HomeMy WebLinkAbout1000-15.-9-5PLANNING BOARD MEMBE~
BENNETT ORLOWSKI, JR.
Chairman
WILLIAM J. CREMERS
KENNETH L. EDWARDS
GEORGE RITCHIE LATHAM, JR.
RICHARD G. WARD
Town Hall, 53095 State Route 25
P.O. Box 1179
Southold, New York 11971-0959
Fax (631) 765-3136
Telephone (631) 765-1938
PLANNING BOARD OFFICE
TOWN OF SOUTHOLD
TO:
FROM:
Edward Forrester, Director, Code Enforcement
Robert G. Kassner, Site Plan Reviewer ~-~
RE:
Orient Point Substation
Private Road, Orient
SCTM# 1000-15-9-5
DATE: April 11, 2000
The Planning Board has reviewed the above project and has determined
that a site plan will not be required.
Any landscaping removed during constriction must be replaced.
PO BOX 483
SELDEN N.Y. 11784
Phone 516-696-0452
Fax 516~696-9090
Email expedites~aol.com
March 22, 2000
Mr. Bennett Orlowski
Chairman Planning Board
Town Hall
Main St
Southold NY 11971
Orient Point Substation
Ref: Dist 1000 Sec 15 Bi 9 Lot 5
Dear Mr. Chairman,
I will be acting as agent for my client KeySpan Energy, and we would like to
submit some preliminary plans for improvements to the Orient Point Substation.
I would like to know if permits will be required, and I have enclosed a
detailed explanation of the projects scope of work and purpose.
If you can there also are two roadways Macadam Dr which is owned by Lipa and
the other road is a private dirt road, owner unknown. Underground work on
these roads will be involved as indicated on the plans and we would like to
know if there would be requirements such as New York State Highway or Suffolk
County Dept of Public Works Road opening permits.
Any information you can provide to me as to the Towns requirements for this
particular project would be helpful, and I and Keyspan Energy await your reply
in confidence. Any questions please call me. Thank you
Very truly yours,
Steven Weintraub
Buitding & Zoning Permits
t' Variances · C of O's
Zoning Board of Appeals
even ~intraub Ex,p~diter, Inc
Residential Perrnit Servlce Commercial
P.O. Box 483 Office: (516) 696-0452
Selden NY 11784 Fax: (516) 696-9090
emaik bldgplan@gateway.net Pager: (516) 386-2108 :PJ,3~lilil~ ~ rd
PROJECT SCOPE DOCUMENT
TITLE: Orient Point Substation - Replace l.~kV Sx~ ~tchgear & Feeders
Problem Definition:
The steel frame supporting tt~e bali line-up 13 kV switchgea¢ unit has corroded in the salt fog
environme~ 0eyond the point of repair. Moisture intrusion and rust formatio~ is presently evident in
each of the two breakers and adjoining metering c0mpa~ments. Field inspection also shows a significant
amount of e~osion to the concrete pad under the switcbgeer unit.
The weak steel frames and foundation will result in improper racking of breakers, misalignmant of breaker
contacts and misoperation of breakers. Also, external bushings may become misaligned end disjointed,
causing electdcel and mechanical failures. Intrusion of moisture may cause catastrophic failure dudng
breaker operation. Operation of the equipment in this condltlon is unsafe and unacceptable
Recommendation:
Replace the switChgear to avoid failure. Replacement of the 13 kV swltchgear is required to supply two
dist~b~.~tJon feeders. The single 3,65 MVA, 23-13 kV transformer, Bank 1 at Orient Point su~:,station normally
supplies a total of 781 custnmers and 40 dMVA of dis~bution Ioacl in
the Bummer, Circuit 8WR-776 feeds Odent Point village to the west and circuit 8VVR-781 feeds the
submarine cable to the U.S. Department of Agriculture facilities on Plum Island (2.2 miles off-shore) to
the east, Circuit 8VVR-778 also provides contingency support to the eastern half of Southold circuit 8J..685
in Greenp0rt and East Marion.
The use of switchgear is preferable to constructing an overhead bus section and installing two free standing
13 kV, 1200^ vacuum circuit b~eakers because it provides 13 kV bus feed through capability during a
contingency anti includes an additional incoming breaker cubicle for Connecting %seco~nd transformer, in
case of future distribution load growth. ~ ~;v¢-o
Work Scope:
The new switchgear unit will be installed in the spare bay on the east side of Orient Point Substation with
an underground cable eatS.'. ~
The two existing 3-1/C 250 kcmil Cu PILC 15 kV feeder exits were installed with the original switchgee¢
unit and are sct'~eduled for replacement with 700' of new 3.21C 750 kcmit Cu EPR cable. The exit riser for
~ircuit 8WR-781 will be relocated one section east to Pole 24, to facilitate the transfer of distribution load
to the new switchgear unit,
The existing 13kV switchgear & out of se~ice capacitor bank enclosure will ~e removed as part of this
project.
[O0'd 6P916 9I :: 1 9,gN3-O3q /NYdS, S 80:80 (fl3l)OO, -'NV
.J
LINE
ISLAND
NOT'CE ~ COUN]'Y OF SUFFOLK 0
........... ER" tON S"L[ O~ I~ Real Property lox Service Agency
LASER FICHE FORM
Planning Board Site Plans and Amended Site Plans
SPFile Type:
Project Type: Site Plans
Status: No Site Plan Required
SCTM #: 1000 - 15.-9-5
Project Name: KeySpan Ener,qy Orient Pt. Substa.
Address: NYS Rt. 25, Orient Point
Hamlet: Orient
Applicant Name: KeySpan Ener,qy/LIPA
Owner Name: Lon,q Island Power Authority
Zone 1:
Approval Date: /'x///~
End SP Date:
OPTIONAL ADDITIONAL INFORMATION
A date indicates that we have received the related information
Zone 2: Zone 3:
Location: n/s/o NYS Rt. 25, Orient Pt.
SC Filin.q Date:
C and R's:
Home Assoc:
R and M A,qreement:
SCAN Date:
SCANNED
Records Management
s22o '
FENCE
X --X
X
LITE
~SST
-- X X × X
NORTH/SOUTH AXIS
FENCE
LITE
100.00'
X X--X X X
100.00
N22o36'og"w
~ N22O36'O6"W
29.84'
125.16
x
PREPAREB BY
KEYSPAN ENERGY
ELECTRICAL ENGR, BEPT,
SURVEY SECTION
ROY D, HUNT L,S, NO, 050220
SYSTEM SURVEYOR
NAR 9. 4 2000
oou~oid Town
Planning Board
/ I ORIENT POJNT~ SUBSTATION AND
J / EXIT F~-EDER TOPO
/ / SITUATED tN
r J ORIENT POINT, TO~WN OF SOUTHOLD
~ ~ SUFFOLK COUNTY, STATE OF NEW YORK
I~ ·-- KEYSPAN ENERGY
BY cgo ~PD MAY 1 1999 HY9905
S0-78
1 2 3 4 5 6
CONCRETE
STEP
SWITCHOEAR OUTLINE
SWlTCHGEAR FOUNDATION PLAN
MATERIAL REQ'D. FOR ONE FDN. '99A"
(INCLUDING 'l~/O STEPS)
REINFORCING SCHEDULE
MK QTY SIZE LENGTH REMARKS
4Al 28 #4- 19'-1" 17'-0"
]2'-1"
4A2 56 #4 17'-0" STR.
4A3 31 //4 16'-9" 12'-7"
2'-1"1 I 2'- 1"
4A4 35 //4 12'-7" STR.
6A5 4 #6 3'-9"'""~1~1~' 1~:6~ -,.4 ~
24 CUBIC YARDS OF CONCRETE
2.400 LIN. FT. OF #4 REINF. BAR
(M & S 175002)
20 LIN. FT. (5'-0" WIDE) 4x4-4/4
(M & S 175011)
15 LIN, FT. OF #6 REINF. BAR
(M & S 175005)
WWF
-~ SWGR. SUPP'T BASE
0
r-- I ~ 1/2" HEX NUT
WASHER
~4 (PAIRS) - 4Al 0 12+ TOP
~ I1 1/4" THK,
TOP . d 5/¢" CHAMFER /C ,~. ~ HOLD DOWN ~
B~OM'~ ?~ T/CQNC EL 130' ~1 I T
(PAIRS) ~ ~ ~/2" D,A.
~ ~ 4A2 ~l .o I
2" .~"
· ALL HARDWARE
2'-0" . ¢-o"L (TYP.)~ ~ SWITCBGEAR
~!~ ~-~: (~BRTH/SOUTH FACE) - (~p,~ -.~p,) MANUFACTURER
SECTION A - A D~AIL 'o'
MAR g,~ 2000
SoO~ho'ld Toe,~,n
NOTES' I~la~'~:lS]~ [Oo'~'~J
1. FOR NOTES SEE FOOTING PLAN.
REFERENCE DWGS.:
8WRSS- FY-05000
GRADtNG, FENCE
AND FOOTING PLAN
PLACE REMOVEABLE CONCRETE SWITCHGEAR
STEP LEVEL WITH OUTLINE
ADJACENT FOUNDATION '~A¢, v- .3/4" CHAMFER DETAIL 'o
/ ,-- WELL COMPACTED
~ SUB-SOIL
/ 4x4-4/4 WWF
SECTION B - B SECTION C - C
T/C
(PRELIMINN~( ANCHORAGE DETNL )
h1257200
Long Imlond Powmr Authodt~
ORIENT POINT SUBSTATleN
OR~r~ pOiNT; NEW YOR~
23--1-~ KV SUBSTAllON
~UN~llON 'DgA'
DErNL SHEEr
K pan Erie
'"~° BWRSS HC 04001 0
4 50
EDGE OF
DOLOMITE
(i'
1 2 3 4 5
ri' (I I/:*"
1 7 ~FDN' SWOR. &
~ CONTF~OL BLDg.
NEW 3" LAYER OF J/4 IN.
DOLOMITE WITHIN ENTIRE AREA OF
PARCEL //2
tM)
SECTION B-B ]YPiCAL AtT SOUTH
EDGE OF FOUNDATION UINLESS
NOTED OTHERWISE
6
7 8 9 10
7*'
~ iL
BREAKER ~
7',
FOUNBAllON SCHEIXJLE
UNDB{ W.O. 49O4,5
SYMBOL mY. DWG. ~.
~ 3 8WRSS-HC-04000
IW.O, 49D4,5
DESIGN 15 BASED ON
PREUMI~ ELECTRICAL
INFORI/AI1ON
U 1 F-166~16
N 2 F-168016
O 1 m F-16~16
HAR 2,~ 2000 ' ,
Southo)d Town ,
Plarmfrl~ Soar~J,
Leng laland Power ,Au'lhorfly
ORIENT POINT SUBffiATION
KIySpon Energy
A
B
C
D
A
'2
-I
20'-0"
POLE #1
CLASS
J
lO'-O"
3
.X
;x
5
7
E
F
21'-6"
ELEVATION A-A
ELEVATION
, MAR,~
~us ,~ SH~W~ A ~CT c,V~le;