HomeMy WebLinkAbout34373-ZFORM NO. 4
TOWN OF SOUTHOLD
BUILDING DEPA=RTMENT
Office of the Building Inspector
Town Hall
Southold, N.Y.
CERTIFICATE OF OCCUPkNCY
NO: Z-34166 Rte: 01/15/10
THIS u~KTIFIES that the building TOWER
Location of Pro~rty: 9245 MAIN RD EAST MARION
(HOUSE NO.) (STREET) (HAMLET)
County Tax Map NO. 473889 Section 31 Block 3 I~t 11.31
subdivision FiledMap NO. __ Lot No. __
conforms substantially to the Application for Building Permit heretofore
filed in this office dated JANIJARY 5, 2009 pursuant to which
Building Permit No. 34373-Z dated JD/gU~=Ry 5, 2009
was issued, and conforms to all of the requirements of the applicable
provisions of the law. The occupancy for which this certificate is issued
is EMERGENCY TELECOMMUNICATIONS TOWER AS APPLIED FOR PER ZBA #5972 DATED
3/8/07.
· ~ne certificate is issued to EAST MARION FIRE DISTRICT
(OWNER)
of the aforesaid building.
Bo~I~( ~DEP~TOF}~THAP~O%r~J~ N/A
R~C'~RIC3%L C~KTIFICATH NO. 08-0149 04/27/09
PLD)~EBS u~KTIFICATION DA'r~u3 N/A
Rev. 1/81
Form No. 6
TOWN OF SOUTHOLD
BUILDING DEPARTMENT
TOWN HALL
765-1802
APPLICATION FOR CERTIFICATE OF OCCUPANCY
This application must be filled in by typewriter or ink and submitted to the Building Department with the following:
A. For new building or new use: 1. Final survey of property with accurate location of all buildings, property lines, streets, and unusual natural or
topographic features.
2. Final Approval from Health Dept. of water supply and sewerage-disposal (S-9 form).
3. Approval of electrical installation from Board of Fire Underwriters.
4. Sworn statement from plumber certifying that the solder used in system contains less than 2/10 of 1% lead.
5. Commercial building, industrial building, multiple residences and similar buildings and installations, a certificate
of Code Compliance from architect or engineer responsible for the building.
6. Submit Planning Board Approval of completed site plan requirements.
B. For existing buildings (prior to April 9, 1957) non-conforming uses, or buildings and "pre-existing" land uses:
1. Accurate survey of property showing all property lines, streets, building and unusual natural or topographic
features.
2. A properly completed application and consent to inspect signed by the applicant. Ifa Certificate of Occupancy is
denied, the Building Inspector shall state the reasons therefor in writing to the applicant.
C. Fees 1. Certi~cate ~f ~ccupancy - New dwel~ing $25.~~~ Additi~ns t~ dwel~ing $25.~~~ A~terati~ns t~ dwel~ing $25.~~~
Swimming pool $25.00, Accessory building $25.00, Additions to accessory building $25.00, Businesses $50.00.
2. Certificate of Occupancy on Pre-existing Building - $100.00
3. Copy of Certificate of Occupancy - $.25
4. Updated Certificate of Occupancy- $50.00
5. Temporary Certificate of Occupancy - Residential $15.00, Commercial $15.00
New Construction: Y
Location of Property: q~.~'
House No.
Old or Pre-existing Building: (check one)
Street
Owner or Owners of Property: ~7'1~,3~ [~IOA/ ~'7L~7 ~[ ,'f'/tb I~'-' o~'''
Suffolk County Tax Map No 1000, Section ~ / Block ~..,~
Subdivision
Permit No.3 $/375
Health Dept. Approval:
Dar e o f Permit. ]/~'~/~
/ /
Filed Map.
Applicant:
Underwriters Approval:
Hamlet
Lot Ii'SI
Lot:
Planning Board Approval:
Request for: Temporary Certificate
Final Certificate:
(check one)
Fee Submitted: $
Applicant Signature
Electrical Inspectors, Inc.
308 Fast Meadow Aveau¢
East Meadow, NY 11554
Office: ($16) 794-0400 C631 )396-7~.74
Fax: (516) 794-5854
Wcb~ite: www.elec Ulcalin spec tots.corn
Email: in fo~elect ricalin~pectors.com
Mail To:
Charles M. Dwyer, Inc.
Charles Dwyer
1457 Montauk Highway
East Patehogue, NY 11772
License: 4278ME
Certi/IcateNumber: 08-0149
Mtml¢ipality: Southold, Town Of
Inspector: 125
l~sue Date: 4/27/2009
Propct~y Add~'c~s:
AT&T Wkelass
9245 Main Road
East Marion, NY 11939
ELECTRICAL APPR 0 VAL CER TIFICA TE
AREAS LISTED BELOW ARE APPROVED BY INSPECTION
AND FOUND TO BE IN COMPLIANCE WITH TI-13E NATIONAL ELECTRIC CODE
NO visual defects were found for the oleclrical inspection provided. No obviouz uasatlsfaotory conditions were found in thc areas
heroin below only.
... Comn~et~clal lnspe.~lon
~OOAmp $inglo Phase ~. ~gr~t~d ~ervlce, 200dm~ Single pltase DisConnect,
Duplicate Original/MH
Richard M. Bivo~
Philip F. Goehring
Chic f Electrical Inspector
Not valid uulcss signed blt
authorized Eli Agent
FORM NO. 3
TOWN OF SOUTHOLD
BUILDING DEPARTMENT
Town Hall
Southold, N.Y.
BUILDING PERMIT
(THIS PERMIT MUST BE KEPT ON THE PREMISES UNTIL FULL
COMPLETION OF THE WORK AUTHORIZED)
PERMIT NO. 34373 Z
Date JANUARY 5, 2009
Permission is hereby granted to:
for :
EAST MARION FIRE DISTRICT
PO BOX 131
EAST MARION,NY 11939
CONSTRUCTION OF AN EMERGENCY COMMUNICATIONS TOWER PER ZBA #5972 AS
APPLIED FOR. THIS PERMIT REPLACES BP 32920.
at premises located at 9245
County Tax Map No. 473889 Section 031
pursuant to application dated JANUARY
Building Inspector to expire on JULY
MAIN RD EAST MARION
Block 0003 Lot No. 011.031
5, 2009 and approved by the
5, 2010.
Fee $ 250.00
Authorized Signature
ORIGINAL
Rev. 5/8/02
FORM NO. 3
TOWN OF SOUTHOLD
BUILDING DEPARTMENT
Town Hall
Southold, N.Y.
BUII/DING PERMIT
(THIS PERMIT MUST BE KEPT ON THE PREMISES UNTIL FULL
COMPLETION OF THE WORK AUTHORIZED)
PERMIT NO. ~920 Z Date APRIL 19, 2007
Permission is hereby granted to:
MARION FIRE DISTRICT EAST
PO BOX 131
EAST MARION,NY 11939
for :
CONSTRUCTION OF A/q EMERGENCY COMMUNICATIONS TOWER PER ZBA #5972 AS
APPLIED FOR
at pre~n~ses located at 9245
County Tax Map No. 473889 Section 031
pursuant to application dated APRIL
MAIN RD EAST MARION
Block 0003 Lot No. 011.031
10, 2007 and approved by the
Building Inspector to expire on OCTOBER 19, 2008.
Fee $ 250.00 ,~~~~/~//~
ORIGINAL
Rev. 5/8/02
inf ig)/
Albany Office
I 1 Herbert
Albany, NY 12203
December 10, 2009
Mr. Richard Chiappa
Bechtel Telecommunications
95 Cheslaut Ridge Road
Montvale NJ 07654
Construction Completion Compliance Letter - AT&T: East Marion Fire District
Site no.: LI 1017
Dear Mr. Chiappa:
Per your request, Infmigy Engineering is providing this letter to serve as a tower foundation Construction
Completion Compliance LetXer for the above referenced site. Prior to issuance of this letter, a final
inspection of the tower's foundation installation was completed and subsequent md-lined construction
drawings, photos of construction process, and data from a post-construction caisson evaluation were
submitted to lnfmigy Engineering.
Per the information provided, lnfmigy Engineering confirms that the tower foundation installation was
performed in general accordance with foundation design drawings prepared by Paul J. Ford and Company,
Dated 01-03-08.
Please do not hesitate to contact me at (518) 434-2288, if you have any questions or comments.
Very truly yours,
John Stevens, PE
Infinigy Engineering PLLC
BL06 ~,EPI
TOWN OF SOUI~CLi?
2255 Sewell Mill Rd 11 Herbert Dr
Madettal, GA 30062 I.at, ham, NY 12110
678-444-4463 518~690-0790
www.infinio¥.com
Frr~l ,D ]~SPECTiON RElY)iRT I DATE
FO~A~ON (1S~
FO~A~ON (2~)
PL~G
~S~ATION PER N. Y.
STATE E~RGY CODE
,
TOWN OF SOUTHOLD
BUILDING ~EPARTMENT
TOWN HALL
SOUTHOLD, NY 11971
TEL: (631) 765-1802
BUILDING PERMIT APPLICATION CHECKLIST
Do you have or need the following, b~efore applying?
Board of Health
4 sets of Building Plans
..... i '~ ~ 7~ Planning Board approval
FAX: (631) 765-9502 ~-, ~-}r~ A,-'~ Survey_
www. northfork.net/Southold/ PERMIT NO.~ Check
~' Septic Form
·//
Examined 7//~ ,20~ Contact: ~ard G. Boyd,
APPLICATION FOR BUILDING PE~IT
INSTRUCTIONS
Date ~'~o ~.~ 2.% ,2006
Esq.
a. This application MUST be completely filled in by typewriter or in ink and submitted to the Building Inspector with 4
sets of plans, accurate plot plan to scale. Fee according to schedule.
b. Plot plan showing location of lot and of buildings on premises, relationship to adjoining premises or public streets or
areas, and waterways.
c. The work covered by this application may not be commenced before issuance of Building Permit.
d. Upon approval of this application, the Building Inspector will issue a Building Permit to the applicant. Such a permit
shall be kept on the premises available for inspection throughout the work.
e. No building shall be occupied or used in whole or in part for any purpose what so ever until the Building Inspector
issues a Certificate of Occupancy.
f. Every building permit shall expire if the work authorized has not commenced within 12 months after the date of
issuance or has not been completed within 18 months from such date. If no zoning amendments or other regulations affecting the
property have been enacted in the inter/m, the Building Inspector may authorize, in writing, the extension of the permit for an
addition six months. Thereafter, a new permit shall be required.
APPLICATION IS HEREBY MADE to the Building Department for the issuance of a Building Permit pursuant to the
Building Zone Ordinance of the Town of Southold, Suffolk County, New York, and other applicable Laws, Ordinances or
Regulations, for the construction of buildings, additions, or alterations or for removal or demolition as herein described. The
applicant agrees to comply with all applicable laws, ordinances, building code, housing code, and regulations, and to admit
authorized inspectors on premises and in building for necessary inspections.
East Marion Fire District
(Signature of applicant or name, if a corporation)
P.O. Box 131
East Marion, New York 11939
(Mailing address of applicant)
State whether applicant is owner, lessee, agent, architect, engineer, general contractor, electrician, plumber or builder
Owner
Name of owner of premises East Marion Fire District
(As on the tax roll or latest deed)
If applicant is a corporation, signature of duly authorized officer
(Name and title of corporate officer)
Daniel H. Wood, Commissioner, EMFD
Builders License No.
Plumbers License No.
Electricians License No.
Other Trade's License No.
1. Location of land on which proposed work will be done:
9245 Route 25
East Marion
House Number Street
County Tax Map No. 1000 Section
Subdivision
(Name)
Hamlet
31 Block 3 Lot 11.31
Filed Map No.
Lot
2. State existing use and occupancy of premises and intended use and oc,~upancy of proposed construc6on:
a. ~'x~stlng use and occupancy Publxc Safety - Flreh~0se
b. Intended use and occupancy
3. Nature of work (check which applicable): New Building_
Repair Removal Demolition
4. Estimated Cost $130,000.00
5. If dwelling, number of dwelling units N/A
If garage, number of cars N/A
Public Safety - Firehouse and Public Safety
Communications Tower
Addition Alt~ation
Other Wo~ Public Safety Communicatio
Tower (Description)
Fee
(To be paid on filing this application)
Number of dwelling units on each floor N/A
6. If business, commercial or mixed occupancy, specify nature and extent of each type of use. N/A
7. Dimensions of existing structures, if any: Front
Height. Number of Stories
Rear Depth
Dimensions of same structure with alterations or additions: Front
Depth. Height Number of Stories
Rear
Dimensions of entire new construction: Front
Height 12O' Number of Stories
Size of lot: Front 293 ' Rear 249 '
10. Date of Purchase 11/23/9 8 Name of Former Owner
Rear Depth
.Depth 342'
Eugene Kessler, as Executor of
the Estate of Herbert R. Mendel
11. Zone or use district in which premises are situated R40 and lib
12. Does proposed construction violate any zoning law, ordinance or regulation? YES__
NO
13. Will lot be re-graded? YES __ NO x Will excess fill be removed from premises? YES x
East Marion 9425 Route 25
14. Names of Owner of premises Fire District Address East Marion, NYPhoneno.
Name of Architect Address Phone No
Name of Contractor Address Phone No.
NO
477-0163
15 a. Is this property within 100 feet of a tidal wetland or a freshwater wetland? *YES __NO __ * IF YES, SOUTHOLD TOWN TRUSTEES & D.E.C. PERMITS MAY BE REQUIRED.
b. Is this property within 300 feet of a tidal wetland? * YES __ NO x
* IF YES, D.E.C. PERMITS MAY BE REQUIRED.
x
16. Provide survey, to scale, with accurate foundation plan and distances to property lines.
17. If elevation at any point on property is at 10 feet or below, must provide topographical data on survey.
STATE OF NEW YORK)
SS:
COUNTY OF Suf fol~9
Daniel H. Wood being duly sworn, deposes and says that (s)he is the applicant
(Name of individual signing contract) above named,
(S)Heisthe Commissioner of the East Marion Fire District, Owner of Premises
(Contractor, Agent, Corporate Officer, etc.)
~q&~,'~O~;~l*~[ and is duly authorized to perform or have performed the said work and to make and file this application;
that all statements contained in this application are tree to the best of his knowledge and belief; and that the work will be
performed in the manner set forth in the application filed therewith.
Sworn to before-me this
~,4 ~/'~ay of July 20 0 6
Notary Public
EDWARD JOHN BOYD 5th
Notary Public State of N~,'.~ York
02600376625 Suffolk County
Commi-,,sion Ex~es April 30, 200
PLANNIN(~ BOARD MEMBERS
Chair
wtt,t.ta.M j. CREMERS
KENNETH L. EDWARDS
GEORGE D. SOLOMON
JOSEPH L. TOWNSEND
October 14, 2009
Net Com Development
Att: Charles Eisenberg
30 Central Drive
Farmingdale, NY 11735
PLANNING BOARD OFFICE
TOWN OF SOUTHOLD
Site plan for E. Marion FD Telecom - final inspection
Located: 9245 Main Road, Mattituck
SCTM# 1000-31-3-11.31
M~II/NG ADDRESS:
P.O. Box 1179
Southold, NY 11971
O~'~'ICE LOCATION:
Town Hall Annex
54375 State Route 25
(cot. Ma/n Rd. & Youngs Ave.)
Southold, NY
Telephone: 631 765-1938
Fax~ 631 765-3136
Dear Mr; Eisenberg:
As per your request, the Planning Staff conducted a site inspection of the above property
on Thursday October 8, 2009 where the site work was determined to be in conformance
with your approved site plan.
Please note any future requested change to the site plan should include a copy of the
approved stamped site plan noting the location of the requested change. If you have
any questions regarding the above, contact me anytime. Thank you.
Sinca~rel. y
Kristy Win~Cer
Senior Planner
Cc:
Planning Board
Heather Lanza, Planning Director
Michael Verity, Chief Building Inspector
Jamie Richter, Town Engineer
APPEALS BOARD MEMBERS
Ruth D. Oliva
Gerard P. Goehringer
James Dinizio, Jr.
Michael A. Simon
Leslie Kanes Weisman
http://southoldtown.northfork.net
ZONING BOARD OF APPEALS
TOWN OF SOUTItOLD
Tel. (631) 765-1809 · Fax (631) 765-9064
Mailing Address:
Southold Town Hall
53095 Main Road · P.O. Box 1179
Southold, NY 11971-0959
Office Location:
Town Annex/First Floor, North Fork Bank
54375 Main Road (at Youngs Avenue)
Southold, NY 11971
FINDINGS, DELIBERATIONS AND DETERMINATION
MEETING HELD: MARCH 8, 2007
ZB File No. 5972 -- EAST MARION FIRE DISTRICT
Property Location: 9245 Main Road, East Marion
Zone Districts (split): HB Hamlet Business; R-40 Low Density Residential
CTM 31-3-11.31 containing 3.05 acres
SEQRA DETERMINATION: The Zoning Board of Appeals has visited the property under
consideration in this application and determines that this review falls under the Type II category of
the State's List of Actions, without further steps under SEQRA. In addition, the Town Planning
Board has issued a Negative Declaration with a Determination of Non-Significance dated September
11, 2006.
PROPERTY FACTS/DESCRIPTION: The applicant's property contains 3.05 acres owned by the
East Marion Fire District and improved with two Fire House structures, as shown on the site plan
prepared by Infinigy Engineering dated 8/17/06.
BASIS OF APPLICATION: The applicant requests a Variance under Section 280-69 (100-162A3,
A5), based on an application for a building permit and the Building Inspector's July 25, 2006 Notice
of Disapproval, concerning construction of a proposed wireless communication/telecommunications
monopole tower on property owned, leased or otherwise controlled by a special district approved by
the commissioners of the special district. The proposed tower will exceed the code limitation - with
a height greater than 10 feet above the average height of buildings within 300 feet of the facility, OR
higher than 10 feet above the average tree canopy height in that radius measured from ground level
if there are no buildings within 300 feet. Also, if there are no buildings within 300 feet of the
proposed facility site, all telecommunication towers shall be surrounded by dense tree growth to
screen views of the facility in all directions.
SPECIAL DISTRICT: The applicant, East Marion Fire District (EMFD), is an established special
district for emergency communications on at least 4.35 acres of land. The EMFD maintains its fire
station communication transmissions to and from this site, and the wireless communications tower
would be in a location that provides sufficient space and height to provide an installation of a 450 Hz
antenna, north of the firehouse.
SUFFOLK COUNTY ADMINISTRATIVE CODE: This application has been referred as required
under the Suffolk County Administrative Code Sections A 14-14 to 23, and the Suffolk County
Department of Planning replied in its communications dated November 24, 2006 and January 22,
Page 2 - March 8, 2007
ZB File No. 5972 - East Marion Fire Distdct ',
CTMNo. 31-3-11.31
2007 stating that the application is considered a matter for local determination as there appears to
be no significant county-wide or inter-community impact.
TOWN CODE CHAPTER 95 (268) LWRP CONSISTENCY: This application has also been referred
as required under Chapter 95 (268) of the Town Code, and LWRP Coordinator Mark Terry has
issued a determination dated Apdl 26, 2006, received October 23, 2006, stating that this application
is consistent with the Policy Standards.
FINDINGS OF FACT
The Zoning Board of Appeals held a public hearing on this application on November 30, 2006 and
January 25, 2007, at which time written and oral evidence were presented. Based upon all
testimony, documentation, personal inspection of the property, and other evidence, the Zoning
Board finds the following facts to be true and relevant:
AREA VARIANCE RELIEF REQUESTED: The applicant, East Marion Fire District, wishes to
construct a telecommunications monopole tower to support public safety communications antennas,
at a maximum height of 120 feet.
REASONS FOR BOARD ACTION: On the basis of testimony presented, materials submitted and
personal inspections, the Board makes the following findings:
1. Grant of alternative relief will not produce an undesirable change in the character of the
neighborhood or a detriment to nearby properties. The site where the monopole antenna will be
constructed is presently open space lying just north of the two structures that serve the community
of East Marion as a firehouse. The site has been used for many years for the pbrposes of storing
and maintaining fire fighting and associated support equipment such as fire trucks, hoses, ladders
and radio equipment to communicate during actual fires. The addition of this monopole antenna will
improve the reliability of the radio equipment currently in use.
2. The benefit sought by the applicant cannot be achieved by some method, feasible for the
applicant to pursue, other than an area variance. The East Marion Fire District only owns one piece
of real property, and it is upon this property that the monopole antenna will be erected. Security,
electrical supply, and proximity to the source of dispatch demand that the principal antenna be
located as close to the firehouse as possible.
3. The alternative relief granted herein is substantial. The variance sought by the applicant and the
alternative relief granted herein, will increase the antenna height at least 90% over the code
maximum. (The code requirement is a maximum of 60 feet in height.) Although a monopole
antenna of this size will create some visual change in the area, this change must be balanced
against the necessity of improving emergency communications for the community.
4. Granting of the alternative relief for a height variance will not have an adverse effect or impact on
the physical or environmental conditions in the neighborhood or district. The monopole antenna is
designed to withstand the highest anticipated wind velocities and constructed in accordance to
current engineering standards. All equipment required for powering and maintenance of the
antenna will be located within a securely fenced area surrounding the base of the monopole, which
Page 3 - March 8, 2007
ZB File No. 5972 - East Marion Fire District
CTM No. 31-3-11.31
will be screened by native plantings. All radio transmissions will be regulated by appropriate
agencies.
5. The alleged difficulty has not been self-created. It is necessary to update the means of
communications as technology advances with time. The current technology requires a certain tower
height in order to guarantee adequate coverage of the fire district.
6. The proposed height is not the minimum that is necessary to preserve and protect the character
of the neighborhood and the health, safety, and welfare of the community. The testimony presented
was not sufficient to persuade that the antenna height of 120 feet is necessary to provide the desired
coverage at the fire district. The Board considers the substantial alternative relief granted to be
sufficient to satisfy the applicant's needs and to meet reasonable concems of public safety.
7. Grant of the requested relief is the minimum action necessary and adequate to enable the
applicant to enjoy the benefit of a telecommunications tower facility, while preserving and protecting
the character of the neighborhood and the health, safety and welfare of the community.
RESOLUTION OF THE BOARD: In considering all of the above factors and applying the balancing
test under New York Town Law 267-B, motion was offered by Member Simon, seconded by Member
Oliva, and duly carried, to
DENY the variance as applied for, and in the ALTERNATIVE, to
GRANT a variance in the location shown on the 6-17-06 Infinigy Site Diagram (setbacks 105
feet from the north lot line, 196+/- feet set back from the westerly lot line), at a maximum
antenna height of 110 feet, subject to the following conditions:
1) The covering of the monopole shall be painted a color that will make it blend into the
area. The board suggests a neutral color such as gray or gray- blue.
2) No flag shall be placed upon the monopole antenna.
3) The monopole shall not be lighted except as required by law.
That these ZBA conditions be written into the Building Inspector's Certificate of Occupancy, when issued.
Any deviation from the variance given such as extensions, or demolitions which are not shown on the
applicant's diagrams or survey site maps, are not authorized under this application when involving
nonconformities under the zoning code. This action does not authorize or condone any current or future use,
setback or other feature of the subject property that may violate the Zoning Code, other than such uses,
setbacks and other features as are expressly addressed in this action.
The Board reserves the right to substitute a similar design that is de minimis in nature for an alteration that
does not increase the degree of nonconformity.
Vote of the Board: Ayes: Members, Oliva, Goehringeg, Simon, and Weisman. Nay: Chairman
Dinizio (in favor of requested 120 ft. hei~ht~. This Res~uti,~n was duly a~opted (4-1).
Ja,~a'-e'~'Dinizio Jr.~-C~airr~n-" /" 3/9/2007
Af~proved for Filing
\,
5
S 65'40'00" 19.58'
~' o~ .,..
A,,.OVEO AS nRE .S,ECnO"
UIJI~ITERS
CERTIFICATE
DATE~/PI!~ B.P., ~~ - REQUIRED BEFORE
~o°~ ~ '~ OPENING
NO'IN BUILDING DEPA~MENT AT
765-1802 8AM TO 4PM FOR THE
FOLLOWING INSPECTIONS: EAST MARION FIRE DISTRICT
~. ~OUNO*T,ON- ~0
~0" ,OU,EO CONC"~ ocCUPANCY
OR
~.,OU~H-FR*M,N~ ~ PLUM~,N~ USE IS UN~WFUk SITE NAME: EAST MARION
4. FINAL' CONSTRUCTION MUST WITHOUT CERTIFICATE
BE COMPLETE FOR C.O.
AL~ CONST,UCT'O" SHA~ UE~ TH" OF OCCUPANCY
REQUIREMENTS OF THE CODES OF NEW
YORK STATE. NOT RESPONSIBLE FOR
DESIGN OR CONSTRUCTION ERRORS.
D~WING INDEX R~ VICINI~ MAP ~ PROJECT INFORMATION
TO1 TITLE SHE~ A~ scoPE oF ~K: oFAN ~Nc~UNMANNEDcoMP~ND~LEC~MUNICA~ONAND 110' UNIP~.¢AC~LI~ IN~UDING ~E INSTA~ON
C01 SITE P~N A
~ ADDRESS: 9245 MNN R~
C02 D~AILED SITE P~N AND DETAILS A ~T ~ON.
CO~ G~DING, EROSION & SEDIMENT CONSOL NO~S A ~NO O~ER/APPLICANT: EAST MA~ RRE DISmlCT
P.O. BOX 151
C03 EL~ATION Vl~S A EAST MARI~, NY 11939
TAX ID NUMBER: 31-5-11.51
C~ CONSTRUCTION D~AILS A LA~O[ (NAD 83): 4~' 07'
~5 CONSTRUCTION D~AI~ A ~' ~ ~~ L~DE (NAD 83): 72' 20' 29.2'
C~ ~NDSCAPE P~N A ~ ~ ~ ~c~: TO~ ~ s~m~ .
E01 ~ERIOR GROUNDING P~N A CURE[NT U~: ,,[ STA~
~ / =~.~ ~ ,- ~C~MUNICA~S FACILI~
~ ' CUR~E,T zo,m,c: SPUT-Z~[D HB
~PHONE COMPANY: ~RIZON
COMPLY WITH ALL CODES OF m
NEW YORK STATE & TOWN CODES
AS REQUIRED AND CONDITIONS OF. SO,HOLD ~ :~ c~~~ ~ "~,J', ~ SITE QUALIFICATION PARTICIPANTS
A/E dOHN S~NS INRNIGY ENGINEERING (518) 454-2288
~ ~~ RF BILL SCHEIBEL BECH~L (651) 655-6650
i ? ~. [ ~, j g Y "ST MARION ~:~ T, TLE SHEET
"~* "' ~ ~ EAST MARION FIRE DISTRICT
CHERYL L. BONDARCHUK
USE: RESIDENTIAL - 1 FAMILY RESIDENCE
ZONED: R-40
%
ANTHONY LEKAKIS
USE: RESIDENTIAL VACNAT LAND
ZONED: R-40
LOT 1
GRAY/BLUE
-EXISTING
CONC. SL~
WMITE SWAN
~ USE: 1 FAMILY
RESIDENCE
N/F ZONED: R-40
EASTERNR.E,BREEZES
USE: 1 FAMILY
RESIDENCE
ZONED: R-40 ~_~.
SITE pLAN tS NOT TO SCALE.
ACTUAL RELD CONDmON OF
EXISTING BUILDING STRUCTURE IS
FROM PROPEEq'( UNES.
NOT WHAT IS DEPICTED ON THIS
PLAN, COMPOUND AND TOWER
SETBACK DIMENSIONS ARE TRUE
SYLVIA M. DALE¥
USE: 1 FAMILY RESIDENCE
ZONED: R-40
SYMBOLS AND MATERIALS
DETAIL REFERENCE
SEC~ONS AND DETAILS
CONCRETE
EARTH
GRAVEL/STONE
i n f i n i c-..,a/Y.
engineering
150 - 034-
NOTE: METES AND BOUNDS ARE TAKEN
FROM A SURVEY PERFORMED BY
PECONIC SURVEYORS PC, UCENSED
LAND SURVEYOR.
S 65'40'00' W
N/F
E.M. WAR MEMORIAL ASSOC,
USE: RESIDENCE
ZONED: HB
SITE PLAN
SITE LEGEND
PROPER~ LINE
FENCE LINE
ELECTRIC SERVICE
/ EXISTING
?
UTILrPf POLE
TELEPHONE SERVICE
PROPOSED CONTOUR
50 EXISTING CONTOUR
lEAST MARION FIRE DISTRICTt j;_ I
7
+
EAST MARION
9245 IvlAIN ROAD
I OESIGNED:
GENERAL NOTES:
1. SITE PLAN INFORMATION WAS WAS BASED ON VARIOUS SOURCES
OF INFORMATION INCLUDING FIELD NOTES & MEASUREMENTS
PERFORMEO BY INFINIGY ENGINEERING, PLLC OF NY.
2. THIS PROPOSAL IS FOR AR UNMANNED TELECOMMUNICATIONS FACILITY
CONSiSTING OF FENCED COMPOUND WITH UTILFFY RACK AND UNIPOLE.
,3. THE PROPOSED EAClLllY W~LL BE UNMANNED AND
DOES NOT REQUIRE WATER OR SEa/ER SERVICE.
4. THE PROPOSED FAClLll'K IS UNMANNED, AND IS NOT
INTENDED FOR HUMAN HABITATION AND THUS DOES NOT REQUIRE HANDICAP
ACCESS.
5. OCCUPANCY IS LIMITED TO PERIODIC MAINTENANCE AND INSPECTION
TIMES PER MONTH.
6. NO STROBIC UONTING IS INCLUDED IN THIS PROPOSAL.
7. NO NOISE, SMOKE, DUST OR ODOR WILL RESULT FROM
TH~S PROPOSAL
8. OUTOOOR STORAGE AND SOUD WASTE CONTAINERS ARE NOT PROPOSED.
9. EXTERIOR SIGNS ARE NOT PROPOSED.
10. NO NE~V ACCESS ROAD WILL BE REQUIRED UNDER THIS APPLICATION.
11. TOTAL AREA OF DISTURBANCE UNDER THIS PROPOSAL: 830 SF±
12. THE INCREASE IN STORM WATER RUNOFF DUE TO THE INCREASE IN
IMPE~OUS AREA IS INSIGNIFICANT. EX~STING DI~JNAGE PATTERNS WILL
NOT BE ALTERED. THEREFORE, DRAINAGE STRUCTURES ARE NOT PROPOSED.
ALL CONSTRUCTION FOR SITE IMPROVEMENTS SHALL CONFORM TO APPLICABLE
SPECIFICATIONS, STANDARDS, AND REQUIREMENTS OF THE GOVERNMENTAL
OR UTILITY AUTHORITIES HAVING JURISDICTION.
14. ALL EXISTING ACTIVE SEWER, WATER, GAS, ELECTRIC. AND OTHER
UTILITIES WHERE ENCOUNTERED IN THE WORK. SHALL BE PROTECTED
AT ALL TIMES, AND WHERE REQUIRED FOR THE PROPER EXECUTION OF
THE WORK, SHALL BE RELOCATED AS DIRECTED BY ENGINEERS.
EXTREME CAUTION SHOULD BE USED BY THE CONTRACTOR WHEN
EXCAVATING OR PIER DRILUNG AROUND OR NEAR UTILITIES.
CONTRACTOR SHALL PROVIDE SAFET¢ TRAININD FOR THE WORKING
CREW. THIS WILL INCLUDE BUT NOT UMITED TO A) FALL PROTECTION
B) CONFINED SPACE C) ELECTRICAL SAFETY D) TRENCHING & EXCAVATION
15. ALL SITE WORK SHALL BE AS INOICATED ON THE DRAWING AND
STIPULATED IN THE PROJECT SPECIFICATIONS.
16. IF NECESSARY, RUBBISH, STUMPS, DEBRIS, STICKS, STONES AND OTHER
REFUSE SHALL BE REMOVED FROM THE SITE AND DISPOSED OF LEC~J_LY.
17. THE SITE SHALL BE GRADED TO CAUSE SURFACE WATER TO FLOW
AWAY FROM THE RADIO EQUIPMENT AND ¢LAGPOLE AREAS.
18. THE SUBGRADE SHALL BE COMPACTED AND BROUGHT TO A SMOOTH
UNIEORM GRADE PRIOR TO FINISHED SURFACE APPLICATION.
19. ALL EXISTING ~NACTIVE SEWER, WATER, GAB, ELECTRIC AND OTHER
UTIUTIES, WHICH INTERFERE WITH THE EXECUTION OF THE WORK,
SHALL BE REMOVED AND/OR CAPPED, PLUGGED OR OTHERWISE
DISCONTINUED AT POINTS WHICH WILL NOT INTERFERE WITH THE
EXECUTION OF THE WORK. SUBJECT TO THE APPROVAL OF
ENGINEERING.
20. THE AREAS OF THE OWNERS PROPERTY DISTURBED BY THE WORK AND
NOT COVERED BY THE PROPOSED IMPROVEMENTS SHALL BE RESTORED
AS REQUIRED.
21. EROSION CONTROL MEASURES, IF REQUIRED DURING CONSTRUCTION,
SHALL BE IN CONFORMANCE WITH THE LOCAL GUIDELINES FOR
EROSION AND SED{MENT CONTROL.
22. ALL SITE WORK SHALL BE COORDINATED WITH THE PROPERTY OWNER
AS REQUIRED.
23. CONTRACTOR SHALL CONTACT DIG ALERT: 800-962-7962 TO
LOCATE' TO CONSTRDCT,ON.
.'?.',
PROPOSED 16'x22'
LEASE AREA --
'PROPOSED 110'
UNIPOLE IN NEUTRN.
GRAY/BLUE COLOR
--PROPOSED 290 SQ. FT. FENCED AREA
(6' BLACK VINYL COATED CHNN UNK FENCE)
DETAILED SITE PLAN
GEN[RAL SITE NOTES:
1. THE 5U~GRADE SHALL BE COMPACTED AND BROUGHT TO A SMOOTH
UNIFORM GRADE PRIOR TO FINISHED SURFACE APPUCATION.
2. ALL EXISTING ACTIVE SE~/ER, WATER, GAS, ELECTRIC, AND OTHER U~UT1ES
WHERE E]flCOUNT-r-RED IN THE WORK, SHALL BE PROTECTED AT ALL TIMES,
AND WHERE REQUIRED FOR THE PROPER EXECUTION OF THE WORK, SHALL BE
RELOCATED AS DIRECTED BY ENGINEERS. EXTREME CAUTION SHOULD BE
USED BY I~IE CO~TOR WHEN EXCAVATING OR PIER DRILUNG AROUND OR
NEAR UTILITIES. CONTRACTOR SHALL PROVIDE SAFELY TRAINING FOR THE
WORKING ENGINEER.
ALL EXISTING INACTIVE SEWER, WATER, GAS, ELECTRIC, AND OTHER UTILITIES,
WHICH INTERFERE WITH THE EXECUTION OF THE WORK, SHALL BE REMOVED AND/OR
CAPPED, PLUGGED OR OTHERWISE DISCON11NUED AT POIN~TS WHICH WILL NOT
INTERFERE WITI4 THE EXECUTION OF THE WORK, SUBJECT TO THE APPROVAL
OF AR ENGINEER.
4. THE SITE SHALL BE GRADED TO CAUSE SURFACE WATER TO FLOW
AWAY FROM ALL EQUIPMENT AND TOWER AREAS.
5. GARBAGE, STUMPS, DEBRIS. STICKS, STONES AND OTHER REFUSE SHALL
BE REMOVED FROM THE SITE AND DISPOSED OF IN A LEGAL MANNER..
6. THE AREAS OF THE OWNERS PROPER~ DISTURBED BY THE WORK AND NOT
COVERED BY THE BUILDING OR DRNEWAY, SHALL BE GRADED TO A UNIFORM
SLOPE, FERTIUZED, AND SEEDEO.
infini!j
engineering
150 - 034
EAST MARION
9245 MAIN ROAD
EAST MARION, NY 11939
lEAST MARION FIRE DISTRICT
A 21-07
,~UNISTRUT PIPE/CONDUIT CLAMp Pl119
OR P2558-B§ (GALV.) (1YPICAL)
BoLTFOLLOWToRQuEMANUF' RECOMMENDATIONS FOR
PIPE (GALV)
UNiSTRUT P1001 (GALV)
UNISTRUT
CONCRETE OR
SAKRETE PIER.
E~L:EC~/TELCO SUPPORT RACK ~
DETAILED SITE PLAN
AND DETAILS
GRADING & EXCAVATING NOTES:
1. ALL EXCAVATIONS ON WHICH CONCRETE IS TO BE pLACED SHALL BE SUBSTANTIALLY
HORIZONTAL ON UNDISTURBED AND UNFROZEN SOIL AND BE FREE FROM LOOSE
MATERIAL AND EXCESS GROUNDWATER. DEWATERING FOR EXCESS GROUNDWATER
SHALL BE PROVIDED IF REQUIRED.
2. CONCRETE FOUNDATIONS SHALL NOT BE PLACED ON ORGANIC MATERIAL. IF SOUND
SOIL IS NOT REACHED AT THE DESIGNATED EXCAVATION DEPTH, THE
UNSATISFACTORY SOIL SHALL BE EXCAVATED TO ITS FULL DEPTH AND EITHER BE
REPLACED WITH MECHANICALLY COMPACTED GRANULAR MAI[RIAL OR THE
EXCAVATION BE FILLED WITH CONCRETE OF THE SAME QUAMTY SPECIFIED FOR THE
FOUNDATION.
3. ANY EXCAVATION OVER THE REQUIRED DEPTH SHALL BE FILLED WITH EITHER
MEChaNICALLY COMPACTED GRANULAR MATERIAL OR CONCRETE OF I~IE SAME
QUALRY SPECIFIED FOR THE FOUNDATION. CRUSHED STONE MAY BE USED TO
STABILIZE THE BOTTOM OF THE EXCAVATION. STONE, IF USED, SHALL NOT BE USED
AS COMPIUNG CONCRE-IE THICKNESS.
4. AFTER COMPLETION OF THE FOUNDATION AND OTHER CONSTRUCTION BELOW
GRADE, AND BEFORE BACKFILMNG, ALL EXCAVATIONS SHALL BE CLEAN OF
UNSUITABLE MATERIAL SUCH AS VEGETATION, TRASH, DEBRIS, AND SO FORTH.
5. -USE APPROVED MATERIALS CONSISTING OF EARTH, LOAM, SANDY CLAY, S~ND
-BE FREE FROM CLODS OR STONES OVER 2-1/2' MAXIMUM DIMENSIONS
-BE PLACED IN 6" LAYERS AND COMPACTED TO 95% STANDARD PROCTOR
EXCEPT IN GR~SSED/LANOSCAPED AREAS. WHERE 90~[ STANDARD PROCTOR
REMOVE ALL VEGETATION, TOPSOIL, DEBRIS, WET AND UNSATISFACTORY SOIL
MATERIALS, OBSTRUCTIONS, AND DELETERIOUS MATERIALS FROM GROUND SURFACE
PRIOR TO PLACING FILLS. PLOW, STRIP, OR BREAK UP SLOPED SURFACES STEEPEN THAN
THAN I VERTICAL TO 4 HORIZONTAL SO FILL MATERIAL WILL BOND WITH EXISTING SURFACE.
WHEN SUBGRADE OR EXISTING GROUND SURFACE TO RECEIVE FILL HAS A DENSI'Pf LESS
THAN THAT REQUIRED FOR FIL~ BREAK UP GROUND SURFACE TO DEPTH REQUIRED,
PULVERIZE, MOISTURE-CONDITION OR AERATE SOIL AND RECOMPACT TO REQUIRED
DENSISY.
PROTECT EXISTING GRAVEL SURFACING AND SUBGRADE IN AREAS WHENE EQUIPMENT LOADS
WILL OPERATE. USE pLANKING OR OTHER SUITABLE MATERIALS DESIGNED TO SPREAD EQUIPMENT
LOADS. REPAIR DAMAGE TO EXISTING GRAVEL SURFACING OR SUBGRADE WHERE SUCH
DAMAGE IS DUE TO THE CONTRACTOB'S OPERATIONS. DAMAGED GRAVEL SURFACING
SHALL BE RESTORED TO MATCH THE ADJACENT UNDAMAGED GRAVEL SURFACING AND
SHALL BE OF THE SAME THICKNESS.
REPLACE EXISTING GRAVEL SURFACING ON AREAS FROM WHICH GRAVEL SURFACING IS
REMOVED DURING CONSTRUCTION OPERATIONS. GRAVEL SURFACING SHALL BE REPLACED
TO MATCH EXISTING ADJACENT GRAVEL SURFACING AND SHALL BE OF THE SAME
THICKNESS. SURFACES OF GRAVEL SURFACING SHALL BE FREE FROM CORRUGATIONS AND WAVES.
EXISTING GRAVEL SURFACING MAY BE EXCAVATED SEPARATELY AND REUSED IF INJURIOUS
AMOUNTS OF EARTH, ORGANIC MATrER, OR OTHER DELETERIOUS MATERIALS ARE REMOVED
PRIOR TO REUSE. FURNISH ALL ADDITIONAL GRAVEL RESURFACING MATERIAL AS REQUIRED.
BEFORE GRAVEL SURFACING IS REPLACED, SUBGRADE SHALL BE GRADED TO CONFORM TO
REQUIRED SUBGRADE ELEVATIONS, AND LOOSE OR DISTURBED MATERIALS SHALL BE THOROUGHLY
COMPACTED. DEPRESSIONS IN THE SUBGRADE SHALL BE FIllEr) AND COMPACTED WITH
APPROVED SELECTED MATERIAL. GRAVEL SURFACING MATERIAL MAY BE USED
FOR FILLING DEPRESSIONS IN THE SUBGRADE. SUBJECT TO ENGINEER'S APPROVAL
DAMAGE TO EXISTING STRUCTURES AND UTILITIES RESULTING FROM CONTRACTOR'S NEGUGENCE
SHALL BE REPNRED/REPLACED TO OWNER'S SATISFACTION AT CONTRACTOR'S EXPENSE.
CONTRACTOR SHALL COORDINATE THE CONSTRUCTION SCHEDULE WITH PROPERI'f OWNER SO AS
TO AVOID INTERRUPTIONS TO PROPER~f OWNER'S OPERATIONS.
ENSURE POSITh/E DRAINAGE DURING AND AFTER COMPLETION OF CONSTRUCTION.
ALL CUT AND FILL SLOPES SHALL BE MAXIMUM 2 HORIZONTAL TO 1 VERTICAL.
CONTRACTOR SHALL BE RESPONSIBLE FOR MONITORING SITE VEHICLE
TRAFRC AS TO NOT ALLOW VEHICLES LEAVING THE SITE TO TRACK
MUD ONTO PUBUC STREETS. THE CONTRACTOR IS RESPONSIBLE
FOR CLEANING PUBUC STREETS DUE TO MUDDY VEHICLES LEAVING
THE SITE.
i n f i n i
engineering
150-034
EAST MARION
9245 MAIN ROAD
GENERAL EROSION & SEDIMENT CONTROL NOTES:
1. THE SOIL ENOSION AND SEDIMENT CONTROL MEASURES AND DETAILS AS SHOWN
HERIN AND STIPULATED WITHIN STATE STANDARDS
SHALL BE FOLLOWED AND INSTALLED IN A MANNER SO AS TO
MINIMIZE SEDIMENT LEAVING THE SITE*
2. PRIOR TO COMMENCING LAND DISTURBANCE ACTMSY. THE
UMITS OF LAND DISTURBANCE SHALL BE CLEARLY AND
ACCURATELY DEMARCATED WITH STAKES, RIBBONS, OR
OTHER APPROPRIATE MEANS.
S. EROSION CONTROL DEVICES SHALL BE INSTALLED BEFORE GROUNO
DISTURBANCE OCCURS. THE LOCATION OF SOME OF THE EROSION
CONTROL DEVICES MAY HAVE TO BE ALTERED FROM SHOWN ON THE
APPROVED PLANS IF DRNNAGE PAl I~I<NS DURING CONSTRUCTION ARE
DIFFERENT FROM THE FINAL PROPOSED DRAINAGE PAT[ERNS. IT IS THE
CONSRACTOR'S RESPONSIBIMS~ TO ACCOMPLISH EROSION CONTROL FOR
ALL DRAINAGE PA~TERNS CREATED AT VARIOUS STAGES DURING CONSTRUCTION.
ANY DIFEICUL~Y IN CONTROLLING EROSION DURING ANY PHASE OF
CONSTRUCTION SHALL BE REPORTED TO THE ENGINEER IMMEDIATELY.
4. THE LOCATION OF SOME OF THE ENOSION CONTROL DEVICES
MAY HAVE TO BE ALTERED FROM THAT SHOWN ON THE
PLANS IF DRAINAGE PATTERNS DURING CONSTRUCTION ARE
DIFFERENT FROM THE FINAL PROPOSED DRNNAGE PATrERNS.
ANY DIFFICUL]Y IN CONTROLMNG EROSION DURING ANY PHASE
OF CONSTRUCTION SHALL BE REPORTED TO THE ENGINEER
IMMEDIATELY.
5. CONTRACTOR SHALL MAINTAIN ALL ENOSION CONTROL MEASURES UNTIL
PERMANENT VEGETATION HAS BEEN ESTABLISHED. CONTRACTOR SHALL
CLEAN OUT ALL SEDIMENT PONDS WHEN REQUIRED BY THE ENGINEER OR
THE LOCAL JURISDICTION INSPECTOR. CONTRACTOR SHALL INSPECT EROSION
CONTROL MEASURES AT THE END OF EACH WORKING DAY TO ENSURE
MEASURES ARE FUNCTIONING PROPERLY.
6, THE CONTRACTOR SHALL REMOVE ACCUMULATED SILT WHEN
THE SILT IS WITHIN 12' OF THE TOP OF THE SILT FENCE.
7. FAILURE TO INSTALL, OPERATE OR MAINTAIN ALL ENOSION
CONTROL MEASURES WILL RESULT IN ALL CONSTRUCTION
BEING STOPPED ON THE JOB SITE UNq]L SUCH MEASURES ARE
CORRECTED.
8. SILT BARRIERS TO BE PLACED AT DOWNSTREAM TOE OF ALL
CIJ~ AND FILL SLOPES.
9. ALL CUT AND FILL SLOPES MUST BE SURFACED ROUGHENED AND
VEGETATED WITHIN SEVEN (7) DAYS OF THEIR CONSTRUCTION.
10. CONTRACTOR SHALL REMOVE ALL ENOSION & SEDIMENT CONTROL
MEASURES AFTER COMPLE'rioN OF CONSSRUCTION AND
ESTABLISHMENT OF PERMANENT GROUND COVER.
11. THE ESCAPE OF SEDIMENT FROM THE SITE
SHALL BE PREVENTED BY THE INSTALLATION OF ENOSION CONTROL
MEASURES AND PRACTICES PRIOR TO, OR CONCURRENT WITH,
L~ND-DISTURBING ACff~qTIES.
EAST MARION FIRE DISTRICT
A 21-07
VEGETATIVE SCHEDULE
SPECIES RATE/1000 S.F. DATE
APPUCATION N, ~/ACRE TOP DRESSING
1st
2nd
NOTE:
FERTILIZER MIX
IP~ 0,. #/ACREI K~O. ~/ACRE IN.
60- 90 1201--:0100 1201-180:0 50
SEEDBED PREPARATION WILL BE REQUIRED, THE FERTIUZER, SEED AND WOOD CELLULOSE FIBEN
BE COMBINED TO FORM A HOMOGENEOUS MIXTURE, AND SPREAD UNIFORMLY OVER THE AREA
WILL BE APPUED WITH BLOWER-~YPE MULCH SPREADING EQUIPMENT WITHIN 24 HOURS AFTER
PERCENT OF THE GROUND SURFACE EXPOSED,
GRADE, SHAPE AND SMOOTH WHENE NEEDED TO PROVIDE FOR SAFE EQUIPMENT OPERATION AT
BE SPREAD UNIFORMLY OVER THE AREA IMMEDIATELY BEFORE SEEDBED PREPARATION, A
ON SITE. THE SEEDBED MUST BE WELL PULVERIZED, SMOOTHED AND FIRMED. SEEDING WILL
SEEDER. SEED WILL BE DISTRIBLqE:D UNIFORMLY OVER A FRESHLY PREPARED SEEDBED AND
UNIFORMLY OVER THE AREA, LEADING ABOUT 25 PERCENT OF THE GROUND SURFACE EXPOSED.
IMMEDIATELY AFTER IT IS SPREAD. A DISK HARROW WEH THE DISK SET STRAIGHT OR A SPECIAL
GRADING, EROSION &
SEDIMENT CONTROL NOTES
24897 ~NYCENY 017 C02A
i] INF'INIGY ENGINEERING HAS NOT EVALUATED THE1
EXISTING TOWER FOR THIS SITE. IT IS THE
CARRIER'S RESPONSIBIIJ~Y TO INVESTIGATE ANY
LOADING CONCERNS WHEN ADDING ADDITIONAL
EQUIPMENT TO THE TOWER.
(TO BE SUPPUED .~D
L~'TALLED BY OTHERS)
PROPOSED 6' BLACK
GRADE LEVEL = O' (AOL) (BY O~HERS)
PROPOSED 6' BLACK
VINYL CHAIN UNK
GRADE LEVEL = 32' (AMSL)
GRADE LEVEL ~ O' (AGL)
SOUTH ELEVATION
EAST ELEVATION
infini(.j
en~ineerino
1 §0-03~-
EAST MARION
9245 MAIN ROAD
EAST MARION, NY 11939
lEAST MARION FIRE DISTRICT
(~Y OTHERS)
TELEWAVE EXPOSED DIPOLE 450D6-9 10 FEET 30 FEET
ANDREW D3205 10 FEET 30 FEET
FIBER GLASS 5db ANDREW D3633 5 FEET TOP OF POLE
FIBER G!.~,SS 5db RFS 201 8 FEET 30 FEL-~
FIBER GLASS 5db ANDREW ASP680 11.7 FEET 50 FEET
ANTENNA MODEL DETAIL
ELEVATION VIEWS
~o3 t I sn~ f
24897 ~NYCENYI017
I
4'-0" GATE OPENING
COATED CHAIN MNK - UNE POST (TI'P,)
/ TfPE LATCH WITH PROVISION FOR
RAIL
PAIR
INDUSTRIAL
/
PADLOCK (PAGE-WILSON TfPE 75 ~--TOP RNL (TYP)
- BLACK VINYL ~: 5/8"e ]RUSS ROD WITH
I ~H, BOTi'OM TENSION WIRE 2" CON
ELECTRICAL COPPER BRND [~ ~ '
[- '- ~= SPACING O'YP.)
I I r6. FORENO,
1'-2" CORNER, & GATE
POSTS
-~-- F[NC£ NOIES:
in ,f.i n. j ~1 y F_*S~'~A.,O. CONSTRUCTION
~"o."~ o.,e.~e~ .,~ Ce/ EAST MARION FIRE DISTRICT DETAILS
i
150-034
MIN
FENCE- WHERE REQUIRED
~YPE C SILT FABRIC ON
UPSTREAM SIDE OF FENCE
DIRECTION
OF FLOW
1. DIG TRENCH
2. LAy IN FABRIC TO
BOTTOM OF TRENCH
3. BACKFILL TRENCH.
COVERING FABRIC
SILT FENCE DETAIL
CONSTRUCTION NOTES FOR FABRICATED SILT FENCE
WOVEN WIRE FENCE TO BE FAS~NED SECURELY
TO FENCE POSTS WITH WIRE TIES OR STAPLES.
FILTER CLOTH TO BE FASTENED SECURELY TO
WOVEN WIRE FENCE WITH TIES SPACED
EVERY 24" AT TOP AND MID SECTION.
WHEN 1WO SECTIONS OF FILTER CLOTH
ADJOIN EACH OTHER THEY SHALL BE OVER-
L~PPED BY SIX INCHES AND FOLDED.
MAINTENANCE SHALL BE PERFORMED AS
NEEDED AND MATERIAL REMOVED WHEN
'BULDGES" DEVELOP IN THE SILT FENCE.
ALL SILT FENCE MATERIALS MUST BE
USTED ON THE CURRENT STATES. D.O.T.
QUALIFIED PRODUCTS MST ~36.
POSTS: STEEL EITHER T OR U
TYPE.
FENCE: WOVEN WIRE, 14 GA. 6" MAX. MESH OPENING.
AS DIRECTED BY BANKS CO,
FILTER CLOTH: FILTER X, MIRAFI lOOX'
STABIUNKA T140N OR
APPROVED EQUAL.
PREFABRICATED UNIT: GEOFAB.
ENVIROFENCE OR APPROVED
EQUAL.
EAST MARION
9245 MAIN ROAD
EAST MARION, NY 11939
EAST MARION FIRE DISTRICT
A 21-07
1
-DP, N)E TO DRNN
AWAY FROM TOWER YN~D
SECTION THROUGH COMPOUND
CONSTRUCTION
DETAILS
C
~ TO RN~
TREE STAKING AND GUYING
1. ~DS S~ FOR~ IN "AMERI~ ~D~D FOR NURSE~ ~K', ~ EDEN, REPRESE~ GUIDEUNE
SPECI~ONS ONLY ~D S~ CONS~ MINIMUM QU~ REQUIR~E~ F~ P~ ~R~
2. ~ P~ ~E SU~ECT TO ~E ~R~ OF ~E ENGINE~'S REPRESE~A~ BEFORE,
DURING, ~D ~R INfO'ON.
5. PRI~ TO CON~U~ION, ~E CO--TOE S~ BE RES~NSIB~ FOR L~NG
UN~RG~ND ~1~ ~D S~ A~ID ~GE TO ~ ~ES DU~NG C~RSE OF ~E W~K.
~E CO~OR IS RES~NSIB~ FOR REPNRING ~ ~E TO ~,
~UC~RES, ~ ~PU~C~, ~C. ~ICH ~CU~ ~ A R~LT OF ~E ~DS~E CONiStON.
6. ~ TRE~ WU~ BE ~ ~NKED, ~ H~ED ~D ME~ ~ RE~IR~E~ SPECIR~.
~. ~ m~ vu~ ~[ O~D OR ~A~D ~ SH~.. ~NSCAPING P~N
8. ~ P~ ~D P~NG ~ MU~ BE ~MP~LY MULCHED ~ SPEClR~.
9. ~E ENGINe'S R~RES~A~ ~ ~PR~ ~E ~ L~ON OF
~ PR~R TO IN~. m
10. ~E CO~ ~ R~NSIB~ FOR ~I~NG ~ QU~ES SH~ ON ~ESE ~S
11. ~E ~TOR IS R~PONSIB~ FOR ~Y ~NNI~ ~ P~NG (INCLUDI~, B~
NOT UU~ TO: WARRING, ~NO, MULCHING, ~U~, ~C.) OF ~NO
U~IL ~E WORK ~ A~E~D IN TOT~ ~ ~E ~GIN~'S R~RESE~A~. ~T~
12. ~ B~NG DUO AT ~E NU~E~ ~URC[ ~ ~S IN ~ S~ BE ~LI~D FOR ~0 (2) ~EKS
UND~ A BI~ ~EM PRIOR TO
wo~) ~ .[ ~.~ .~ ~. ~ ~ ~ .~ w~ ~ o~ ~ ~ s~c,~.
SEE
R~KS
14. ~E CO~TOR S~ ~MP~LY G~E ~ P~ ~R~ FOR A PER~D OF ONE
(1) ~ BEGINNING AT ~E ~ OF TOT~ ~CE~CE. ~E ~TOR S~ P~M~Y
i e 9 i j g y ~ST MARION NDSCAPE
g' e ' g
= ~. = ~. ~. ,. ~ EAST MARION FIRE DISTRICT
150-034
I
D
PLANT MATERIALS LIST
CODED DRAWING NOTES GROUNDING NOTES
1. ALL ELECTRICAL WORK SHALL BE PERFORMED ~N ACCORDANCE WITH
THE NATIONAL ELECTRIC CODE AND ALL OTHER APPLICABLE LOCAL
~ PRO, DE ~2 COPP[~ GROUND RING (MIN. 1'-6" FROM OUTSlD~ ~E OF CODES
TOV/~R FOUNGAIION) BURIED AT MINIMUM 50' BB. OW GRADE.
~ CONNECT FENC£ TO GROUND RING. IYPIGAL 4 PLACES. ~'~ -- ~ 2. THE CONTRACTOR IS RESPONSIBLE FOR PROPERLY SEQUENCING
GROUNDING AND UNDERGROUND CONDUIT INSTALLATION SO AB TO
~ OcN.EcT T~ER ~E TO GROB.O ROC IN ,WED .IRO,~' FGR 3,~.~ ~ PR~ENT ~ ~OSS 0~ CGN~NUI~ IN THE GROUNDING SY~EM OR
C~/)WELD TO TOWER BASE P!J~TE OR AS PER MANUFACTO ER'S SPECl '(~)~~ DAMAGE TO THE CONDUIT.
~ CONNECT GATE TO GATE POST ~fP. FOR 2) ~ 4/0 ~ING
~T Y~S ~ CRIMPED ON EACH END WITH ^ C~ FOR IHE CN)WELD ~ 3. ALL GROUND CONNECTIONS BELOW GRADE SHALL BE EXOTHERMIC
PROCESS. LENGTH SHN_L NJ.OW FULL S~ING OF GATE. CONNECT GATE (CADWELD).
POSTS TO GROUND ROD. PROVIDE A WEEP HOLE ON ROITON CONDUCTOR
FOR DRN~AG~. 4. ALL GROUND CONNECTIONS ABOVE GRADE SHALL BE FORMED USING
~ ROND UTIUIY RACK SUPPORT POST TO EQUIPMENT GROUND RIRO 2-HOLE LUGS AND 1WO (2) HIGH PRESS CRIMPS.
WITH ~2 AW(;. LEGEND 5. ALL EXOTHERMIC MECHANICAL CONNECTIONS TO THE GROUND RODS
CAT ilO. 3012-1 OR EQUAL <~ 9. CONNECTIONS TO THE GROUND BARS SHALL NOT BE DOUBLED UP
GROUND BAR SUPPORTED.
~ - -- ~ ELECTRICAL SYMBOLS
, ABBREVIATIONS
AWG AMERICAN WIRE GAUGE
~ ~__~' L DWG DRAW,NC ® GROUND ROD
EMT ELECTRICAL METALLIC TUBING [~J DISCONNECT SWITCH
GROUND RD0 COPPERViELD IMC INTERMEDIATE METALLIC CONDUIT [] METER
/5/8"~x10'-0" LONG MGB MASTER GROUND BAR
I
CIRCUIT
BREAKER
PVC POLYVINYL CHLORIDE CONDUIT · CADWELD TYPE CONNECTION
EXTERIOR GROUNDING PLAN c~o
~ ~ ~ I ! COPPER-CLAD/~ ~'P TYPICAL
STEEL GROUND ROD ~/~'~~.~X~"'~-'~REPRESENTS DETAIL NUMBER
etL?jgY,..., EAST MARION FIRE DISTRICT 'I EXTERIOR
i FAST MARION
~ ' ~ ', ~ , ~ GROUNDING PLAN
e
150-034 sc~: I~""~: I ~":
^
UTILITY ROUTING PLAN
infi ni(.j
engineering
150-034
TELCO
PROPER'P( UNE (TYP)
ELEC. METER
AND SERVICE ENTRANCE
PANEL
· NEMA 3R
ELCO BOX 30'x30'x12"
WrTH 5/8' PLYWOOD
BACKBOARD
/
/
CALLED NORTH
1~iViLARGED
LITY ROUTING PLAN
SC. NE:
CNJ. ED NOR~
EAST MARION
9245 MAIN ROAD
FAST MARION, NY 11939
, EAST MARION FIRE DISTRICT
A 214
ELECTRICAL NOTES
1. ALL ELECIR~CAL WORK SHALL BE PERFORMED IN ACCORDANCE WITH
THE NATIONAL ELECTRIC CODE AND ALL OTHER APpUCABLE LOCAL
CODES.
2, THE CONTRACTOR IS RESPONSIBLE FOR PROPERLY SEQUENCING
GROUNDING AND UNDERGROUND CONOUIT INSTAU~TION AS TO
PREVENT ANY LOSS OF CONTINUI3Y IN THE GROUNDING SYSTEM OR
DAMAGE TO THE CONDUIT,
ALL ELECTRICAL iTEMS SHALL BE U.L. APPROVED OR USTED
CONDUCTORS SHALL BE INSTALLED IN SCHEDULE 40 PVC CONDUITS
(UNDERGROUND) AND IMC CONDUITS ABOVEOROUND.
CONTRACTOR SHALL OBTAIN ALL PERMITS, PAY ALL PERMIT FEES,
AND SCHEDULE ALL REQUIRED INSPECTIONS.
CONTRACTOR SHALL OBTAIN LOCAL POWER AND TELCO COMPANY
APPROVAL AND COORDINATE WiTH UTILITY COMPANIES SERVICE
ENTRANCE REQUIREMENTS.
CONTRACTOR SHALL PROVIDE ALL LABOR AND MATERIAL DESCRIBED
ON I~IIS DRAWING. AND ALL ITEMS INCIDENTAL TO COMPLETING AND
PRESENTING THIS PROJECT AS FULLY OPERATIONAL
PRO.DE 2' SCHEDULE 40 RVC UNDERGROUND CONDUIT wn~'( PULL
WIRE BEIWEEN ELECTRICAL UTILllY DEMARCATION POINT AND KWH
METER BASE.
CONDUIT ROLqlNGS ARE SCHEMATIC, CONTRACTOR SHALL INSTALL
CONDUITS SO THAT ACCESS TO EQUIPMENT IS NOT BLOCKED.
SERVICE TO EQUIPMENT CABINETS SHALL BE 120/240 VAS. 200
AMP. 1-PHASE.
CONIRACTOR SHALL DETERMINE REQUIRED NUMBER AND LOCATION OF
PULLBOXES PER UTILllY STANDARDS.
USE ADAPTER FROM PVC CONDUIT TO RIGID STEEL 90' BEND AND
USE REDUCER TO ENTER METER BOX WITH 2' DIA. CONDUIT.
AS REQUIRED
PAVEMENT,
GRAVEL OR LAWN AREA
RESTORATION TO MATCH
SLOPE AND THICKNESS OF
EXISTING
TELCO CONDUIT
¢' PVC SCH.
COMPACTED BACKFILL
(SAND OR NATIVE SOIL)
WARNING TAPE
ELEC1RICAL CONDUIT
4# RVC SCH. 40
UTILITY TRENCH DETAIL
!/~/o~ ~