HomeMy WebLinkAbout51599-Z s°uTyo�o Town of Southold
* * P.O. Box 1179
53095 Main Rd
Southold, New York 11971
CERTIFICATE OF OCCUPANCY
No: 46376 Date: 08/06/2025
THIS CERTIFIES that the building GENERATOR
Location of Property: _ 9502 N Bavview Rd Southold, NY 11971
Sec/Block/Lot: 88.-2-20
Conforms substantially to the Application for Building Permit heretofore,filed in this office dated: 12/06/2024
Pursuant to which Building Permit No. 51599 and dated: 01/31/2025
Was issued, and conforms to all of the requirements of the applicable provisions of the law.
The occupancy for which this certificate is issued is:
Accessory generator as applied for..Maintain clearances as required- minimum 3ft to
combustibles.
The certificate is issued to: 9502 N Bayview Rd LLC
Of the aforesaid building.
SUFFOLK COUNTY DEPARTMENT OF HEALTH APPROVAL:
ELECTRICAL CERTIFICATE: 51599 7/3/2025
PLUMBERS CERTIFICATION:
A thoriz Signature
of'Sao., <c TOWN OF SOUTHOLD
BUILDING DEPARTMENT
TOWN CLERK'S OFFICE
o(f�UUMf,M�
SOUTHOLD, NY
BUILDING PERMIT
(THIS PERMIT MUST BE KEPT ON THE PREMISES
WITH ONE SET OF APPROVED PLANS AND SPECIFICATIONS
UNTIL FULL COMPLETION OF THE WORK AUTHORIZED)
Permit#: 51599 Date: 01/31/2025
Permission is hereby granted to:
9502 N Bayview Rd LLC
9502 N Bayview Rd
Southold, NY 11971
To:
install generator as applied for.
Premises Located at:
9502 N Bayview Rd, Southold, NY 11971
SCTM#88.-2-20
Pursuant to application dated 12/06/2024 and approved by the Building Inspector.
To expire on 01/31/2027.
Contractors:
Required Inspections:
Fees:
GENERATOR $125.00
ELECTRIC -Residential $100.00
CO- SIDENTIAL $100.00
Total $325.00
4Bu ding Inspector
O:*pF 50!/r�ol
o
Town Hall Annex Telephone(631)765-1802
54375 Main Road
P.O.Box 1179 G • Q
Southold,NY 11971-0959 �Q
BUILDING.DEPARTMENT
TOWN OF SOUTHOLD
CERTIFICATE OF ELECTRICAL COMPLIANCE
SITE LOCATION
Issued To: William E Litton 11
Address: 9502 N.Bayview Rd City: Southold St: NY Zip: 11971
Building Permit#: 51599 Section: $$ Block: 2 Lot: 20
WAS EXAMINED AND FOUND TO BE IN COMPLIANCE WITH THE NATIONAL ELECTRIC CODE
Contractor: Electrician: G&S Electric License No: 578ME
SITE DETAILS -
Office Use Only
Indoor r1_6 Basement Cj Service Solar 1-
Outdoor (✓J 1st Floor (✓ Pool ❑ Spa F
Renovation 2nd Floor 171 Hot Tub 1J Generator (✓
Survey 1- Attic 1 GGarage Battery Storage (-
INVENTORY_
Service 1 ph Heat Duplec Recpt Ceiling Fixtures Bath Exhaust Fan
Service 3 ph (-i Hot Water GFCI Recpt Wall Fixtures Smoke Detectors
Main Panel A/C Condenser Single Recpt Recessed Fixtures CO Detectors
Sub Panel A/C Blower Range Recpt Ceiling Fan Combo Smoke/CO
Transfer Switch 150x2 UC Lights Dryer Recpt Emergency Strobe Heat Detectors
Disconnect Switches 4'LED Exit Fixtures
Other Equipment: 32kW Generac Generator w/ (2) 150A Transfer Switches
Notes: Generator
Inspector Signature: X- Date: July 3, 2025
Sean Devlin
Electrical Inspector
Sean.devlin(&-town.Southold.ny.us
9502N BayviewGenerator
1�
50U1y0
# # 'TOWN OF SOUTHOLD BUILDING DEPT.
coum, 631-765-1802
INSPECTION
[ . ] FOUNDATION 1 ST/ REBAR [ ] ROUGH PLBG.
[ ] FOUNDATION 2ND . [ ] INSULATION/CAULKING
[ ] FRAMING /STRAPPING [ aZFINAL
[ ] FIREPLACE & CHIMNEY ( ] FIRE SAFETY INSPECTION
[ ] FIRE RESISTANT CONSTRUCTION [ ] .FIRE RESISTANT PENETRATION
[ ] ELECTRICAL-(ROUGH) [ ] ELECTRICAL (FINAL)
[ ] CODE VIOLATION [ ] PRE C/O [ ].' RENTAL
REMARKS: e c cee-4 c, a v1 ems.
cam 6s
DATE INSPECTOR
hO��OE SOUI 51
TOWN OF. S O UTHOLD,BUILDING DEPT.
631-765-1802
I-NSPECTION
[ ] FOUNDATION 1 ST/ REBAR [ ] ROUGH PLBG.
[ ] FOUNDATION 2ND [ .] INSULATION/CAULKING
[ ] FRAMING /STRAPPING [ ] .FINAL
[ ] FIREPLACE & CHIMNEY [ -] FIRE SAFETY INSPECTION
[ ] FIRE RESISTANT CONSTRUCTION : [ ] FIRE RESISTANT PENETRATION
[ ] ELECTRICAL (ROUGH) ELECTRICAL (FINAL)
[ -] CODE VIOLATION [ ] PRE C/O [ ] RENTAL
REMARKS:
DATE /_ 142 INSPECTOR
SOUIyO4WNI S 1 `��02 N' V r�
# #
OF OUTHOLD BUILDING D T
cou 631-765-1802
INSPECTION
[ ] FOUNDATION 1ST/ REBAR [ ] ROUGH PLBG.
[ ] FOUNDATION 2ND [ ] INSULATION/CAULKING
[ ] FRAMING /STRAPPING [ ] FINAL
[ ] FIREPLACE & CHIMNEY [ ] FIRE SAFETY INSPECTION
[ ] FIRE RESISTANT CONSTRUCTION [ ] FIRE RESISTANT PENETRATION
[ ] ELECTRICAL (ROUGH) ELECTRICAL (FINAL)
[ ] CODE VIOLATION ] PRE C/O [ ] RENTAL
REMARKS: 6,&A�r ��Af
;ate4g-ev- 6f riflual" ac-!�Q je
r _
, 1
t r�
08, -71Z 312�c-
DATE 3 2 INSPECTOR
?IELD INSPECTION REPORT DATE COMMENTS / f�
v, •c
FOUNDATION (IST) --- --- -- ------ - - --- --
------------------------------------- -
FOUNDATION (2ND) _— Gor)
z
0
ROUGH FRAMING&
PLUMBING a
INSULATION PER N. Y. --
- — a
STATE ENERGY CODE —
YVI (Wv-nrL --
FINAL - --
ADDITIONAL COMMENTS
-- - -a.5 Eta. ���� �c --------------- --
rn
-o
y z
t�
-o
�o�SUFFoc �oGy TOWN OF SOUTHOLD—BUILDING DEPARTMENT
Town Hall Annex 54375 Main Road P. 0. Box 1179 Southold,NY 11971-0959
Telephone (631)765-1802 Fax(631) 765-9502 https://www.southoldtovmny.go_v
Date Received
APPLICATION FOR BUILDING PERMIT
C
For Office Use Only i i t IS
�� pE - :r
PERMIT NO. Building Inspector: C 6 2024
AppUcatigns and forms must be filled out;in their,entirety.Incomplete t ,q .C' L
applications will not be accepted ';Where the Applicant is not the
Owner's Authori anon form(Page 2)shall be'completed.
Date:
OWNERS)OF PROPERTY
Name:Alan Weiss SCTM#1000-88-02-20
Project Address:9502 N Bay_vieW Southold NY 11971�
Phone#:516-512-2016 Ema1l q njweiss@optonline.net
Mailing M Address:9502 N 13 yVy W _Southold NY 11971
CONTACT PERSON k 4;
Name:Jesse Gaffga__q_� _
Mailing Address:3350 Grand Ave Mattituck NY 11952
Ph one#:631-375-2737 _ Email:Jgaffga@jtechSs.Com
DESIGN'PROFESSIONAL' INFORMATION X _m
Name:
Mailing Address:
Phone#: Email:
CONTRACTOR INFORMATION:
P`;.
Name:J-Tech Surface Solutions
Mailing Address:3350 Grand Ave Mattituck NY 11952 -
Phone#:631-298-4238 Email:jgaffga@jtechSS.com_M
DESCRIPTION OF PROPOSED"CONSTRUCTION
El New Structure ❑Addition ❑Alteration ❑Repair ❑Demolition Estimated Cost of Project:
DOtherinstall 32KW stand by generator $15000.0
[Will the lot be re-graded? ❑Yes BNo Will excess fill be removed from premises? ❑Yes BNo
1
;. PROPERTY,INFORMATION
Existing use of propeina n.gle_fa_mih/__ Intended use of property_S�n.g�e
Zone or use district in which premises is situated: Are there any covenants and restrictions with respect to
this property? ❑Yes ®No IF YES, PROVIDE A COPY.
8`.Check Box After Reading The owner/contractor/desigmprofessional is;responsible for all drainage and'storm'water issues as provided by '
Chapter 236 of the Town Code.`APPLICATION IS'HEREBY MADE to the Building Department for the issuance of 6 Building'Permit pursuant to the Building Zone
Ordinance`of the Town ofsouthold,Suffolk,County,New'York andiother applicable laws,Ordinances'-di Regulations,for the construction of,buiidings,
additions,alterations oil or,removal or.demolition as herein described:Theapplicant agrees to comply with all applicable laws;ordinances;building code,.. ,
housing,code and regulations and to admit authorized inspettors;on premises and In building(s),,for necessary inspections.False''statements,made herein are
punishableasa Class A misdemeanor pursuant to Section210.45 of the New York State Penal Law. '
Application Submitted By(print name):Jesse Gaffga ®Authorized Agent ❑Owner
Signature of Applicant: Date: 10r2,/24
STATE OF NEW YORK)
SS:
COUNTY OF )
Jesse Gaffga being duly sworn, deposes and says that(s)he is the applicant
(Name of individual signing contract)above named,
(S)he is theContractor
(Contractor,Agent,Corporate Officer,etc.)
of said owner or owners,and is duly authorized to perform or have performed the said work and to make and file this
application;that all statements contained in this application are true to the best of his/her knowledge and belief;and
that the work will be performed in the manner set forth in the application file therewith.
Sworn before me this� '
day of 0 ( ,20a
o ry Public
BETSYA. PERKINS
ary Public,State of New York
PROPERTY OWNER AUTHORIZATION No.01 PE6130636
Qualified in Suffolk Cou t
(Where the applicant is not the owner)Commission Expires July 18NaZS—
Alan Weiss residing at 9502 N Bayview
Southold, NY ,
do hereby authorize Jesse Gaffga to apply on
my behalf to the Town of Southold Building Department for approval as described herein.
Owner's Signature Date
A#7(11 095
Print Owner's Name
2
BUILDING DEPARTMENT- Electrical Inspector
TOWN OF SOUTHOLD
H $ Town Hall Annex- 54375'Main Road - PO Box 1179
o • Southold, New York 11971-0959
'ffj a0�' Telephone (631) 765-1802 - FAX (631) 765-9502
iamesh(cDsoutholdtownny.gov — seand(cDsoutholdtownny.gov
APPLICATION FOR ELECTRICAL INSPECTION
ELECTRICIAN INFORMATION (All Information Required) Date: 11/24/2024
Company Name: G&S Electrical Contractor
Electrician's Name: Rob Guarriello
License No.: 31568-ME Elec. email:
Elec. Phone No: 631-375-2737 ❑1 request an email copy of Certificate of Compliance
Elec. Address.: 250 Budds Pond rd Southold NY 11971
JOB SITE INFORMATION (All Information Required)
Name: Alan Weiss
Address: 9502 N Bayview NY 11971
Cross Street:
Phone No.: 516-512-2016
BIdg.Permit#: 5 email:alanjweiss@optonline.net
Tax Map District: 1000 Section:88 Block: 02 Lot:20
BRIEF DESCRIPTION OF WORK, INCLUDE SQUARE FOOTAGE (Please Print Clearly):
Install 32KW Stand By Generator
Square Footage:
Circle All That Apply:
Is job ready for inspection?: ❑ YES ❑� NO 0 Rough In ElFinal
Do you need a Temp Certificate?: ❑ YES ❑� NO Issued On
Temp Information: (All information required)
Service Size❑1 Ph❑3 Ph Size: A # Meters Old Meter#
❑New Service❑Fire Reconnect❑Flood Reconnect❑Service Reconnect❑Underground❑Overhead
# Underground Laterals 1 FJ2 H Frame , Pole Work done on Service? Y FIN
Additional Information:
PAYMENT DUE WITH APPLICATION
r
rot/( BUILDING DEPARTMENT- Electrical Inspector
Hall Annex
OF SOUTHOLD
Town nnex- 54375 Main Road - PO Box 1179
o Southold, New York 11971-0959
p� Telephone (631) 765-1802 - FAX (631) 765-9502 -,
jamesh southoldtownnyaov - seand(c-D south oldtownny.ctov
APPLICATION FOR ELECTRICAL INSPECTION
ELECTRICIAN INFORMATION (Ali information Required) Date: 11/24/2024
Company Name: G&S Electrical Contractor
Electrician's Name: Rob Guarriello
License No.: 31568-ME Elec. email:
Elec. Phone No: 631-375-2737 ❑1 request an email copy of Certificate of Compliance
Elec. Address.: 250 Budds Pond rd Southold NY 11971
JOB SITE INFORMATION (All Information Required)
Name: Alan Weiss
Address: 9502 N Bayview NY 11971
Cross Street:
Phone No.: 516-512-2016
Bldg.Permit#: .5 1-5 q email:alanjweiss@optonline.net
Tax Map District: 1000 Section:88 Block: 02 Lot:20
BRIEF DESCRIPTION OF WORK, INCLUDE SQUARE FOOTAGE (Please Print Clearly):
Install 32KW Stand By Generator
Square Footage:
Circle All That Apply:
Is job ready for inspection?: ❑ YES ❑✓ NO ❑Rough In ❑ Final
Do you need a Temp Certificate?: ❑ YES 0 NO Issued On
Temp Information' (All information required)
Service Size❑1 Ph❑3 Ph Size: A # Meters Old Meter#
❑New Service❑Fire Reconnect❑Flood Reconnect❑Service Reconnect❑Underground❑Overhead
# Underground Laterals M 1 2 M H Frame D Pole Work done on Service? Y N
Additional Information:
PAYMENT DUE WITH APPLICATION
PERMIT# Address:
Switches
Outlets
GFI's
Surface
Sconces
H H's
UC Lts Fridge HW POOL
Panel
Fans Mini Fr. W/D Pump
Exhaust Oven Sump Heater
Trnsfmr
Smokes DW Generator Salt Gen.
Carbon Micro GrbDis Water Bond
Lights
Heat Pucks ERV
HOT TUB/SPA
Inst Hot DeHum Transfer Disc
Combo Cooktop Minisplit Blower
AC AH Hood Blower
Service Amps Have Used
Sub Amps Have Used (Z
Comments
NORrF7 SURVEY OF
8AYV1 LOT 4
�w Etiy RO�4DMAP OF
PELLICANO WOODS
FILE N.. 10059 FILED OCTOBER e.1997
p 9 Ai SITUATE
o A BAYVIEW
TOWN OF SOUTHOLD
Cc)� SUFFOLK COUNTY, NEW YORK
S.C. TAX N0. 1000-88-02-20
SCALE 1"=40'
AUGUST
{g2py�201 B
ocroe(n iwm 2 0 ciN suft/E1rLOM°N
,/ AIAUST 10.20M AOD NO(E�YEOL COYFA p FRONE YAfro
T� AUGUST 70.��UPOAIE SIIRJLY
/ AREA 2AQ W,1t.
{
SM N MrALM MAD L C
Dion WoM
/ q /
AM VM
UVMTIW OF
RDMS NATIONAL TME DMUU NCE mtaurc nAowlum
`/� �
'So.
s saa,. O O
S0.f
Sy 30• • �i�.
0-7
q�r9.p 0
B
MY=SMEY 11E YrAM MEY1S
CORKER❑A CNN ,�� �'• Nf°
SEP11C TANK �• 298' ///� ^M
COVEN ^1
�NOI POOL °1' u• /
LEACHING POOL �. �• I pAM, ' /
COVEN 2LEACHI
1m Nub '1Co. COVER"s P00L �• s9• G %•>I
e P J ^
urwmcLft�Auaew a AOta110M � �� O
as�mA
`k ro 11m tiA,tY O•YOL91l•1 or O
Osys s Y rw M- -UV
ro to A aIn 1mLc LaPr. q
wis P.. 0
ora�r° "ra rco°of mi°K M'�'wY �"iv40J. 9
1roiKNw.r -A a Nam nrauvm,as Q o
�N0/09 E
Mpny1p
L5°mGe�' r No7 eLtoNN ASC NOr � �'R ��
��x Aaannwce wLx M LNIEEY o OQq�
f011 f�II1gVpC.f�Bptl 1S61EIQ®
`�NF11tlK lW['�LNO f0
IV r e
toi'�vr ®.La
KYS.U.N.e04P S S0
W
Nathan Taft Corwin 111
V�
Land Surveyor LS T. J.Yd—J
44p% ftD S �r
Omwftr Slmdq J. ALA gpT'4'Ypp��
S �`,,•��LY/��ft,,S��OA �q ,. ryN /�
JSPN A h.M L.S. a' 'E rQ.e 1'oR z$�ZJ , GJ a$Ir
Heft 9u r/i+-SLGdYSIns-st.M-- C-b f.Lpc.K
PHONE(e31)727-2090 Eft.(6-31)727-1727
OFFM LDIM7ED AT LL1681G ALNII✓F.4 L@re rotWn.�V•'
Jnmftpl email,1-Y 119/7 J—p t N.Ye k 11947 0,
e
APPROVED AS NOTED
DA �3 &P# 5-
FEE Z5W BY
NOTIFY BUILDING DEPARTMENT AT
631 765•1802 8AM TO PM FOR THE OCCUPANCY OR
FOLLOWING INSPECTIONS: USE IS UNLAWFUL
1. FOUNDATION-TWO REOUIRED
FOR POURED CONCRETE WITHOUT CERTIFICAT'
2. ROUGH-FRAMING&PLUINIBING
3. INSULATION OF OCCUPANCY
4. FINAL-CONSTRUCTION MUST
BE COMPLETE FOR C.O.
ALL CONSTRUCTION SHALL MEET THE
REQUIREMENTS OFTHE CODES OF NEW
YORK STATE. NOT RESPONSIBLE FOR
DESIGN OR CONSTRUCTON ERRORS
COMPLY WITH ALL CODES OF
NEW YORK STATE&TOWN CODES
AS REQUIRED AND CO ITIONS OF ELECTRICAL
SOUTHOLDT NZBA INSPECTION REQUIRED
--.---.._.._...SOUTHOLD OWN PLANNfNG BOARD
SOUTHO TOWN TRUSTEES
VS.D
SO LD HPC
Sc
•
GENERAC® •
0
XG Protector R Series
Protector® Series Standby Generators _
Liquid-Cooled Gaseous Engine
STANDARD FEATURES STANDBY POWER RATING
Model XG03245 2 kW,60 Hz Emergency Standby Power Generator
• Power Zone®410 Controller,NFPA 110 System Control Capable odeI XG04 -40 W,60 Hz Emergency Standby Power Generator
• Padlockable Control Panel Cover with UV Protection Model XG04845-48 kW,60 Hz Emergency Standby Power Generator
• Cellular Connectivity for Mobile Link and Fleet,
• Quiet Operation
• Corrosion Resistant Aluminum Enclosure,Electro-Galvanized Baseframe '� _ —-
Components,and Stainless Steel Exhaust Systems
• 5 Year/2,000 Hour Limited Warranty
• High Motor-Starting&Surge CapacityF .,
• ±1%Digital Voltage Regulation
• <5%Total Harmonic Distortion Power Quality ( MSFM
• Fuel Efficiency zt
• Controller-Selectable Fuel Type-Propane or Natural Gas )r {
• 1-Phase or Configurable 3-Phase Voltage Output Models
• Single-Side Regular Maintenance Access \�
• EPA Emissions Certified GENE• CA&MA Emissions Compliant 40&48 kW Models {� tea•
• UL 2200 Listed ACt "
• 145 mph(233 km/h)Wind Speed Ratin92
1-Cellular service for the US,Canada,and other supported countries using the "' Q
Generac Generator Connectivity Accessory,Cellular(GGCAC)
2-Requires correctly prepared concrete pad and anchoring system.
OPTIONAL FIELD-INSTALLABLE FEATURES
Available as field-installable kits Product may vary from above image depending on model.
• 3-Phase Voltage Configuration Cartridge(VCC)
• 3-Phase Circuit Breakers(1-Phase Generators Include the Circuit Breaker)
• Generator Ready-Status Indicator
• Push-Button Emergency Stop ♦ 1
• NFPA System Control&Remote Annunciation c FjV USQUI�Mobile Link.
• Cold Weather
her Operation Heaters
• Level 2 Sound Reduction 0
• Extreme High Wind Resistance2
• Provisions for Rooftop and Elevated Mounting
• Baseframe Block-off
• Engine Fluid Containment EPA Emissions Certified
• Seismic Anchoring CA&MA Emissions Compliant 40&48 kW Models
FEATURES
O INNOVATIVE DESIGN & PROTOTYPE TESTING are key components of O SOLID-STATE,FREQUENCY COMPENSATED VOLTAGE REGULATION.This
GENERAC'S success in"IMPROVING POWER BY DESIGN."But it doesn't stop state-of-the-art power maximizing regulation system is standard on all Generac
there.Total commitment to component testing,reliability testing,environmental models. It provides optimized FAST RESPONSE to changing load conditions
testing, destruction and life.testing, plus testing to applicable GSA, NEMA, and MAXIMUM MOTOR STARTING CAPABILITY by electronically torque-
EGSA,and other standards,allows you to choose GENERAC POWER SYSTEMS matching the surge loads to the engine.Digital voltage regulation at±1%.
with the confidence that these systems will provide superior performance.
O SINGLE SOURCE SERVICE RESPONSE from Generac's extensive service
O MOBILE LINK®CONNECTIVITY:Standard cellular connectivity included with network provides parts and service know-how for the entire unit, from the
every XG generator, Mobile Link allows users to monitor generator status from engine to the smallest electronic component.
anywhere in the world using a smartphone, tablet, or PC. Easily access
information such as the current operating status and maintenance alerts.Uses. O GENERAC TRANSFER SWITCHES: Long life and reliability are synonymous
can connect an account to an authorized service dealer for fast,friendly, and with GENERAC POWER SYSTEMS. One reason for this confidence is the
proactive service. With Mobile Link, users are taken care of before the next GENERAC product line is offered with its own transfer systems and controls for
power outage. total system compatibility.
O TRUE POWERTM ELECTRICAL TECHNOLOGY:Superior harmonics and sine
wave form produce less than 5% Total Harmonic Distortion for utility quality
power.This allows confident operation of sensitive electronic equipment and
micro-chip based appliances,such as variable speed HVAC systems.
1
GENERAC®
GENERATOR SPECIFICATIONS
GENERATOR OUTPUT
PROPANE
XG03245 XG04045 XG04845
Voltage
Power(kW) Current(A) Power(kW) Current(A) Power(kW) Current(A)
120/240 V 1—Phase 32 133 40 167 48 200
208/120 V 3—Phase 32 111 40 139 48 167
240/120 V 3—Phase 32 96 40 120 48 144
480/277 V 3—Phase 32 48 40 60 48 72
NAT L GAS
XG03245 XG04045 XG04845
Voltage
Power(kW) Current(A) Power(kW) Current(A) Power(kW) Current(A)
120/240 V1-Phase 32 133 40 167 48 200
208/120 V 3-Phase 32 111 40 139 48 167
240/120 V 3-Phase 32 1 96 40 120 48 144
480/277 V 3-Phase 32 48 40 60 48 72
Emergency Standby Power(ESP)Rating:Standby ratings apply to installations served by a reliable utility source.The ESP rating is applicable to varying loads for the
duration of a power outage.The average power output over 24 hours shall not exceed 70%of the ESP rating.
ALTERNATOR SYSTEM
XG03245 XG04045 XG04845
1-Phase 120/240 V Only 120/240 V Only 120/240 V Only
Voltage Output 208/120 V;Configurable for 240/ 208/120 V;Configurable for 240/120 208/120 V;Configurable for 240/
3-Phase 120 or 480/277 V with Optional VCC or 480/277 V with Optional VCC 120 or 480/277 V with Optional VCC
-Phase Circuit Breaker(CB) 150 200 200
Size(A) 3-Phase Not Included;Optional,Field- Not Included;Optional,Field- Not Included;Optional,Field-
Installable Kit Installable Kit Installable Kit
Alternator Type Synchronous
Rotor Insulation Class F
Stator Insulation Class H
Telephone Interference Factor(TIF) <50
Bearings', Sealed Ball
Coupling Flexible Disc
Excitation System Direct
Total Harmonic Distortion <5%
VOLTAGE REGULATION
Type Digital
Sensing All Phases
Regulation ±1
GENERAC®
GENERATOR SPECIFICATIONS
SURGE CAPACITY
Surge Amps at<0.4 XG03245 XG04045 XG04845
Power Factor 15%Voltage Dip(A) 30%Voltage Dip(A) 15%Voltage Dip(A) 30%Voltage Dip(A) 15%Voltage Dip(A) 30°%Voltage Dip(A)
1 00/240 V 1-Phas 107 204 117 267 — — •
208/120 V 3-Phase 111 167 139 215 —
240/120 V 3-Phase 91 140 114 150 — —
480/277 V 3-Phase 55 87 63 102 — —
ENGINE SYSTEM lie,
X 03245 XG04045 XG04845
Make Generac
Model 4.5 L,Inline 4-Cylinder,Naturally Aspirated
Compression Ratio 9.9:1
Lifter Type Hydraulic
Oil Pump Type Gear
Oil Filter Type Full Flow Spin-on Cartridge
Crackcase Capacity(qt(L)) 12(11)
Temperature Derate 1.7%per 10°F above 77°F(1.5%per 5°C above 25°C)
Altitude Derate 3%per 1,000 ft above 600 ft(1%per 100 m above 183 m)
Exercise Speed(rpm) 1,200
Operating Speed(rpm) 1,800
Exhaust Flow at Rated Output(CFM(m3/min)) 187(8.3) 235(6.7) 280(7.9)
GOVERNOR
Type Electronic
Frequency Regulation Isochronous
COOLING SYSTEM
XG03245 XG04045 XG04845
Coolant 50/50(50%Ethylene Glycol)
Coolant System Capacity(US gal(L)) 2.9(11)
Water Pump Type Belt Driven
Fan Type Belt Driven Electric
Fan Quantity 1 3
Maximum Ambient Air Temperature(°F(°C)) 122(50)
GENERAC®
0 GENERATOR SPECIFICATIONS
FUEL SYSTEM
Fuel Types Liquid Propane(LP)Vapor or Natural Gas(NG)
Fuel Type Configuration Controller-Selected Only
LP Vapor Pressure(in H2O(kPa)) 7-14(1.74-3.48)
NG Pressure(in H2O(kPa)) 3.5-14(0.87-3.48)
' Fuel Shutoff Solenoid Standard,Dual
FUEL CONSUMPTION
LIQUID PROPANE
XGO 245 XG04045 XG04845
Rated Load
(US gph) (L/h) (US gph) (L/h) (US gph) (L/h)
25% 2.2 8.3 2.6 10.0 2.9 10.9
50% 3.4 12.9 3.8 14.5 4.2 15.7
75% 4.2 15.8 4.7 17.7 5.3 20.0
100% 4.9 18.5 5.7 1 21.7 6.6 25.0
Propane-91,452 BTU/US gal(25.5 MJ/L);36 ft3/US gal(0.27 m3/L);2,516 BTU/ft3(93.7 MJ/m3);4.24 lb/US gal(0.508 kg/L)
NATURAL GAS
X 03245 XG04045 XG04845
Rated Load
(CFH) (m3/h) (CFH) (m3/h) (CFH) (m3/h)
25% 169 4.8 184 5.2 201 5.7
50% 240 6.8 289 8.2 336 9.5
75% 335 9.5 392 11.1 447 12.7
100% 406 11.5 494 14.0 604 1 17.1
Natural Gas-1,036 BTU/ft'(37.3 MJ/m3)
See Emissions Data Sheets for maximum fuel flow for EPA and SCAQMD permitting purposes.
ELECTRICAL SYSTEM
XG03245 XG04045 XG04845
System Voltage(V) 12
Charge Alternator(A) 37 145
Battery Charger(A) 5
Recommended Battery(not included) Flooded Lead Acid,Group 27,600 CCA Minimum
Maximum Allowable Battery Flooded Lead Acid,Group 31,750 CCA Minimum
ENCLOSURE
XG03245 XG04045 XG04845
Sound Level at Exercise Speed(dB(A)@ 23 ft(7m)) 60 60 -
Sound Level at Operating Speed&No Load(dB(A)@ 23 ft(7m)) 67 67 -
Wind Speed Rating(mph(km/h))4 145(233)
Color Metro Gray
4-ASCE 7-16 exposure B wind speed rating