HomeMy WebLinkAboutHVAC Piping LeaksE. S. KALOGERAS,
ACEC Member
Suppo~ng Excellence
UNION SQUARE ONE UNION AVENUE RD #1 BOX 530 RIVERHEAD, NY 11901
Town Board
Town of Southold
Town Hall
Main Road
Sonthold, New York 11971
September 24, 1992
Gentlemen:
Re~
Engineering Report on HVAC Piping Leaks
at the Town Hall, Main Road, Southold, N.Y.
In accordance with your authorization, by Town Board resolution, we have completed our
investigation of the leaking HVAC piping system in the older portion of the Town Hall. An inspection
of the entire piping system was conducted on September 18th, 1992 jointly with your Town Engineer and
building maintenance personnel, whom we gratefully acknowledge. In addition, the services of a private
HVAC Contractor were solicited by the Town to aid us in the shutdown/startup of the system and
cutting/sampling of the existing pipe system. The HVAC Contractor was also present during the
inspection period and was an invaluable aid during our investigation. The ensuing engineering report is
a result of the efforts of all those present during our inspection of your HVAC piping system.
The piping system is entirely located in the basement of the Town Hall and consists of various
diameters and lengths of black iron, schedule 40, threaded and coupled pipe. All fittings or elbows are
also of similar material. The entire pipe network is wrapped with fiberglass insulation and covered with
cloth wrapping. The insulation is intended to maintain cooling/heating temperatures within the piping
system for distribution to the various fan coil units spread throughout the Town Hall. The fan coil units
function to maintain ambient room temperatures and relative humidity levels independent of outside air
temperature and conditions, wherever installed within the Town Hall.
The initial investigatory step was conducted by removing a portion of any insulation which
appeared stained from leakage or weapage, thereby exposing the underlying piping. Most of the piping
runs were located above suspended ceilings. In some cases, piping was located above older gypsumboard
ceilings covered over by the newer suspended ceilings. Some insulated piping runs were also constructed
along walls and ceilings, in an exposed fashion, in storage and maintenance moms. The exposed portions
of piping under the stained insulation was found to be encrustated with iron oxide and leaking. This is
likely due tO the failure of the insulation at those locations. It is our opinion that those failures of
insulation allowed warmer, humid air surrounding the piping to condense on the piping, specifically during
TEL: (516) 727-5135 / (516) 722-4040 FAX: (516) 722-5093
E. S. KALOGERAS,
Engineering Report ....(Cont'd)
Page 2.
September 24, 1992
the normal cooling operation periods of the summer. Gradually the condensate quantity increased such
that the insulation was completely soaked through its exterior cloth covering where it mixed with
additional oxygen in the surrounding air. This ~nixture of water and oxygen consequently reacted
chemically with the iron piping and caused corrosive ferrous oxide encrustation to form and continuous
deterioration of pipe joints, particularly at threaded locations such as elbows, couplings, etc., thus resulting
in leakage and structural disintegration of the pipe's exterior and threads at joints. The encrustation, in
most cases, was moderate to hea,,% depending on the particular location.
The final investigatory element was to determine the interior condition of piping system and the
effect of normal domestic water for heating and cooling passing through it. All initial and makeup water
for the heating/cooling system is supplied fi:om municipal sources, in this case from the Village of
Greenport's Water Supply System. We selected the worst leak area for a sample of the piping system to
be obtained. We felt that this location would be indicative of the majority of the piping system and if
found to be badly deteriorated, additional samples could be obtained fi'om other areas. To our delight and
surprise, the piping sample showed little if any corrosion on its interior after over 15 years of service life.
Because of this successful sample, we determined that additional sampling would be a waste of the Town's
investigatory appropriation, and we suspended further investigation of the interior condition of the piping.
Based on the results of our investigation, we recommend that the Town proceed with a minimal
remediation program to ensure that the integrity of the piping system is maintained throughout its useful
life (which should be approximately a minimum of fort5, (40) years). The remediation program we
recommend may be accomplished as a phased program either by Town Personnel or outside Contractors.
The latter is recommended so that modern, efficient techniques of remediation are continually applied to
the piping network. The following program of remediation is recommended:
PHAS'E1-
Remove and replace all heavily, surface corroded, piping and fittings with new
sections of galvanized~ or b'.ack irou. ~cl:edt:le 40 pipe and fittings (Generally in
those areas where large stains on the insulation covering were observed and evident
during our inspection period).
Remove all insulation on the heating/cooling system piping within the Boiler Room.
Completely clean to bare metal all pipe and fitting surfaces by sand blasting, wire
brushing or other means and apply an epoxy coating system prior to recovering with
insulation. Upon proper curing of new coating system, all piping should be
reinsulated with a modern material capable of providing trouble free operation and
preventing future condensation trod subsequent corrosion of the encapsulated piping.
Engineering Report.....(Cont'd)
Page 3.
September 24, 1992
PHASE 2-
Annually remove sections of fiberglass insulation from piping, clean and coat piping
as described for Phase 1 and reinsulate with modem insulating material. The extent
of such work annually would be dependant upon your fiscal capabilities and/or your
desire to complete as quickly as possible in order to minimize the effects of the
annual disruption of your office staffs normal operations. It is strongly
recommended that this remediation be completed not longer than five (5) years
henceforth.
ESTIMATED REMEDIATION COSTS -
The following costs are estimated for remediation of the HVAC piping system to prevent
surface corrosion and maintain its useful life cycle and are based on outside Contractors performing the
work:
PHASE 1 - Repair isolated sections of piping and completely reinsulate all
heating/cooling piping in the existing Boiler Room.
$ 4,800.00
PHASE 2 -
Remove and replace sections of insulation with more modern
material to maintain the integrity of the existing piping system.
4 years ~ $ 4,500.00/year
$ 18,000.00
Engineering costs for design and construction services are not included in the above values. We
would be happy to undertake such work on either a fixed cost basis or a per diem cost basis depending
on your preference. In either case, our fee would be a small amount and would ensure that the
remediation work is of the best quality, at the lowest possible cost to the Town to achieve long term
continued use of the heating/cooling pipe system. If you have any questions concerning this report, we
would be happy to meet with you to answer any questions you may have.
Respectfully submitted,
E.S. KALOGERAS, P.E.
CONSULTING ENGINEER
ESK:gd
cc: Mr. James Richter