HomeMy WebLinkAbout33413-ZFRONT ELEVATION
REAR ELEVATION
32'- 10"
DECK
TO BE REMOVED
~ EXISTING WINDOWS
III / TO BE REMOVED
EXISTING INTERIOR PARTION
WTO BE REMOVED
-39'
II II
BEDROOM .#1
BEDROOM #2
EXISTING FLOOR PLAN
20'-3"
BOARD OF ASSESSORS
TAX MAP #/~ ~.~.~z.//,~..~.~,
pERMIT ~ ¢ ~,~ :/f~ ~
JL JL JLJL JL JL JLJLJL JL JLJL JL
EXISTING WINDOWS
TO BE REMOVED
14'-1"
GRADE TO
RIDGE
(EXISTING)
RIGHT-SIDE ELEVATION
LEFT-SIDE ELEVATION
OFFICE SET
9.7.07
Zl;
LIJz
Oo
<
'0
'r
~ 0
__.
o~0 mO
SCALE:
1/4" = 1 '0"
DWG. NAME:
EXISTING
FL. PLAN /
DEMOLITION
PL-~N
DWG. NO,:
A. EX
NOTE
INSULATION NOTES
PROV, ADDITIONAL 8/4" FOIL FACED FOAM BOARD
UNDER ALL NEW CONSTRUCTION,
NEW EXTERIOR WALLS: 2"X6" WOOD STUD, R-21 FOIL FA, HIGH DENSITY
INBULATION BY 'CERTAINTEED' OR APPROVED EQUAL.
NEW ATFIC/ROOF',, R-38 KRAFT-FA, INSULATION BY 'CERTAINTEED' OR
APPROVED EQUAL.
CRAWL SPACE; R-21 KRAFT-FA, INSULATION WITH PROPER WIRE TIES
INTERIOR WALLS: R-21 BA~I' INSULATION
GARAGE CEILING: R-21 KRAFT-FA. INSULATION WITH PROPER WIRE TIES
PLUMBING LEGEND
Dp
PROVIDE ALL NECESSARY PLUMBING ROUGHING AND VENTING AS
INDICATED ON CONSTRUCTION PLANS. FOLLOW ALL NECESSARY
N,Y,S. AND LOCAL PLUMBING CODES THAT APPLY TO WORK TO BE
COMPLETED. PROVIDE ALL NECESSARY DRAIN VALVES FOR
WINTERIZATION. REP. TO CONBTRUCTION PLANS FOR FIXTURE TYPES.
ALL WASTE LINES ARE TO BE INSULATED WITH SOUND A'ITENUATING
INSULATION (TYP. ALL AREAS)
ALL SUPPLY &WASTE LINES ARE TO BE INSULATED WITH SOUND
A~i"ENUATING INSULATION. ('~Y'P. ALL)
SHOWER HEAD (FROST FREE SHOWER BODY)
Af
25'
GREAT RM.
1 7'-0" X 21 '-0"
TILE LEGEND
~ 10" CEP~MIC TILE ~ "AMERICAN OLEAN" TILE OR APP. EQUAL. TILE
BORDER W/SO" TILE ON A 4ED TO BE INSTALLED OVER 1/2" CEMENT
BOARD, U,O.N. WALL AND FLOOR GROUT TO HAVE WATERPROOF
ADDITIVE MIXED IN.
I OTSI 6" X E" CERAMIC TILE - "AMERICAN OLEAN" TILE OR APP. EQUAL. TILE
BORDER W/20" TILE ON A 4§" TO BE INSTALLED OVER 1/2" CEMENT
BOARD, U.O,N, WALL AND FLOOR GROUT TO HAVE WATERPROOF
ADDITIVE MIXED IN,
PLUMBING FIXTURE LIST:
BATHROOM FIXTURES: BY KOHLER (VERIFY WITH OWNER)
TOILET: CIMARRON COMFORT HEIGHT TWO PIECE - K-3497-RA
SINK: THOREAU UNDERCOUNTER LAVATORY - K-SS07-4U
SINK FAUCET: FORTE WIDESPREAD LAV. FAUCET - K-10S72-4G
SHOWER TRIM KIT: FORTE ESSENTIALS PERFORMANCE PACKAGE - K-,10827-4
KOHLER $2" X 60" TUB
PROV. ALL NECESSARY PLUMBING VENTS
SHOWER BODIES BY "KOHLER"
PROVIDE TOILET BEATS
VERIFY FIXTURE LIST WITH OWNER PRIOR TO PURCHASE
GLASS SHOWER DOORS BY OTHERS
ELECTRICAL LEGEND
NOTE: ALL ELECTRICAL WORK TO BE IN ACCORDANCE WITH THE RULES &
REGULATIONS OF THE N,Y,B,F,U, AND A CERTIFICATE FROM THE N,Y.B,F.U.
IS TO BE PRESENTED TO THE OWNER AT THE COMPLETION OF THE JOB.
THE OWNER SHALL PROVIDE ALL SURFACE MOUNTED LIGHT FIXTURES. ALL
OTHER ELECTRICAL EQUIP, TO BE SUPPLIED BY ELECTRICAL CONTRACTOR.
ALL SWITCHES AND RECEPTACLES TO BE 'LUTRON', "DECORA" COLOR T.B.D.
RECESSED DOWNLIQHTS TO BE "LIGHTOLIER" OR APP. LQ. TRIM - WHITE.
NOTE: CONTRACTOR SHALL PROVIDE DIMMER SWITCHES FOR ALL RECESS.
DOWNLIGHTS. VERIFY LOCATIONS OF ALL ELEC. DEVICES WITH CLIENT.
DOOR SCHEDULE
WIDTH:
HEIGH'
DOORMAT'L,
OPERATION:
LOCATION:
6'-0" 6'-8" FRENCHWOOD DBL. SLIDER ENTRANCE
2'-0" 6'-8" MASONITE RIGHT SWING CLOSET
LEFT SWING
2'"8"' 6r-E" MASONITE BI"FOLD CLOSET
2"6" 6'-8" MASONITE RIGHT SWING MASTER BED
WINDOW SCHEDULE
ALL WINDOWS TO BE ANDERSEN 400 SERIES,
ANDERSEN REFER, NO,
ROUGH
WIDTH
ROUGH
OPENIN(~
HEIGHT
GUANTIT~
MISC. NOTES
3'-0 1/2"
4'-0 1/2'~
0X24 5'-3 1/4"
AWNING~
CASEMENT W/2"
HORIZONTAL BAR
R - 21 iH DENSITY FOIL FACE
(TYP. ALL AREAS)
1/2" GYP, BB. ALL
EXPOSED WALLS
~& CEILINGS (TY'p.) ' r~-
UF
24'-6"
tA
Af
22'- 1 1"
M. BEDROOM
12'-2" X 1 5'-0"
M. BATH
5'-0" X 9'-4"
1/2 GYP. ED, ALL
EXPOSED WALLS
& CEILINGS (TYP.)
tA
C~RACTOR TO NOTIFY THE ARCHITECT
OF ANY AND ALL REVIEIONS DUE TO FIELD
CO~IENT, AND OR GENERAL
CONTRACTOR WHICH DIFFER FROM THE
( CONSTRUCT, DRAWINGE/EPECIFIOAT,ONS,J
FIRST FLOOR PLAN
42O SQ.FT.
SECOND FLOOR: PLAN
325 SQ,hl.
OFFICE SET
9.7.07
DWG. NAME:
FIRST AND
SECOND FL.
PLAN
DWG. NO.:
A.1
25'
6' CRA YL SPACE
4" P. CONCRETE SI~ ,B ON CLEAN
COMPACTED FILL W~,~,W,W,M, 6" X 6"
REINFORCEMENT, (T~P, ALL AREAS)
30'-6"
PROV, "WATCHDOG" WATER PROOFING
PERIMETER OF FOUND, WALL
BELOW FIN, GRADE, INOLUB~ING
PARGED JOINT BETWEEN FOUND
WALL AND FOOTING (TYP, ALL AREAS)
8" P. CONC. FOUNDATION WALL
WITH 1'-4" W, X T-0" B, P, COINC,
FOOTING (OONT,) W/W,W,M, IN
WALL AND FOOTING, 36" BEL.OW
FIN. GRADE
10" X 1'-0" SCREENED VENT
PROV k. X 10" L. STEEL ANCHOR
FOR SILL PL. OF LIGHI FRAME
CONSTRUCTION EMBEDDED INTO
CONCRETE ~ NO MORE THAN 3L0" C.C.
@ 1 '-0" AWAY FROM EACH CORNER
(TYPICAL AROUND FOUND, pERIMETER)
VENT
FOUNDATION PLAN
PROV, 2- I 3/4" X 11 7/8" LVL MICROLLAM
FLUSH HEADER UNDER ALL PARTITIONS
O~-RACTOR TO NOTIFY THE ARCHITECT
OF ANY AND ALL REVISIONS DUE TO FIELD
CONDITIONS, CLIENT, AND OR GENERAL
CONTRACTOR WHICH DIFFER FROM THE
CONSTRUCT, DRAWIN CS/8 PECIFIOATIONS
25'
Iq
11 7/8" TJI 380 @
-16" C.C. (TYP. ALL NE'C/)
TOP OF NEW F.J. TO BE FLUSH~
~ WITH TOP OF EXISTING F.J.
91
PROV, DBL, 2"X 12" R,R,
-,%
EXISTING HSE.
NEW 2" X 6" STUD WALL
PROV. CONTINUOUS I 3/4" X 11 7/8"
"GP - FIBERSTRONG~r RIM BOARD.
(TYP. ALL PERIMETER AREAS).
FIRST FL. DECK FRAMING PLAN
OFFICE SET
9.7.07
<
0
o
SCALE:
1/4"= 1 '0"
DWG. NAME:
FRAMING
P~NS
A.1 -1
PROV, 2- I 3/4" X 11 7/8" LVL MIC
FLUSH HEADER
11 7/8" TJI 860 ~ .
-16" C.C. (TYP, ALL NEW)
11 7/8" TJI 360 ~, .
-16" C.C. ¢'~P, ALL I~EVV~
PROV. ;3- I 3/4" X 11 7/8" LVL MICROLLAM
FLUSH HEADER UNDER ALL PARTITIONS
(TYp. ALL PERIMETER AREAS).
LIVING RM..~
11 '-8" X 22'-4"
-16" O,C, (TYP, ALL
PROV. DE~L, 2" ~( 12" WINDOW & DOOR
HEADER (TYp. ALL NEW AERAS)
PROV 2- I 3
PROV. 2- I 3/4" X 11 7/8" LVL MICROLLAM
HEADER (FLUSH W/BOSq'OM OF C.J.) --
~IOROLLAM
PARTITIONS
1ST. FL. CEILING FRAMING PLAN
. PROV. 2 - 2" X 10"
WINDOW HEADERS
(TYP, ALL NEW)
2" X I
2" X 8" O.J. 16" O,C,
@ 16" O.C.BELOW.
RIDGE BEAM.
2"X 10'~R,R, (~ 16%
- O.C, (TYP. ALL)
REPLACED IN-KIND
ROOF & CLNG FRAM'lNG PLAN
~ONTRACTOR TO NOTIFY THE ARCHITECT
OF ~,_N.Y~,ND ALL REVISIONS DUE TO FIELD
CONDITIONS, CLIENT, AND OR GENERAL
CONTRACTOR WHICH DIFFER FROM THE
CONSTRUCT DRAWl N G 8/8 PECI FICATIO
OFFICE SET ]
9.7,07
Oo
Z>
0z
<
0
Z
--0
CJ
SCALE:
DWG. NAME:
1ST. FL. CEILING~
ROOF FRAMING
P~N
A.1 -2
FRO N~E'E~VATI O N
EXISTING HOUSE
RIGHT-SIDE ELEVATION
EXISTING HOUSE
PROV, CONT, "COBRA" RIDGE VENT
AND HIPS),
81
22'-10" +/-
FIN. GRADE
TO RIDGE
(PROPOSED) ~ ~
NEW VINYL BEVELED SIDING
COLOR & STYLE T,B,D, BY OWNER
NOTE:
CONTRACTOR TO NOTIFY THE ARCHITECT
OF ANY AND ALL REVISIONS DUE TO FIELD
CONDITIONS, CLIENT, AND OR GENERAL
CONTRACTOR WHICH DIFFER FROM THE
EXISTING HOUSE
REAR ELEVATION
EXISTING HOUSE
14'-1"
GRADE TO
/~ RIDGE
(~ISTING)
LEFT-SIDE ELEVATION
OFFICE SET
9.7.07
0 Q
~_,,o ~o ~o
d
w o r~ o
1/4" = 1 '0"
PROPOSED
ELEVATIONS
A.2
81
22'-9" +/-
FIN. GRADE
TO RIDGE
(PROPOSED)
81
61
10d NAILS OR
16d SINKERS
3" ¢
STRONG-WALL
SHEARWALL
PRE-A~TACHED
REF. TO A-3 FOR PILING
GIRDER CONNECTION,
METAL FASTENER SCHEDULE
(EXAMPLE)
(ALL STRAFING TO BE @ 16" O.C,)
TRUSS/RAFTER
-- TO TOP pLATE
(RPS4}
TRUSS BRACING
(UTS12)
iTUD TO STUD
(CS16)
3 TO BAND JOIST
(OS16)
:~DER ANCHORAGE
(LSTA18)
PROM. 11 7/8" BOX BEAM
SILL PLATE TO
DOUBLE GIRDER.
(BP)
PROM. METAL FLASHING
AT ALL WINDOW SILLS.
¢FYP. ALL LOCATIONS)
SECTION A-A
RIDGE
BEAM
KANT-SAG LSTI22 OR
ON LSTA21 STRAP
~6~ 10d X I 1/2 FASTENER
(STRAP REQUIRED FOR 16" JOIST
DEPTH OR MEMBERS WITH SLOPE
CONNECTION OF RIGDE
BEAM TO ROOF RAFTER
(EXAMPLE)
CORNER CONNECTION
(EXAMPLE)
X- BRACING
(EXAMPLE)
81
22'-9" +/-
FIN. GRADE
TO RIDGE
(PROPOSED)
81
CLIP ANGLE (BOTH SIDES OF
CONNECTION) MIN, LENGTH = JOIST
WEB DEPTH MINUS 1/2"
8 SCREWS (4 PER LEG
JOIST TO HEADER JOIST
(EXAMPLE)
WALL
(3) 2"X 10"
WIN[
HEADER
ROOF
TRUSS
SHEATING TO
TOP PLATE.
DOUBLE
TOP PLATE
MI~TAL HURRICANE
CO)NNECTOR
WALL
SHEATING
CONNECTION OF TOP
WALL PLATE TO WALL STUD.
(EXAMPLE)
LVL RIDGE BEAM (TYP.)
PROM. 8/8~ AOQ. PLY. SHEATHING
(TYPICAL ALL ROOF AREAS).
PROM, "LIFETIME" "GAF" ASPHALT
ROOF SHINGLES (TYP. ALL AREAS)
OVER 15 LB. FELT, (COLOR T.B,D.)
PROV, "WEATHERWATCH" UNDER-
LAYMENT ALONG ENTIRE BOqq'OM
EDGE OF ROOF UP 2~-0" (TYPICAL)
ALL ROOF SECTIONS).
PROM. "TYVEK DRAIN WRAP"
TAPE ALL TYVEK SEAMS,
(TYPICAL ALL SURFACES),
(TYP. ALL AREAS)
PROV, BLOCKING FOR T,J.L JOISTS
PROM, OONT "AZEK" BEAD BOARD
SOFFIT W/SCREENED 1" VENT
(TYPICAL ALL AREAS)
PROM. 5" EXPOSURE VINYL CEDAR
SIDING ("CEDAR IMPRESSIONS" BY
"CERTAINTEED" OR APP. EQUAL.
R - 21 HIGH DENSITY FOIL FACE
INSULATION. ("F~P. ALL AREAS)
2" X 6" WOOD STUDS ~
PLYWOOD SHEATHING, (TYPICAL)
STUD
CONNECTION OF WALL
TO WINDOW
HEADER
~IECTION OF WALL
'4G TO 2"X 6~' STUDS
JACK
STUDS
CONNECTION OF WALL SHEATHING
TO WINDOW HEADER
( EXAM P L E)
(2) 2" X 4" TOP PLATE
BIRDSMOUTH CUT
LOW END OF JOIST ONLY
(EXAMPLE)
NOTE: ]
~-RACTOR TO NOTIFY THE ARCHITECT
OF ANY AND ALL REVISIONS DUE TO FIELD
CONDITIONS, CLIENT, AND OR GENERAL
CONTRACTOR WHICH DIFFER FROM THE
CONSTRUCT DRAWINGS/SPECIFICATIONS.
PROM. CONT. "COBRA" RIDGE VENT
RIDGE AND HIPS).
R - 38 HIGH DENSITY FOIL FACE
(TYP. ALL AREAS)
2" X El" C,T. ~ 18" C.C.
BD ALL
EXPOSED WALLS
& CEILINGS (TYP.)
PROM. 3/4" T & G PLY~/OOD
SUB-FLR. tTYP, ALL AREAS). \
PROM. 3/4" X 3" W. RED OAK
"SELECT" WOOD FLOORING
AT AREAS NOTED ON PLAN.
IDOWS
IN LIEU OF DOUBLE PLATE. (TYP.
SECOND FL. LEFT/RIGHT ELEVATIONS)
PROVIDE CONTINUOUS 2 X 10
RAFTER TAILS.
¢FYPICAL ALL AREAS)
6" WHITE ALUMINUM GU'~FER AND
(TYPICAL ALL AREAS},
PROM,
COATS "BENJAMIN-MOORE" PAINT
OR APP. LQ. (TYP. ALL AREAS)
PROM CONTINUOUS I 1
"GP - FIBERSTRONG" RIM BOARD.
EXCEPT AREAS OF OPENINGS. (~YP.
ALL PERIMETER AREAS).
PROM. 2 - I 3 7/8" "GP LAM"
LVL HEADER ABOVE ALL WINDOW
& DOOR OPENINGS
7/8 "TJ1360 ~ 16" C.C.
PROM. CONTINUOUS I 1/8" X 11 7
"GP - FIBERSTRONG~' RIM BOARD.
EXCEPT AREAS OF OPENINGS. (TYP
ALL PERIMETER AREAS).
PROV. WATER BARRIER BETVVEENI
FOUNDATION WALL & RIM JOIST,
PROM. DBL. 2" X 6" ACC, SILL PLATE
(TYPICAL ALL AREAS)
4" P. CONE3 SLAB
PROM. W.W.M. IN SLAB
OVER GRAVEL TAMPED BASE.
~. 8" P. CONC. FOUNDATION WALL
WITH 1'-4" W, X 1'-0" D, P. CONC,
FOOTING (CONT*} W/W,W M, IN
WALL AND FOOTING,
-- WALL STUD
-- WALL STUD
BO~FOM pLATE
BAND JOIST
HEADER
STUD
JACK'
STUDS
CONNECTION OF WINDOW
SIMPSON LSTA16 STRAP WITH
(12) 10d FASTENER.
MEMBER FLOOR SUPPORT BEAM
FLOOR FRAMING
SIMPSON LSTA18 S~IFRAP WITH
(12) 10d FASTENER.
CONNECTION OF BALND JOIST TO SUPPORT
SIMPSON LTP4 STBAIP (12) 8d X I 1/2"
CONNECTIION OF WALL
TO FLOOIR FRAMING.
(EXAMPLE)
TWO- MEMBER FLOOR
SUPPORT BEJAM
CONNECTION OIF FLOOR FRAMING
TO SUPPORT BEAM. SIMPSON LTS12
STRAP WITH 12)) 10d X I 1/2 FASTENER
INTO FLOOR JO IST AND SUPPORT BEAM
CONNECTION OF FLOOR FRAMING
TO SUPPORT BEAM.
(EXAMPLE)
CONNECTION OF WALL SHEATHING
OFFICE SET 1
9.7.07
TO STUDS AROUND WINDOW HEADER
(EXAMPLE)
7>-
<
0
SCALE:
1/4" = 1 '0"
DWG. NAME'
BUILDING
SECTION
CONSTRUCTION
DETAILS
A.3
FASTEST MILE WlNDSPEED (MPH)
PRESCRIPTIVE DESIGN TABLE 3,2 (AMERICAN FOREST & PAPER ASSOCIATION
9O 100 110 120
Of (FT.)
STORIES: REQUIRED CAPAC TY OF CONNECT ON (LBS) ~'"
20 58 % * 681 264 ~* 681 206 ~* 681 291 681
24 89 % I 325 260 355
SILL PLATE TO __
FOUNDATION 2 28 119 % 356 ~ 314 % 426
(CRAWL SPACE OR 32 149 r,,l, A. 447r,,l ,A. 35.I~ ,A. 4,3
BASEMENT) I
CODES. 36 179 ! X 509 % 422 X 561
24 58 N~4S* 421 128 ~ 421 206 ~l~k 421 291 254 421 ,
WALL BO~FOM % I 170 260 358
PLATE TO 25 89
FOUNDATION 2 32 119 211 314 426
FASTEST MILE WlNDSPEED (MPH)
PRESCRIPTIVE DESIGN TABLE 3,3 (AMERICAN FOREST & PAPER ASSOCIATION
90 100 110 120
SPACING (IN.) (FT.)
REQUIRED CAPACITY OF CONNECTION (LBS)~'~"
16 12 %-%~ 93% 2~:~ 191 280 I 325 264 ~35 2;0 421 341 ~84 280 826 427 Si9 2;0
20 282 % % 386 % 500 % 626
I
16 24 327 ~%~ ,.__ 447 ~ 580 ~ 726
28 371 509 660 828
32 416 ~ 570 740 927
36
461
U' = CONNECTOR UPLIFT LOAD,
L4 = CONNECTOR LATERAL LOAD, (PERPENDICULAR TO THE WALL)
S = CONNECTOR SHEAR LOAD, (PARALLEL TO THE WALL)
~ TABULATED UPLIFT REQUIREMENTS ASBUME A ROOF/CEILING DEAD LOAD OF 10 PSF(2/3 X 15 pSF),
~ TABULATED UPLIFT AND LATERAL CONNECTION REQUIREMENTS SHALL BE PERMI~FED TO BE MULTIPLIED BY 0,70 AND 0,85, RESPECTIVELY, FOR FRAMING NOT
LOCATED WITHIN 8 FEET OF BUILDING CORNERS,
~ TABULATED UPLIFT LOADS ARE SPECIFIED FOR ROOF-TO-WALL CONNECTIONS. WHEN CALCULATING UPLIFT LOADS FOR WALL-TO-WALL OR WALL-TO
FOUNDATION CON NEOTIONS, TABULATED UPLIFT VALUES SHALL BE PERMITFED TO BE REDUCED BY 66 PLF (2/3 X 100 PLF) FOR EACH FULL WALL ABOVe,
*TABULATED LENGTH REQUIREMENTS ASSUME A MEAN ROOF HEIGHT OF 33 FEET. FOR MEAN ROOF HEIGNTS OF 15 FEET OR LESS, IHS TABULATED VALLUES
SHALL BE PERMI~ED TO BE MULTIPLIED BY 0,80.
SILL OR BOTTOM PLATE TO FOUNDATION ANCHOR BOLT CONNECTIONS
RESISTING LATERAL & SHEAR LOADS
PRESCRIPTIVE DESIGN TABLE 3.2A ALTERNATIVE TO TABLE 3.2 (AMERICAN FOREST & PAPER ASSOCIATION)
1/2" ANCHOR BOLTS 5/8" ANCHOR BOLTS
ANCHOR BOLT
CONNECTION
FOUNDATION
SUPPORTING
BRACING WALL PERIMETER
EDGE NAIL SPACING
FASTEST-MILE WIND SPEED
(MPR)
90I 10011101120
MAXIMUM ANCHOR BOLT
SPACING (IN.)
FASTEST-MILE WIND SPEED
(MPH)
MAXIMUM ANCHOR BOLT
SPACING (IN.)
SILL PLATE TO FOUNDATION*
CRAWL SPACE OR BASEMENT) 2 STORIES ALL~ 23 36
32 19 28
6a
36
1-3 STORIES
WALL PLATE TO FOUNDATION*
(SLAB-ON-GRADE)
57
U = CONNECTOR UPLIFT LOAD,
L = CONNECTOR LATERAL LOAD. (PERPENDICULAR TO THE WALL)
S = CONNECTOR SHEAR LOAD. (PARALLEL TO THE WALL)
*ANCHORAGE REQUIRED TO RESIST LATERAL LOADS SHALL BE D~FERMINED IN THE FOUNDATION DESIGN PER SECTION 1.1.4.
~ ANCHOR BOLT SPACINGS BASED ON MAXIMUM SHEAR CAPACITY OF UNBLOCKED ROOF AND/OR FLOOR DIAPHRAMS (279 PLF),
~ ANCHOR BOLT SPACINGS BASEDON MAXIMUM SHEAR CAPACITY OF BRACING WALL PERIMETER EDGE NAIL SPACING OF 3" O,C, (731 PLF) BUILT
IN ACCORDANCE WITH SECTION 3,4,4
' ANCHOR BOLT SPACINGS BASEDON MAXIMUM SHEAR CAPACITY OF BRACING WALL PERIMETER EDGE NAIL SPACING OF 6" O.0, (421 PLF) BUILT
IN ACCORDANCE WITH SECTION 3,4,4,
SILL OR BOTFOM PLATE TO FOUNDATION ANCHOR BOLT CONNECTIONS
RESISTING UPLIFT
PRESCRIPTIVE DESIGN TASLE 3,25 ALTERNATIVE TO TABLE 3,2 (AMERICAN FOREST & PAPER ASSOCIATION)
1/2" ANCHOR BOLTS 5/8" ANCHOR BOLTS
FASTEST-MILE WIND SPEED FASTEST-MILE WIND SPEEE~
(MPR) (MPH)
90I 10011101120 90I 100I 110 I 1'~0
ANCHOR BOLT FOUNDATION SUPPORTING: MAXIMUM ANCHOR BOLT MAXIMUM ANCHOR BOLT
CONNECTION SPACING (IN,) SPACING (IN,)
SILL pLATE TO FOUNDATION* ?'2
(CRAWL SPACE OR BASEMENT) 1-3 STORIES 72 72 72 72 72 72 72
WALL PLATE TO FOUNDATION 1-3 STORIES 40 35 28 25 51 42 36 32
(SLAB-ON-GRADE)
RAFTER/CEILING JOIST TO TOP PLATE
LATERAL AND SHEAR CONNECTION
REQUIREMENTS
PRESCRIPTIVE DESIGN TABLE 3,3A ALTERNATIVE TO TABLE 3,3
(AMERICAN FOREST & PAPER ASSOCIATION)
1/2" ANCHOR BOLTS
FASTEST-MILE WIND SPEED
(MPH)
RAFTER/
CEILING JOIST WALL HEIGHT MAXIMUM ANCHOR BOLT
(FT,) SPACING (IN,)
SPACING (IN,)
10 3 ~ 3 4
HOD BOX NAILS CAN BE SUBSTITUTED FOR 8D COMMON NAILS,
"WHEN CEILING JOISTS ARE INSTALLED PARALLEL TO RAFTERS, THE SUM
OF THE TOE NAILS IN THE RAFTER AND CEILING JOIST SHALL EQUAL
OR EXCEED THE TABULATED NUMBER OF NAILS REQUIRED,
"TO AVOIB SPLI~FING, NO MORE THAN 2 TOENAILS SHALL BE INSTALLED IN
LA, SIDE OF A RAFTER OR GLO, JOIST WHEN FASTENED TO A 2 X6 TOP PL,
UPLIFT STRAP CONNECTION REQ.
(ROOF-TO-WALL, WALL-TO-WALL, AND
WALL-TO- FO U N BAIl ON)
PRESCRIPTIVE DESIGN TABLE 5,35 ALTERNATIVE TO TABLE 3,3
(AMBBICANEOREST~PAPER^SSOC,) ~0 I 100 I 110 I 120
FRAMING SPACING ROOF SPAN NUMBER OF 5D COMMON NAILS
(IN,) (FI,) END OF 1-1/4" X 20
12 2 3 3 3
16 2 3 3 4
20 3 4 3 4
16 24 3 4 4 5
28 3 4 4 5
32 4 5 5 6
36 4 4 5 7
U4 = CONNECTOR UPLIFT LOAD.
L4 = CONNECTOR LATERAL LOAD, (PERPENDICULAR TO THE WALL)
S = CONNECTOR SHEAR LOAD (PARALLEL TO THE WALL)
~ TABULATED UPLIFT REQUIREMENTS ASSUME A ROOF/CLG. D.L. 1 0 P,S.F.),
IF A CEILING ASSEMBLY IS NOT PRESENT OR IF THE CEILING ASSEMBLY IS
NOT CONNECTED TO THE ROOF ASSEMBLY, THE TABULATED NUMBER OF
NAILS SHALL BE INCREASED BY 1 NAIL AT EACH END.
"FOR WALL-TO-WALL AND WALL-TO-FOUNDATION CONNECTIONS. THE
TABULATED NUMBER OF NAILS SHALL BE PERMI~'ED TO SE REDUCED BY
1 NAIL AT EACH OF THE STRAP FOR EACH FULL WALL ABOVE.
"'"--'~-15" /--WALL
21"
CLEARANCE
TOILET, BATH AND
SHOWER SPACED
SCALE: 1 '=1/2"
~-- WALL
OR EXCEED THE TABULATED NUMBER OF NAILS REQUIRED,
TO A 2 X 6 TOP PLATE.
WALL
/-
- WALL
/
WALL
24" CLEARANCE
IN FRONT OF OPNG.
WALL
--15"/
CLEARANCE
1~--2" WALL
/
TOILET, BATH AND
SHOWER SPACED
SCALE: 1'=1/2"
~3" VENT
1/2"
,-1 1/2"
TUE
LINE
AT 1/8" SLOPE PER 1'-0"
PLUMBING RISER DIAGRAM
N.T.S.
OFFICE SET
9.7.07
7¢
<
0
"- 0
1/4" = 1 '0"
qAILING SOHED,
PLUMBING
RISER DIAGRAM
GENERAL NOTES
1 FAMILY DETACHED DWELLING
ZONE 11B
HEATING DAYS = 5750
MINIMUM EQUIPMENT PERFORMANCE
GENERAL FLOOR PLAN NOTES
1. DIMENSIONS SHALL TAKE PRECEDENT OVER SCALE DRAWINGS (DO NOT
SCALE DRAWINGS).
S. ALL INTERIOR WALLS TO BE COVERED WITH 1/2" GYPSUM BOARD WITH
METAL CORNER REINFORCING. TAPE, FLOAT, AND SAND (S-COATS).
3. WALLS COMMON TO GARAGE AND HOUSE TO HAVE A LAYER OF 8/8",
FIRE RATED GYPSUM BOARD AT GARAGE SIDE WITH 5'-0" RETURN ON
ADJACENT WALLS & CEILING, MANUFACTURED LUMBER REQ, 2 LAYERS
OF 5/8" FIRE RATEB GYPSUM BOARD
4, ALL BATH/TOILET AREA WALLS AND CLG, AD J, TO WET AREAS TO HAVE
WATER RESISTANT GYP, BD,, OR WALL TILE SET ON COHO, BD, OR APP, HQ,
GENERAL FRAMING NOTES
1. ALL WALLS, 2"X4" AND 2"X6", TO BE STUD GRADE OF BE'FrER 16" O,C.,
ALL OTHER FRAMING MATERIAL TO BE #2 DOUGLAS FIR OR BETTER.
2, ALL WOOD FRAMING IN CONTRACT WITH CONCRETE OR MASONRY
TO IBE PRESSURE TREATED,
3, PROVIDE DOUBLE FLOOR JOISTS UNDER ALL WALLS PARALLEL TO FLR.
JOIST SPAN DIRECTION UNLESS OTHERWISE SPECIFIEB,
4, PROVIDE X-BRACING OR SOLID BLOCKING ATA MAXIMUM OF 8'-0' O,C,
FOR ALL DIMENSIONAL LUMBER FLOOR JOISTS,
6, FLOOR CONSTRUCTION: 3/4" T. & G, PLYVVOOD SUBFLOOR, FINISHED
MATERIAL TO BE APPLIED OVER SUBFLOOR, GLUE AND SCREW PLYWOOD
TO FLOOR JOISTS,
6, ALL WINDOW AND DR, HDRS, TO BE MIN, (2) 2"X10" UNLESS OTHERWISE
SPEOIFIEB, ALL IHT, HDRS, TO BE (2) 2'X10" UNLESS OTHERWISE SPEOIFIEB,
7. PROVIDE FULL SOLID BLOCKING UNDER ALL BEARING WALLS,
8. ALL BMS, TO HAVE ADEQUATE BEARING AT EACH END OR AS SPECIFIED.
9, ALL FLUSH BM, AND JOIST INTERSECTIONS TO HAVE GALVANIZED HGRS,
10, TYPICAL EXTERIOR WALLS AND ROOF TO BE SHEATHED WITH 1/2" EXT,
GRADE PLY~VOOD. PLYVVOOD TO SPAN OVER ALL PLATES AND HEADERS,
11. PROVIDE INSULATION BAFFLES AT HAVE VENTS BETWEEN RAFTER.
GENERAL ELEVATION NOTES
1. EXT, FLASHING TO BE CORRECTLY INSTALLED AT ALL CONNECTIONS
BETWEEN ROOFS, WALLS, CHIMNEYS, PBOJECTIONS, AND PENETRATIONS
AS REQUIRED BY APPROVED CONSTRUCTION PRACTICES,
2, GENERAL CONTRACTOR TO PROVIDE ADEQUATE ATTIC VENTILATION &
ROOF VENTS.
3, PROVIDE APPROPRIATE SOFFIT VENTILATION AT OVERHANGS,
GENERAL PLUMBING NOTES
1. PLUMBING SUBCONTRACTOR TO BE RESPONSIBLE FOR COMPLIANCE W/
ALL APPLICABLE CODE AND SAFETY REQUIREMENTS,
2, IF WALL pLATES OR JOISTS ARE CUT DURING THE INSTALLATION OF
PLUMBING FIXTURES OR EQUIPMENT, PROVlBE BRACING TO THE FRAMING
PER ALL APPLICABLE CODES,
GENERAL HVAC SYSTEM NOTES
1. MECHANICAL SUBCONTRACTOR IS RESPONSIBLE FOR ADHERING TO ALL
APPLICABLE CODES AND SAFETY REQUIREMENTS,
2, HVAC SUBCONTRACTOR TO FULLY COORDINATE ALL SYSTEM DATA AND
REQUIREMENTS WITH THE EQUIPMENT SUPPLIER.
3. HVAC SUBCONTRACTOR TO PROVIDE FINAL SYSTEM LAYOUT DRAWING
& SUBMIT IT TO GENERAL CONTRACTOR, OWNER, AND EQUIPMENT
SUPPLIER FOR FINAL REVIEW,AND APPROVAL,
EMERGENCY ESCAPE/RESCUE OPENINGS
SECT, R310
1. MINIMUM OF ONE EMERGENCY ESCAPE AND RESCUE OPENING
REQUIRED IN EVERY SLEEPING ROOM,
2, OPENING SILL HEIGHT TO BE A MNIMUM OF 44 INCHES ABOVE FLOOR.
NET CLEAR OPENING SIZE TO BE A MINUMUM OF 5.7 SQUARE FEET.
4, MINIMUM OF 5,0 SC, FT, REQUIRED FOR GRADE FLOOR OPENINGS,
5, MIN. NET CLEAR OPENING SILL HT, LOCATED BELOW ADJ GROUND ELEV.
WINDOW WELL REC. ALLOW FOR DR. OB WINDOW TO BE FULLY OPENED.
S. MIN, OF S SQUARE FEET IN HORIZONTAL DIMENSION, MIN, WIDTH OF 36"
(ENCROACHMENT OF 6 INCHES PERMITTED FOR LADDER OR STEPS).
7. PERMANENT COMPLYING LADDER OR STEPS WHERE VERTICAL DEPTH
EXCEEDS 44 INCHES,
8, BULKHEAB ENCLOSURES WITH DIRECT EXTERIOR ACCESS PERMI'FI'EB
IF IN COMPLIANOEWlTH MINIMUM NET CLEAR OPENING REQUIREMENTS,
9. BARS, GRILLES, COVERS AND SCREENS PROHIBITED UNLESS DEVICES
ARE RELEASABLE OR REMOVEABLE FROM INSIDE WITHOUT USE OF KEY,
TOOL OR EXCESSIVE FORCE.
PERSPECTIVE BUILDING ENVELOPE REQUIREMENTS O/VINDOW AREA 30% OF GROSS EXTERIOR WALL AREA)
MAXIMUM vIAXIMUM
HEATING
DEGREE DAYS GLAZING CEILING EXTERIOR WALL FLOOR BASEMENT WALL SLAB PERIMETER CRAWL SPACE
U-FACTOR R-VALUE R-VALUE R-VALUE R-VALUE R-VALUE & DEPTH WALL R-VALUE
ZONE 115
0,45 R-38 R-21 R-30 R-10 R-9,2 FT R-38
5750
CLIMATE-SPECIFIC REQUIRED & PROPOSED
PROPOSED MINIIfVlUM NOTES:
DESCRIPTION R-VALUE R-VALUE
WALL TYPE I 10" P,CONC, 9' H. R - 10 B - 1C 6" P.CONC, FNDN, WALL ON TOP OF A CONT, FOOTING,
WALL TYPE 2 2"XS" W,D,STUD R - 21 R - 211 2" X 6" WOOD STUD WALL WITH 1/2 CDX PLY WD,
WALL TYPE 3 2"X4" W,D,STUD R - 15 R - 15 2" X 4" WOOD STUD WALL WITH 1/2" GYP, ED,
ROOF TYPE 2" X 12" DOUG FIR R - 38 R - 3¢ GAF TIMBERLINE LIFETIME ROOF SHINGLE,
FLOOR TYPE I 3/4" X 11 7/8" R - 21 R - 21t 1 3/4" X 11 7/8" TGI PRO, 550 F.J. @ 16" C.C.
CEILING TYPE I 3/4" X 11 7/8" R- 21 N/R 1 3/4" X 11 7/8" TGI PRO, 550 F.J. ~ 16" C.C.
SLAB 4" P,OONC, R - 9,2 R - 9, 2 4"' P,CONC,SLAB ON COMP, FILL W/W,W.M. 6 X 6 REINF,
NAILING SCHEDULE
PRESCRIPTIVE DESIGN TABLE S,1 (AMERICAN FOREST & PAPER ASSOCIATION
CONNECTION FASTENING SPACING
NO. COMMON
I RAFTER TO TOP PLATE (TOE-NAILED)@16" O,C, 3 5d PER RAFTER
2 CEILING JOIST TO TOP pLATE (TOE-NAILED) 3 8d PER JOIST
6 BLOCKING TO RAFTER (TOE-NAILED) 2-8D EACH END
7 RIM BOARD TO RAFTED (END-NAILED) 2-16D EACH END
8 TOP PLATE TO TOP pLATE (FACE-NAILED) 2-16D PER FOOT
9 TOP PLATE AT INTERSECTIONS (FACE-NAILED) 4-165 JOINTS-EACH SIBE
10 STUD TO STUD (FACE-NAILED) 2-16D 24" O,C.
11 HEADER TO HEADER (FACE-NAILED) 16D 16" C.C. ALONG EDGES
12 TOP OR BOTTOM PLATE TO STUD (END-NAILED) 2-16D PER 2 X 4 STUD
13 BO'~'OM PLATETO FLOOR JOIST, BAND JOIST, END JOIST
OR BLOCKING (FACE-NAILED) 2-16D PER FOOT
14 JOIST TO SILL, TOP PLATE OR GIRDER ¢-OE-NAILEB) 4-16D PER JOIST
15 BRIDGING TO JOIST (TOE-NAILED) 2-8D EACH END
16 BRIDGING TO JOIST (TOE-NAILED) 2-8D EACH END
17 BLOCKING TO SILL OR TOP PLATE (TOE-NAILED) 3-16D EACH BLOCK
18 LEDGER STRIP TO BEAM (FACE-NAILED) 3-16D EACH JOIST
19 JOIST ON LEDGER TO BEAM (TOE-NAILED) 3-8D PER JOIST
20 BAND JOISTS TO JOIST (END-NAILED) 3-16D PER JOIST
21 BAND JOIST TO SILL OR TOP PLATE (TOE-NAILED) 2-16D PER FOOT
HEATING & COOLING
CRITERIA ZONE 1 1 B
DETACHED ONE FAMILY WALLS,
MODE: HEATING OR COOLING 0.14
ROOF CEILING 0,031
CLIMATE AND GEOGRAPHIC DESIGN 'CR T =RIA
TABLE 301.2 (RESIDENTIAL CODE OF NEW YORK) CONTRACTOR TO NOTIFY THE ARCHITECT
ONDITIONS CLIEN r, AND OR GENERAL
GROUND WIND SEISMIC SUBJECT TO DAMAGE FROM" WINTER Of 4~;¢,1~1C H DIFF~ F'~MqTHE
SNOW
DESIGN
DESIGN O I',~lF~f~A~ N G S/S ~J'~T[o N S.
LOAD SPEED (MPH) CATEGORY WEATHERING FROST LINE
DEPTH TERMITE DECAY TEMP. ~E~U!RED
LOAD BEARING
VALUE OF
EXPOSURE SOIL 3,000 PSF MODERATE TO SLIGHTLY TO
45 PSF CATEGORY "B" "B" "SEVERE" 12" FOOTINGS HEAW MODERATE ZONE 11B = 11 ° YES
120 MPH
FLOORS, WALLS, AND CEILINGS
OVER OUTSIDE AIR,
DESCRIPTION INSULATION
R-VALUE U- FACTOR X AREA : UA
CEILING R-38 0.31 520 SQ.FT, 161
INTERIOR FLOOR R-38 0,31 420 SQ,FT, 130
EXTERIOR WALLS R-21 0.31 1,400 SC.FT. 434
TOTAL AREA 2,340 SQ,FT,
FLOORS AND FOUNDATIONS
INSUL, INSUL, U-FACTOR OR AREA OR
DESCRIPTION D~PTH R-FACTOR R-FACTOR X PER[METER UA
BASEMENT WALL 2'-0" R-10 0,56 446 SC,FT. 249
2, RAWLS FAC E WALL 2'-0" R-19 0.56 -- N/A
UNHEATED SLAB 4" R-4.5 N/A 446 SQ,FT, N/A
TOTAL PROPOSED "UA" 249
WALLS, WINDOWS, AND DOORS
INSULATION
DESCRIPTION R-VALUE U- FACTOR X AREA = UA
WALL R-21 UO=0,14 1,400 SQ,FT, 196
WINDOW R= ,3 / SC.FT. 0,35 161 SQ,FT, 56
DOOR N/A 0.35 72 SC,ET, 12
TOTAL AREA 1,633 8Q,FT,
DESIGN CRITERIA
REF. TABLE R301.2(2)
AMERICAN FOREST AND PAPER ASSOCIATION (AF&PA)
WOOD FRAME CONSTRUCTION
ZONE ROOF > 30° - 36.3 -30,3 -46,4
23,7 40" X 1,53 ROOF > 30°-40° Xl,53 WINDSPEEB
3 120 M/HR
DESIGN CRITERIA
REF. TABLE 1609.6.2.1 (1)
MAIN WlNDFORCE-RESISTING SYSTEM WIND LOADS FOR A BUILDING WITH ROOF HEIGHT OF 30 FEET LOCATED IN EXPOSURE Ba
WIND LOAD ROOF HORIZONTAL LOADS VERTICAL LOADS
VELOCITY DIRECTION ANGLE END ZONE INTERIOR ZONE END ZONE INTERIOR ZONE WINDWARD
OVERHANG
WALL ROOF WALL ROOF NINDWARB LEEWARD~ ¢VlNDWAR£ LEEWARD END INTERIOR
ROOF ROOF ROOF ROOF ZONE ZONE
TRANSVERSE 30~<ANGLE ~< 45' 25,7 17,6 20,4 14,0 9,9 -15,6 8.6 -13,4 -11,6 -13,0
120
23,7 ALL ANGLES 22,8 -11.9 15.1 -7,0 -27.4 -15.6 -19,1 -12,1 -41.1 -32,7
R-3 SINGLE FAMILY RESIDEN CE
OCCUPANCY & HT. CLASSIFICATIONS
PIROPOSED
USE
MINIMUM
PROPOSED SILOPE HT./
REQUIRED FURRED HT,
MINIMUM REQ'D.
1BT. FLOOR
344 SC, FT. N/rR
182 SC,FT. N/IR
50 SC.FT. N/eR
USE
INTERIOR ENVIRONMENT
SECTION 1202.4.1 & 1204.1
1 ST. FLOOR
GREAT RM. 344 SC,FT. 76 SC,FT.
M. BEDROOM 182 SC.FT. 45 SQ,FT,
M, BATH 50 SQ.FT, 6 SC.FT.
22% 6SQ.FT, 12%
28 SOFT, 12%
24% 45 SC.P-T, 24%
12%
OFFICE SET
9,7.07
<
0
-- 0
__.
SCALE:
1/4"---- 1 '0"
DWG, NAME:
ENERGY
CALCULATIONS