTHOLD
BUILDING DEPARTMENT
TOWN CLERK'S OFFICE
'$.�,� y i SOUTHOLD, NY
1 ;4`
f
BUILDING PERMIT
(THIS PERMIT MUST BE KEPT ON THE PREMISES
WITH ONE SET OF APPROVED PLANS AND SPECIFICATIONS
UNTIL FULL COMPLETION OF THE WORK AUTHORIZED)
Permit#: 38766 Date: 4/4/2014
Permission is hereby granted to:
Mattituck Plaza LLC
PO BOX 77
Mattituck, NY 11952
To: Commercial Electrical
At premises located at:
10095 Route 25, Mattituck
SCTM # 473889
Sec/Block/Lot# 142.-1-26
Pursuant to application dated 4/4/2014 and approved by the Building Inspector.
To expire on 10/4/2015.
Fees:
ELECTRIC $120.00
Total: $120.00
III
Building Inspector
,�,,, ice.
le NI%IpF SO(/r�,ol
Town Hall Annex ��� : Telephone(631)765-1802
54375 Main Road i lig illi % Fax(631)765-9502
P.O. Box 1179 : v' � i
. roger.richert(a�town.southold.ny,us
Southold,NY 11971-0959 %�` 4:::1
COUNTY, 8.'
BUILDING DEPARTMENT
TOWN OF SOUTHOLD
CERTIFICATE OF ELECTRICIAL COMPLIANCE
SITE LOCATION
Issued To: Mattituck Plaza--CJ,s American Grill
Address: 10095 Main Rd--Unit-8 City: Mattituck St: NY Zip: 11952
Building Permit#: 38766 Section: 142 Block: 1 Lot: 26
WAS EXAMINED AND FOUND TO BE IN COMPLIANCE WITH THE NATIONAL ELECTRIC CODE
Contractor: DBA: JJW Electric Inc License No: 4664-me
SITE DETAILS
Office Use Only
Residential Indoor X Basement Service Only
Commerical X Outdoor 1st Floor X Pool
New Renovation 2nd Floor Hot Tub
Addition Survey Attic Garage
INVENTORY
Service 1 ph Heat Duplec Recpt Ceiling Fixtures HID Fixtures
Service 3 ph Hot Water GFCI Recpt Wall Fixtures Smoke Detectors
Main Panel NC Condenser Single Recpt Recessed Fixtures CO Detectors
Sub Panel NC Blower Range Recpt Fluorescent Fixture Pumps
Transformer Appliances Dryer Recpt Emergency Fixtures Time Clocks
Disconnect Switches Twist Lock Exit Fixtures TVSS
Other Equipment: 1-combination exit/emergency fixture, 1-exit fixture, 1-emergency fixture
Notes:
Inspector Signature: Date: May 7 2014
81-Cert Electrical Compliance Form.xls
,11�,�o��OF o�``
VtcP =tea
/ �y�DUNT'1,��,•��
TOWN OF SOUTHOLD BUILDING DEPT.
765-1802
INSPECTION
[ ] FOUNDATION 1ST [ ] ROUGH PLUMBING
[ ] FOUNDATION 2ND [ ] INSULATION
[ ] FRAMING / STRAPPING [ ] FINAL
[ ] FIREPLACE & CHIMNEY [ ] FIRE SAFETY INSPECTION
[ ] FIRE RESISTANT CONSTRUCTION [ ] FIRE RESISTANT PENETRATION
[ ] ELECTRICAL (ROUGH) ELECTRICAL (FINAL)
[ ] CODE VIOLATION [ ] CAULKING
REMARKS:
DAT E 0/(47 INSPECTOR Z
Town Hall Annex * *; Telephone(631)765-1802
54375 Main Road `
a Q � roaer.richertd n a a
nv.us P.O.Box 1179
Southold,NY 11971-0959 `3 AO D ��� .
BUILDING DEPARTMENT
TOWN OF SOUTHOLD
APPLICATION FOR ELECTRICAL INSPECTION
REQUESTED BY: Date: 3/30/(."
Company Name: 7`'„ 74) EZ /<, •
Name: o�.�
License No.: 5 G '-f6.6e1
Address:
iFePcc 3d , e_cj,�� , 9 3/
• Phone No.: 13-66.
JOBSITE INFORMATION: (*Indicates required information)
*Name: ( I Its 47,0cric, c6r' 11 tl-C_
*Address: 16O95-- Gin/ TYI a i/1 Poo o Meti-ti lc i1J 1/�c)-
*Cross Street: �J
*Phone No.: G 5i — 3/ 5 5`3 t
Permit No.: 3k7(9e19
Tax•Map District: 1000 Section: jq-.. . Block: I Lot: J.4'
*BRIEF DESCRIPTION OF WORK(Please Print Clearly) • s714-1leo 0 L''>4'Z—G/�,�7'''
o
lye"( N&wk. =.Asr,4ctj /rre,tv ere,. 471. —eit - '• P
17c>/t -� �xj.�f yr s {
(Please Circle All That Apply)
*Is job ready for inspection: ES/ O Rough In Final
*Do you need a Temp Certificate:
Y p YE / N
Temp information(If needed) l
*Service Size: 1 Phase 3Phase 100 150 200 300 350 400 Other
*New Service: Re-connect Underground Number of Meters Change of Service Overhead
Additional Information: PAYMENT DUE WITH APPLICATION
82-Request for Inspection Form o 1
AES MANUFACTURER:
SEAL TIGHTS (TYP.)
RANGE GUARD: _RG 1.25 GAL. RG 2.5 GAL. RG 4 GAL. X RG 6 GAL.
� — __ 1�_ Piping Material BLACK SCH 40 Max. Rise 12'
:" :: 14"x14" DUCT 14"x14" DUCT Supply Pipe Size 3/4" Branch Pipe Size 1/2" DROPS 3/8"
Gas Valve Type: MECH Size 2" Manufacturer ASCO
ADP ADP 14' HOOD ADP ADP Detector Temperature Rating: 360', 450' & 500'
1 Hood Size: 14' Duct Size: (2) 14"X14"
r - - - - - - - L� —ICI- - - - - - - -®- -Ie4� - - -®
CONTROL 360' 360' 360' 500' 450' 450' o EQUIPMENT SURFACE NOZZLE
HEAD -~ ADP 1 I_ADP J I TYPE QTY. AREA TIP#/QTY' HEIGHTS LOCATIONS
J ► N
�— — T T T T T DUCT 2 14"X14" ADP 4 0"-6" 0"-6" IN OPENING
I I I I PLENUM 1 14 FT. ADP 2 0"-6" FROM END OF PLENUM
RC I I I I I I I 6 BURNER RANGE 2 36"x27" R 4 20"-42" CENTER
6.0 ♦ ♦ ♦ ♦ I ♦ ♦ UPRIGHT BROILER 1 32"x20" ADP 1 - TOP 4" OF COMP. t f<
GAL. R R R R F F FRYER 2 14"x23.5" F 2 27.5"-45" 45' TO 90'
•
L ADP 6„ _ . i
Lo
PULL I MIN. TO EDGE
STATION 32"x20" a` ce OF HOOD ON c° — —
D X UPRIGHT >- o r o BOTH SIDES
1 Q I 2" GAS 36"x27" 36"x27" BROILER u m m RANGE GUARD - RG 6.0 GALLON - MAX. FLOW POINTS = 18
VALVE 6 BURNER 6 BURNER ;1- , E E2 POINTS USED = 15
RANGE RANGE KS ° M °
L — X x TOTAL PIPE VOLUME NOT TO EXCEED 400 CUBIC INCHES
— . 3 3 MAX. PIPE LENGHT 75 FT.
' RG-6.0 GAL. CYLINDER #60-20005-001 LINK HOUSING #804548
DISCHARGE ADPT. KIT #83-844908-000 MANUAL RELEASE #B100030
VENT PLUG #9196984 360' LINK #WK-282664-000
A FIRE EXTINGUISHER SHELF BRACKET #100013 450' LINK #WK-282663-000
WITH A MINIMUM RATING UCH #B120099 500' LINK #WK-282666-000
FRONT VIEW OF CLASS K MUST BE DUAL SPDT #9197228 2" GAS VALVE #B120075
3/8"=I-0"
INSTALLED WITHIN THE ADP NOZZLE #87-120011-001
SCALE: VICINITY OF THE F NOZZLE #87-120012-001
COOKING AREA. R NOZZLE #87-120014-001
SCFM STAMP NOTES: Anderson Fire
x Fryers to have High Limit Control to shut off fuel at 425'. 9 O'Neil Ave., Bay Shore, N.Y. 11706
x Detectors shall be located over every piece of equipment.
x The System installed as per manufacturers specs and the AHJ. Tel: 631-435-1002
x The System has been installed as per UL300.
x The following functions to operate upon system discharge: Contact: Patrick Turro
* Supply air damper closes * Gas fuel shuts off in kitchen
* Exhaust fan remains on * Electric fuel shut off under hood �P,.S E"a'^EyFq'i
* All systems to activate simultaneously in same hazard area. :1 wi ' T . PEGASUS ENGINEERING
* Fire Alarm sholl activate if one is installed in building.
x Manual Pull is located a maximum 20 ft. from hood and 4 ft. 6 Nodworny Lone, Stony Brook, N.Y. 11790-2100
from floor. PLANNING A BETTER WORLD
x All fuel sources are GAS unless otherwise noted. • C*
631-751-6600
___ _- ZSOP"di WWW.PEGASUS.ENG.PRO
UNAUTHORIZED ALTERATION OF, OR THE ADDITION SEAL
TO PLANS OR DOCUMENTS BEARING THE SEAL JOB SITE:
OF A LICENSED PROFESSIONAL ENGINEER IS A
VIOLATION OF SECTION 7209, SUBDIVISION 2 OF CJ's American Grill
THE HE NEW NEW YORK STATE EDUCATION LAW. -
ANY ALTERATION TO THIS DOCUMENT MUST BE
DONE BY A PERSON ACTING UNDER THE DIRECT ` i p L 10095 Unit 8, Main Rd., Mattituck, N.Y. 11952
SUPERVISION OF A LICENSED PROFESSIONAL IN
ACCORDANCE WITH THE STATE EDUCATION LAW.
COPIES OF THIS DOCUMENT NOT MARKED WITH
AN ORIGINAL OF THE PROFESSIONAL ENGINEERS DATE: SCALE: DWG BY: DWG N0
INKED OR EMBOSSED SEAL SHALL NOT BE
04/1 7/1 4 AS SHOWN A.X.C. 1
CONSIDERED TO BE VALID TRUE COPIES. -
System Design
3-6.1.1.2 Ducts 50 to 100 inches in Perimeter
Two ADP nozzles, P/N 87-120011-001, pointing in the same direction are required for protection of
ducts with perimeters greater than 50 inches and less than or equal to 100 inches. Ducts can be of
unlimited length(refer to Figure 3-30).
For other option of ducts up to 75 perimeter inches (See Figure 3-32).
Note: All Range Guard systems are listed by UL and ULC for use with the exhaust fan either on or
off when the system is discharged.
DUCT
t====
HOOD
X
4/x+/ + +X +/.d +/d MAX.DIAMETER 31.83 In.(809 mm)
/<x /x
NOZZLES TO BE ALONG ONE
25 in.(635 mm) CENTERLINE AT THE 1/4 POINTS.
MAX.SIDE 1 Fp� • NOZZLES TO BE 0-6 In.(0-152 mm)
UP FROM ENTRANCE OF VERTICAL DUCT
MAX.DIAGONAL 11.78 in.(300 mm)
MAX.DIAGONAL TYP.(2)ADP NOZZLES
11.78 in.(300 mm)
SQUARE RECTANGULAR ROUND
C.
r-- ADP NOZZLE
0 to 6 In.
rOito 152 mm)
DUCT ENTRANCE
C OF VERTICAL DUCT
14/1
C
I , � OF HORIZONTAL DUCT
2-4 in.(51 mm-102 mm) /
ADP NOZZLE � AIM POINT
NOZZLE TIP TO DUCT HIP
VERTICAUHORIZONTAL DUCT
Figure 3-30. Duct Protection Using Two ADP Nozzles, P/N 87-120011-001
April 2009 3-36 P/N 60-9127100-000
System Design
4 ft. NOZZLE
(1.2 m)
DUCT ,/ 4 ft. DUCT 0,0e :,...... 4 ft.
(1.2 m) (1.2 m)"."
to ;.*.°' / NOZZLE ®��� 10 ft. k41 (6 20 ft.
(3 m) AC ft m)
NOZZLE (1.2 m))/
"V" FILTER BANK COVERAGE "V" FILTER BANK COVERAGE
10 ft.(3 m) PLENUM 20 ft.(6 m)PLENUM
<>1.evi.2. - NOZZLE
3/4H H
f
"V" FILTER BANK
COVERAGE(END VIEW) `-""
,
At, 4 ft. NOZZLE
piiii:'2 ni)f
w f DUCT � „ �"
4 ft. DUCT
-5.--,,p, : (1.2m) / ®�' (12m)
Jr �i
re)41 ✓ N OZZLE 01 ..
10 ft , `` 77-
(3 m) /� . (6 m)ta,�\ 4 ft.`•
(1.2 m))".
NOZZLE \,
SINGLE FILTER BANK COVERAGE N. SINGLE FILTER BANK COVERAGE
10 ft.(3 m) PLENUM 20 ft.(6 m) PLENUM
-1+113 Wk-
I
3/4 H1. ; T -- ------- /
1
IA- w -*I
SINGLE BANK FILTER
COVERAGE(END VIEW)
Figure 3-28. ADP Protection Nozzle, P/N B120011
Apr-112009 3-34 P/N 60-9127100-000
System Design
3-4.2 18-1/2 in. x 24-1/2 in. Deep Fat Fryer With Drip Board
Table 3-3. F Nozzle Coverage Area
Items Parameters
Maximum Hazard Area 18-1/2 in.x 18 in. (470 mm x 457 mm)
Maximum Appliance Area(with drip board) 18-1/2 in.x 24-1/2 in. (470 mm x 622 mm)
Nozzle Aim Midpoint of module area per nozzle
Nozzle Location(at an angle of 45°or more from the horizontal 27-1/2 in.(699 mm)Min.
above each module) 45 in. (1143 mm)Max.
Module Area(half of hazard area) 18-1/2 in.x 9 in. (470 mm x 229 mm)
AN F NOZZLE MAY BE LOCATED M AN F NOZZLE MAY BE LOCATED
In. 45 ANYWHERE WITHIN THE GRID -\ ANYWHERE WITHIN THE GRID
(1143 mm) (1143 mm)
' _ MAX. DIAGONAL FROM
45M. I• •,` •�I�•;•►,~ AIM POINT
(1143 mm) ' •■• „ ••• �` 45 In.
♦�-��•�,I•.� 50 (1143 mm)
MAX. \ivrt\Ivrt/ ■■■ MAX.
27.1/2 In. ♦r'."::i• Pa.;:i'. IMAGINARY LINE
(899 mm) DIVIDING MODULES
MIN.
MIDPOINT OF
MODULE AREA
FRONT OF 19-1Q In.
APPLIANCE (470 mm)
MAX.
9In. 1— 9In.
(229 mm) (229 mm) -Poi
• 2412 In.
(622 mm)
MAX.
SIDE VIEW
2 F NOZZLES ARE REQUIRED FOR THIS APPLIANCE
AN F NOZZLE MAY AN F NOZZLE MAY BE
LOCATED ANYWHERE i LOCATED ANYWHERE
WITHIN THE GRID
WITHIN THE GRID
VIA P:111P /
NOZZLE LOCATION i , �F�
45 OR MORE FROM ♦♦ ♦♦ i i/ `4°j -.
HORIZONTAL(TYP) ♦ ♦/ ww
♦ A /�C
♦ i ♦ i w
♦i ♦//As
AIM POINT:
MIDPOINT OF
HAZARD AREA
HAZARD AREA
DRIP BOARD
16.12 In.(4T0 mm)MAX.
24-112 In.(622 mm)MAX.
APPLIANCE AREA
SIDE VIEW
Figure 3-3. 18-1/2 in.x 24-1/2 in. (470 mm x 622 mm) Deep Fat Fryer
P/N 60-9127100-000 3-7 April 2009
System Design
3-4.10 Two Burner Ranges
Table 3-14. R Nozzle Coverage Area—Two Burner Range
Items Parameters
Maximum Hazard Length 28 in.(711 mm)
Nozzle Aim Midpoint of hazard area
Nozzle Location-Anywhere within the area of a circle 20 in. (508 mm)Min.
generated by a 9 in. (229 mm)radius about the midpoint 42 in. (1067 mm)Max.
Note:Shape of burner not important.
+ �18in.(457mm)DIA.
# — 42 In.(1067 mm)MAX.
(FROM TOP OF RANGE)
1 A A'R'NOZZLE MAY BE
! LOCATED ANYWHERE WITHIN
THE SHADED AREA
20 In.(508 mm)MIN. # AIM POINT:MIDPOINT OF
(FROM TOP i HAZARD AREA
OF RANGE)
WSW /
28 in.(711 mm)MAX. Irfr 14 In.(356 mm)MAX.BURNER
HAZARD AREA CENTERLINE TO CENTERLINE
LENGTH
Mgr
Figure 3-11. R Nozzle Coverage for a 2-Burner Range
April 2009 3-16 P/N 60-9127100-000
System Design
3-4.9 Four Burner Ranges
Table 3-13. R Nozzle Coverage Area—Four Burner Range
Items Parameters
Maximum Hazard Area 28 in.x 28 in. (711 mm x 711 mm)
Nozzle Aim Midpoint of Hazard Area
Nozzle Location—Anywhere within the area of a circle 20 in. (508 mm)Min.
generated by a 9 in.(229 mm)radius about the midpoint 42 in. (1067 mm)Max.
Note: Shape of burner not important.
18 in.(457 mm)DIA.
1 _ 42 in.(1067 mm)MAX.
' (FROM TOP OF RANGE)
I
•
I A'R'NOZZLE MAYBE
i LOCATED ANYWHERE WITHIN
THE SHADED AREA
•
�+ i
20 In (508 mm)MIN. _ / j... AIM POINT:MIDPOINT OF
(FROM TOP OF HAZARD AREA
RANGE)
•
4011 r
�� inow
28 In.(711 mm) 14 In.(356 mm)MAX
MAX.HAZARD BURNER CENTERUNE
AREA LENGTH i TO CENTERLINE
nil. i
ii 461.1117
nor
i
14 in.(356 mm)MAX.
BURNER CENTERLINE
TO CENTERLINE
/-- 28 In.(711 mm)MAX. -P•
HAZARD AREA WIDTH
Figure 3-10. R Nozzle Coverage for a 4-Burner Range
P/N 60-9127100-000 3-15 April 2009
System Design
3-4.13 Upright Broilers
Table 3-19.ADP Nozzle Coverage Area
Items Parameters
Broiler Compartment With Maximum Internal Horizontal 30-1/4 in.x 34 in. (768 mm x 864 mm)
Dimensions
Nozzle Aim Through grill toward the center of the grease drain-off
opening
Nozzle Location Within the top 4 in. (102 mm)of space in the broiler
compartment. Commonly mounted near the front
opening and directed inside the broiler
BROILER _ EXHAUST
COMPARTMENT RM I G ; DUCT
*VE■
GRILL
4 in. (102 mm) ; >
MAX. ;4 1 4 n. 4..._ 34 In.(864 mm)
(768 mm)MAX. '
y MAX.
GREASE
•
a �--14GREASE DRAIN PANJ DRAIN-OFF
J FRONT J U
(BROILER DOOR REMOVED) RIGHT SIDE
NOTE: DIMENSIONS SHOWN ARE INSIDE BROILER COMPARTMENT
ADP NOZZLES SHOULD BE MOUNTED ON THE PERIMETER OF THE BROILER
TOP(SHADED AREA). IT SHOULD BE DIRECTED THROUGH THE GRILL
TOWARD THE CENTER OF THE GREASE DRAIN-OFF OPENING. NOZZLE
DISCHARGE SHALL NOT BE OBSTRUCTED BY ANY STRUCTURAL PART OF
THE BROILER.
Figure 3-15. ADP Nozzle Placement for Upright Broilers
April 2009 3-20 P/N 60-9127100-000