HomeMy WebLinkAbout51069-Z �OF SOUryo`o Town of Southold
* * P.O. Box 1179
�0 53095 Main Rd
CDUNT1 Southold, New York 11971
CERTIFICATE OF OCCUPANCY
No: 45701 Date: 10/26/2024
THIS CERTIFIES that the building EXHAUST HOOD AND/OR FIRE SUPRESSION SYSTEM
Location of Property: 1205 Route 25 Greenport, NY 11944
Sec/Block/Lot: 35.-1-25
Conforms substantially to the Application for Building Permit heretofore, filed in this office dated: 07/31/2024
Pursuant to which Building Permit No. 51069 and dated: 08/15/2024
Was issued, and conforms to all of the requirements of the applicable provisions of the law.
The occupancy for which this certificate is issued is:
alterations to existing Ansul system as applied for (Community Center).
The certificate is issued to: Peconic Landing(a�Southold
Of the aforesaid building.
SUFFOLK COUNTY DEPARTMENT OF HEALTH APPROVAL:
ELECTRICAL CERTIFICATE:
PLUMBERS CERTIFICATION:
J
rAuoUizeSignature
TOWN OF SOUTHOLD
�o�°SUFFock�° BUILDING DEPARTMENT
'
ca
H TOWN CLERK'S OFFICE
SOUTHOLD, NY
�
BUILDING PERMIT
(THIS PERMIT MUST BE KEPT ON THE PREMISES
WITH ONE SET OF APPROVED PLANS AND SPECIFICATIONS
UNTIL FULL COMPLETION OF THE WORK AUTHORIZED)
Permit#: 51069 Date: 8/15/2024
Permission is hereby granted to:
Peconic Landing @Southold
1500 Brecknock Rd
Greenport, NY 11944
To: Cook line appliance order change, No piping changes, Same existing tanks and control
head. (changing Nozzles only) Gex +tI—)
At premises located at:
1205 Route 25, Greenport
SCTM # 473889
Sec/Block/Lot# 35.-1-25
Pursuant to application dated 7/31/2024 and approved by the Building Inspector.
To expire on 2/15/2026.
Fees:
FIRE SUPP. SYSTEM/HOOD/EXHAUST SYSTEM $300.00
CO-COMMERCIAL $100.00
Total: $400.00
Building Inspector
0FS0UTyO� ���� c-- ` (/Jr`�'�
# T WN OF SOUTHOLD BUILDING DEPT.
cou 631-765-1802
INSPECTION
[ ] FOUNDATION 1ST/ REBAR [ ] ROUGH PLBG.
[ ] FOUNDATION 2ND [ ] INSULATION/CAULKING
[ ] FRAMING/STRAPPING Z14.FINAL e® s S
[ ] FIREPLACE & CHIMNEY [ ] FIRE SAFETY INSP CTION
[ ] FIRE RESISTANT CONSTRUCTION [ ] FIRE RESISTANT PENETRATION
[ ] ELECTRICAL (ROUGH) [ ] ELECTRICAL (FINAL)
[ ] CODE VIOLATION [ ] PRE C/O [ ] RENTAL
REMARKS: )91&� � Dvvc
m �gx&,e el
k A) pi �:3W P302AS ic%eeel�7
DATE 8 f 2 . INSPECTOR /
o�oSUFFat�COG TOWN OF SOUTHOLD—FIRE MARSHAL
o� X, Town Hall Annex 54375 Main Road P. O. Box 1179 Southold,NY 11971-0959
oy • o� Telephone (631) 765-1802 Fax (631) 765-9502 htt-os://www.southoldtowM.gov
FIRE PROTECTION SYSTEM PERMIT Date Received
APPILICATION
For Office Use Only ;1 ED)
PERMIT NO. Building Inspector: D
Applications.and forms must be filled out.in their entirety.Incomplete_ . J JUL 3 1
applications will not be ac -eeptM WORK IS NOT TO BE STARTED.prior' 2024
to,tfie approval of plans and'issuance'of a,permit., ;.' ' ;• •` „,.;.'.
Has a building permit been obtained for this project? ❑Yes ' YNo
If yes,building permit# �I+�O01•
Date: -7.- 10 -;Z aq q
PROJECT INORMATION: ,
Project Address: - SCTM# 1000- 33- 01 -;2 S
� BR_e.c1C.!��EK__.._!?�?_._.-. .._._.._._-.._.__...._.-_... .._m_... ..-__.__._..�._,_�._...__._._. . __.-....._.... -.�.r.....---__._.
City:. .... G. l lq
Zip:
'CONTACT PERSON INFORMATION:
Name:
Mailing Address: o t-1-02e_....w.._ .N�..._ _ 1..� 7.c_�.w_.._.•_......_.._ ___.. _._..----...- ___....
Phone#:...... 3`- 31.6_-ti�9a Email:
_.._ ... .. .._._._... ...._ . - . ...._...�N-i�c:�sa�h4 F/./_tC.•�nl�:.�..Lidr+A.,+L_�_t.�..r1 ......
Preferred contact method(select one): Mlhone ❑Email
CONTRACTORINFORMATION:
Name: Contractor License#: t t 3 . .. .......... ......... . .. ..
Mailing Address:
. . `�.. .. c�N.0.',LL . .A4z. ...... QA`/ 40 xq. . . . j��r�.6 .
Phone#: - Email:
At4t�r�s'�?-yF.Rz�''^).c: C�°...C.;I�A:_L_-
CO,!PE OF WORK:SC
Occupancy Description: ❑Assembly NrBusiness ❑Education ❑Factory/Industrial ❑Institutional ❑Mercantile
❑Residential ❑ Storage
Description of Work:
p - .-1LJ-A(?- . -. o zzLe s ��fL C:o o K,'n1(i. .. L%n e,d P k-l- Csi Er
❑ New System RlExisting System Modification
Sprinkler/Standpipe%,Water:Supply, Fire Alarm/CO Detection Systems .:. Other Fire Protection Systems
Check all that apply) (Check all-that apply) (Check all that apply) .
❑NFPA 13,13D or 13R System ❑Manual ❑Automatic ❑ Smoke Control
❑Standpipe ❑ Fire Pump ❑Protected Premises (local) N(Wet or Dry Chemical/Clean
❑Supervising station Agent
Number of sprinkler heads: ❑Central Station ❑Kitchen hood/exhaust ❑ Other
Floor Area(sq.ft.): _, _. _._ ._._..._._.-....__..._.._...._..-...
1
Check'Box After Reading:,,Y;the,Undersigned,understand that the issuance`of a permit for;tlie,type which is herein applied for is,tiased an;
the agreement to.conforin to all re'gul'ations and regairements.I further understand that non-compliance;of said requirements;;by myself,or any offceror
employee 'f the firm or individual listed as the applicant on this form,shall be cause ford evocation of said' e'rmit.Upon revocation of said permit'the
applicant or any employee of the applicant shall be prohibited to conduct such work for which this permit was issued.The reissuance of a permit shall be
based upon review of the circumstances leading to the revocation.,Any.false statement(s)made herein are punishable as.a Class A misdemeanor pursuant
to Section 210.45 of.the Penal.Law
Application Submitted By(print name): Qp,,L EAuthorized Agent ❑Owner
Company(if applicable): „►a� s�t ._____ ..le-e----
Applicant Signature: Date:
FIRE PROTECTION SYSTEM PERMIT APPLICATION SUBMITAL INSTRUCTIONS
Submit application only after reviewing the requirements for the specific permit for which you are applying(click the applicable link
below).
• FIRE ALARM/CARBON MONOXIDE DETECTION SYSTEM SUBMITTAL GUIDELINES
• FIRE SPRINKLER SYSTEM SUBMITTAL GUIDELINES
• FIXED FIRE SUPPRESSION HOOD&EXHAUST SYSTEMS SUBMITTAL GUIDELINES
FEES
A$250 permit fee is required for a non-residential permit.A$50 Certificate of Occupancy fee is required if the project is not part of
an existing open building permit. All checks should be made payable to the Town of Southold.
Permits,once issued,shall at all times be kept on the premises designated thereon with a copy of approved drawings and all related
documentation required to obtain said permit,Installations subject to final testing,inspection and approval.Arrangements for
testing/inspection shall be made by contacting the Town of Southold Building Department(631)765-1802.
FOR OFFICE USE-pNLY
Amount Paid: '.: Check No.: �FM:
Permit No.,:,, Date: Exp.Date:. . .
2
SUFFOLK COUNTY
DEPARTMENT OF RRE9 RESCUE AND EMERGENCY SERVOCES
PORTABLE FIRE EXTINGUISHER AND AUTC)mmIC FIRE EXTINGUISHING SYSTEMS LICENSING
BOARD
CERTIFICATE ®F REGISTRATION
REGISTRATION #: 113 _
EFFECTIVE DATE: 1/19/2023 b EXPIRATION DATE: 1/31/2025
ISSUED TO: NAME: Suffolk Fire Inc. dba Anderson Fire Equipment
ADDRESS: 9 O'Neil Avenue
Bay Shore; NY 11706 _
ENDORSEMENTS: Portable Fire Extinguishers
High Pressure Hydrostatic Testing.-
Dry/Wet-Chemical Extinguishing Systems
This Certificate of Registration Does Not Exclusively Recommend the Bearer
COMMISSIONER CHIEF FIRE MARSHAL
2/28/23,6:40 AM Training Certificate
eel a . ,
c"e, Of eomp -
o#
This is to certify that
an employee of
an Authorized Badger Fire Protection Distributor
has successfully completed a certification training session covering design, installation,
operation and maintenance and has demonstrated a practical knowledge of following
Badger products:
fAA
Issue Date: 2/28/2023
.Y. a Expiration Date: 2/28/2026
Michael Kraus
Training Manager
This certificate is not transferrable.Certificate is only valid as long as the above named company employs the training participant.Acceptance of this certificate
implies that the parties agree to abide by the terms of the distributor agreement or absent an agreement Kidde Fire Systems Terms and Conditions of Sale.Any
violation or alteration of this certificate will result in the immediate voiding of this certificate and possible revocation of access to the Kidde Fire Systems product line
pertaining to this certificate.
hfps://www.kidde-fenwal.com/Training/Certificate?id=46527 �/�
NYS1F
New York State Insurance Fund PO Box 66699,Albany,NY 12206
1 nysif.com
CERTIFICATE OF WORKERS' COMPENSATION INSURANCE (RENEWED)
A A^^A 113268460
SUFFOLK FIRE INC T/A
ANDERSON FIRE EQUIPMENT CO 0 .,
9 ONEIL AVE SCAN TO VALIDATE
BAY SHORE NY 11706 AND SUBSCRIBE
POLICYHOLDER CERTIFICATE HOLDER
SUFFOLK FIRE INC T/A TOWN OF SOUTHOLD
-ANDERSON FIRE EQUIPMENT CO 64376 ROUTE 25A
9 ONEIL AVE PO BOX 1169
BAY SHORE NY 11706 SOUTHOLD NY 11971
POLICY NUMBER CERTIFICAE NUMBER POLICY PERIOD DATE
1723 238-2 162511 10l29l2023 TO 10/28l2024 1/21/2024
THIS IS TO CERTIFY THAT THE POLICYHOLDER NAMED ABOVE IS INSURED WITH THE NEW YORK STATE INSURANCE
FUND UNDER POLICY NO. 723 238-2, COVERING THE ENTIRE OBLIGATION OF THIS POLICYHOLDER FOR
WORKERS' COMPENSATION UNDER THE NEW YORK WORKERS' COMPENSATION LAW WITH RESPECT TO ALL
OPERATIONS IN THE STATE OF NEW YORK, EXCEPT AS INDICATED BELOW.
IF YOU WISH TO RECEIVE NOTIFICATIONS REGARDING SAID POLICY,INCLUDING ANY NOTIFICATION OF CANCELLATIONS,
OR
STATE INSURANCE RFUND IS NOT LIABLE INTIFICATE,VISIT OUREBSIITE THE EVENT O FN TO GIVE SUCH NOTIFICATIONS. NEW
THIS POLICY DOES NOT COVER CLAIMS OR SUITS THAT ARISE FROM BODILY INJURY SUFFERED BY THE OFFICERS OF THE
INSURED CORPORATION.
PATRICK TURRO(PRESIDENT)OF A ONE
PERSON CORPORATION
THIS CERTIFICATE IS ISSUED AS A MATTER OF INFORMATION ONLY AND CONFERS NO RIGHTS NOR INSURANCE
COVERAGE UPON THE CERTIFICATE HOLDER. THIS CERTIFICATE DOES NOT AMEND, EXTEND OR ALTER
THE COVERAGE AFFORDED BY THE POLICY.
NEW YORK STAT SU NCE FUND
DIRECTOR,INSURANCE FUND UNDERWRITING
VALIDATION NUMBER:96866288
SUFFFIR-01 E A TI
CERTIFICATE OF LIABILITY INSURANCE DAT 511120/YYYY)
5/1/2024
THIS CERTIFICATE IS ISSUED AS A MATTER OF INFORMATION ONLY AND CONFERS NO RIGHTS UPON THE CERTIFICATE HOLDER.THIS
CERTIFICATE DOES NOT AFFIRMATIVELY OR NEGATIVELY AMEND, EXTEND OR ALTER THE COVERAGE AFFORDED BY THE POLICIES
BELOW. THIS CERTIFICATE OF INSURANCE DOES NOT CONSTITUTE A CONTRACT BETWEEN THE ISSUING INSURER(S),AUTHORIZED
REPRESENTATIVE OR PRODUCER,AND THE CERTIFICATE HOLDER.
IMPORTANT: If the certificate holder is an ADDITIONAL INSURED,the policy(les)must have ADDITIONAL INSURED provisions or be endorsed.
If SUBROGATION IS WAIVED, subject to the terms and conditions of the policy,certain policies may require an endorsement. A statement on
this certificate does not canter fthts to the certificate holder In Ileu of such ea rdasera4erlus.
PRODUCER CT
James F.Sutton Agency,Ltd. PHONE FAX
143-149 East Main St a ANo.Fid: 631 581-7978 ,Ne:631 581-5M
PO Box 76
East Islip,NY 11730
61SURER131AFFORDINGCOVERAGE. a
INSURER A:Forteara SpedaRy Insurance CO.
INSURED INSURER B
Suffolk Fire Inc DBA Anderson Fire Equipment INSURER Patrick Turroc'
9 O'Ne)A Avenue INSURER D:
Bay Shore,NY 11706 INSURERE
INSURER F:
COVERAGES CERTIFICATE NUMBER: REVISION NUMBER:
THIS IS TO CERTIFY THAT THE POLICIES OF INSURANCE LISTED BELOW HAVE BEEN ISSUED TO THE INSURED NAMED ABOVE FOR THE POLICY PERIOD
INDICATED. NOTWITHSTANDING ANY REQUIREMENT, TERM OR CONDITION OF ANY CONTRACT OR OTHER DOCUMENT WITH RESPECT TO WHICH THIS
CERTIFICATE MAY BE ISSUED OR MAY PERTAIN, THE INSURANCE AFFORDED BY THE POLICIES DESCRIBED HEREIN IS SUBJECT TO ALL THE TERMS,
EXCLUSIONS AND CONDITIONS OF SUCH POLICIES.LIMITS SHOWN MAY HAVE BEEN REDUCED BY PAID CLAIMS.
ILTRNSR TYPE OF INSURANCE ADDL SUBS POLICY NUMBER POLICY EFF POLICY EXP LIMITS
A X COMMERCIAL GENERAL LIABILITY 110009000
EACH OCCURRENCE
CLAIMS-MADE OCCUR C-CGL100001T-03 4IM024 404W25 taaMAt�Tot%rrED 1091600
MED ExP VVw ewe en= 51000
PERSONAL&ADV INJURY 190001wo
GERL AGGREGATE LIMIT APP IES PER: GENE AGGREGATE 2�000r�
POLICY a j LOC PRODUCTS-COMPIOP AGG 2,000,000
OTHER: $
AUTOMOBILE LIABILITY COMBINED SINGLE LIMIT
ANY AUTO BODILY INJURY Perperson)
AUrC ONLY Ap►�OpSyU�LED WLY NJUR Per&x1dent
AUTOS ONLY AUTOS O ePM AMAGE
UMBRELLA UAB OCCUR EACH OCCUR ENCE
EXCESS LIAB CLAIMS-MADE GGREGA
TE
DED I I RETENTION$
WORKERS COMPENSATION PER OTH
AND EMPLOYERS'LIABILITY Y 1 N STATuTE
o
ANYICEOPRIETERIPARTUDED?EC�VE NIA E.L. HACCIDENT
EXCandatory In NH)
Ifyyes describe under E.l DIS E-F1A F1u1P10
DESdId P 0%OF OPERATIONS below E.L.DISEASE-POLICY LIMIT
DESCRIPTION OF OPERATIONS I LOCATIONS I VEHICLES(ACORD 10%Additional Remarks Schadule,may be attached U mom space Is requhod)
Proof of Insurance
CERTIFICATE HOLDER CANCELLATION
SHOULD ANY OF THE ABOVE DESCRIBED POLICIES BE CANCELLED BEFORE
Town of Southold THE EXPIRATION DATE THEREOF, NOTICE WILL BE DELIVERED IN
5437$Route 25 ACCORDANCE WITH THE POLICY PROVISIONS.
PO Box 1169 Southold ED,NY 11971 AUTHORIZ RBPRE _
ACORD 25(2016103) m 1988-2016 ACORD CORPORATION. All rights reserved.
The ACORD name and logo are registered marks of ACORD
Zm
�
rl— - - - - -- - - - - - - - - - - - - --- - - - � � Z
22"x14" DUCT i i 22"x14" DUCT SEAL TIGHTS I W Z
( )ADP ADP ADP ADP I "
* I I * * 28'-0" HOOD —
I I IM
® - -�- -- - - — ® � — - - - - - ---
W CONTROL� — — — — — — — — 4 - - - - - - - - - - o
a
4 4 - - - - ® — aD
- - - - -- - VENT PLUG m z
ADP ADP ADP ADP
— - - - - - - - -- - - - - -- - — - - - - --- co
—� - - - - -- - - - — - -- - (TYP.) S
31"x21" J o C1? I W
r —L 1 SALAMANDER f 1� %"A" REDUCER r 1 I 1 a z
ADP
� CD
F F GRW GRW R R F F RANGE GUARD I I Q
FRYER
GUARD LPR LPRco
I _
38"x38" I RPSM e (n Z
`o ¢
CONVECTION I PULL Q o 9
6 Le, m 0° 33"x24" 36"x28n 36"x28" " n " " OVEN 36" 2" GAS I STATION
MIN. TO z 9- r a 6 BURNER 24 x36 32 x24 VALVE I o
LQ � LO 5: RADIANT 6 BURNER STEAM i
EDGE OF o o RANGE STEAMER TILT SKILLET EXIST. I pF N E W
HOOD ON X CHAR-BROILER RANGE NO-SHELF KETTLE (EXIST.)
J - Y0,9
BOTH SIDES X X 3
P
FLOOR ti Tq cF�
r 13O q
FRONT VIEWLai
SCALE:3/"=1'-O" A .
` cQ
AES MANUFACTURER: COMPONENTS: ' NOTES: U:�,` S1�Np�=oe
RANGE GUARD. _RG 1.25 GAL. RG 2.5 GAL. _RG 4 GAL 1 RG 6 GAL RANGE GUARD - RG 2.5 GALLON x Fryers to have High Limit Control to shut off fuel at 425'. o -=o
MAX. FLOW POINTS = 8 (8 USED) x Detectors shall be located over every piece of equipment. F1THUR _
Piping Material BLACK SCH 40 Max. Rise 12` TOTAL PIPE VOLUME NOT TO EXCEED 139 CUBIC INCHES x The System installed as per manufacturers specs and the AHJ. �=g <o:'
x The S tem has been installed as er UL300. P� <= �
RG 6.0 GAL. Supply Pipe Size 3 4 Branch Pipe Size 1 2 DROPS 3 8 MAX. PIPE LENGHT 63.4 FT. Ys P �¢� _ �-
" " " RANGE GUARD - RG 6.0 GALLON x The following functions to operate upon system discharge: NooZo Foal =No
RG 2.5 GAL Supply Pipe Size 1 2 Branch Pipe Size 3 8 DROPS 3 8 * Supply air damper closes * Gas fuel shuts off in kitchen oZ N= W=2. � ��
MAX. FLOW POINTS = 18 15 USED pp y P
Gas Valve Type: MECH Size 2" Manufacturer ASCO (EXISTING) ( ) * * o� S amok a wW��
yP ( TOTAL PIPE VOLUME NOT TO EXCEED 400 CUBIC INCHES Exhaust fan remains on Electric fuel shut off under hood 0W00 rnFao< s"W`z
Detector Temperature Rating: 360' 450' MAX. PIPE LENGTH 75 FT. * All systems to activate simultaneously in same hazard area. 2�as fag WT e oe
* Fire Alarm shall activate.
Hood Size: 28'-0" Duct Size: �21 22�x14" RG-2.5 GAL CYLINDER #60-120002-001 x Manual Pull Station shall be located a minimum of 10 ft. from i?
EQUIPMENT SURFACE NOZZLE RG-6.0 GAL CYLINDER #60-120005-001 hood & a maximum of 20 ft. from hood and 4 ft from floor. Q, 1E
#
QTY. TIP#/QTY. LOCATIONS CONTROL HEAD B120099 x All fuel sources are GAS unless otherwise noted.
TYPE AREA HEIGHTS
ADP NOZZLE #87-120011-001
DUCT 2 22"x14" ADPI 4 On-so 0"-6" IN OPENING F NOZZLE #87-120012-001 CODE REFERENCES: (TYPE 1 GREASE HOOD) z r
PLENUM 1 28-0 ADP 4 0 -6 FROM END OF PLENUM t Z o
LPR NOZZLE #87-120022-001 C
FRYER 2 14"x23.5" F 2 27"-45" 45' TO 90' THIS INSTALLATION IS IN CONFORMANCE WITH: n
RAD. CHAR-BR. 1 33 x24 GRW 2 24 -48 45' TO 90' R NOZZLE #87-120014-001 C0
n n " " GRW NOZZLE #87-120013-001 - NFPA 17A - 2017 �t.; �' �`rj t� m O o
6 BURNER RANGE 1 36"x28" LPR 2 16"-20" CENTER 369 LINK WK-282664-000 - NFPA E A ICAL ��J
# - NYS MECHANICAL CODE 506,507,508
SAIAMANDER 1 31"x21" ADP 1 - TOP 4" OF COMPARTMENT 45V LINK #WK-282663-000 - ASTM E2336 - 2016 }
6 BURNER RANGE 1 36"x28" R 2 20"-42" CENTER LINK HOUSING #804548 - THE BUILDING AND FIRE CODES OF NEW YORK STATE - 2020 SEP - 9 2024 c Q o
TILT SKILLET 1 32"x24" F 2 27.5"-46" FRONT EDGE AIM CENTER MANUAL RELEASE #B875572 NOTE:
2" GAS VALVE B120075
# - COOKING EQUIPMENT CHANGE Building Deg�artct��n m ,,+ z
A FIRE EXTINGUISHER WITH A MINIMUM RATING — NO PIPING REQUIRED town of Southold aCD
CD CO
OF CLASS K MUST BE INSTALLED WITHIN THE — SAME CONTROL HEAD
VICINITY OF THE COOKING AREA. — SAME TANKS o_
n " rl-- - --- - --^- - -- - ----- —^
- - - --- - -- - - - -- -�� � � a
F•�I �
22 x14 DUCT I I 22"x14" DUCT SEAL TIGHTS I W r
*P I I *P * 28'-0" HOOD
ADP z
CET-
�— - - - $r-- - ®- - -- - - r--- - - - - - -- CONTROL ---1
450'CET 450' 450' 450' 3�- —1 I — —— — — — 4-®—— r —— — — HEAD I �, �-
—L �I— _ -- _ - - �I— J 1 VENT PLUG rn CR Z
ADP _r - - — ADP ADP - - -�- -- — 1-11 ADP O
--- - - -- -- -- -- n „— -- —— — — -- - -- - --- -- `- - -- - - - - - ----— — — (TYP.)
3 F_
r I r 17 1 S AlAMANDER F_ 1 " " REDUCER I- 1 co cv I I a
�► �► �► ADP l l C.DW I I z
F F Gaw GRW I — R R F �f Z co
VA RANGE GUARD 1 I wa
FRYER �~
in GUARD LPR LPR o z
I " " RPS G n " :_ � CONVECTION 1 PULM
o U 6 O
L m M 33"x24" 36"x28" 36 x28 n .P_5�!'
OVEN " p STATIONMIN. TO n a a 6 BU NER 24 x36 �34?` 36 2 GASEDGE OF "' o 'n c RADIANT t6 BURNER STEAM VALVE I o F N E INC —B OU_ER RANGE RANGE STEAMER T�i.TT I 0 O,Q
HOOD
ON
DES NO _"' KETTLE (EXIST.)
—I �* �ti T
FLOOR co v
FRONT VIEW g
SCALE:38"=1'-0" 0776
Pam'
AES MANUFACTURER: COMPONENTS: NOTES: OF SS
RANGE GUARD: _RG 1.25 GAL _(1)_RG 2.5 GAL. —___RG 4 GAL. I RG 6 GAL. RANGE GUARD — RG 2.5 GALLON x Fryers to have High Limit Control to shut off fuel at 4257. o a =izo
Piping Material �IACK SCH 40 Max. Rise _ MAX. FLOW POINTS = 8 (8 USED) x Detectors shall be located over every piece of equipment. � W W
" TOTAL PIPE VOLUME NOT TO EXCEED 139 CUBIC INCHES x The System installed as per manufacturers specs and the AHJ, s <o�
RG 6.0 GAL. Supply Pipe Size 3 4 Branch Pipe Size 1 2 DROPS 3 8 MAX. PIPE LENGHT 63.4 FT. x The System has been installed as per UL300. .��Q
Supply p " x The followin functions too p 4§<� i;Z�o
RG 2.5 GAL Su I Pipe Size 1 Branch Pipe Size 3 8 DROPS 3 8 RANGE GUARD — RG 6.0 GALLON 9 perate upon system discharge: 8 Mal l � 8
* Supply air damper closes * Gas fuel shuts off in kitchen g�o $_� s op;
Gas Valve Type: MECH Size 2" Manufacturer ASCO (EXISTING) MAX. FLOW POINTS = 18 (15 USED) * Exhaust fan remains on * Electric fuel shut off under hoods � Q ratY�Z
Detector Temperature Rating: 360' 450' TOTAL PIPE VOLUME NOT TO EXCEED 400 CUBIC INCHES All systems to activate simultaneously in same hazard area. �2�asZa«a 808
Hood Size: 28'-0" Duct Size: (2) 22"x14„ MAX. PIPE LENGTH 75 FT. * Fire Alarm shall activate.
RG-2.5 GAL. CYLINDER 60-120002-001 x Manual Pull Station shall be located a minimum of 10 ft. from C
EQUIPMENT SURFACE NOZZLE # hood & a maximum of 20 ft. from hood and 4 ft from floor. ~
CI
TY.om' AREA TIP#/QTY. HEIGHTS LOCATIONS RG-6.0 GAL. CYLINDER #60-120005-001 x All fuel sources are GAS unless otherwise noted. o a
DUCT 2 '22"x14" ADP 4 0"-6" 0"-6" IN OPENING CONTROL HEAD #B120099
ADP NOZZLE #87-120011-001
PLENUM 1 28'—O" ADP 4 0"-6" FROM END OF PLENUM Z }
FRYER 2 14"x23.5" F 2 27"-45" 45' TO 90' F NOZZLE #87-120012-001 CODE REFERENCES: (TYPE 1 GREASE HOOD) r t Z
LPR NOZZLE #87-120022-001 . o 0 E
(O
THIS INSTALLATION IS IN CONFORMANCE WITH: c o
�I
D. CHAR—BR. 1 33"x24" GRW 2 24"-48" 45' TO 90' R NOZZLE #87-120014-001 m
— NFPA 17A — 2017 ,J T Q o
6 BURNER RANGE 1 36"x28" LPR 2 16"-20" CENTER GRW NOZZLE #87-120013-001 — NFPA 10 — 2018 .0 m
rA
SALAMANDER 1 31nx21" ADP 1 — TOP 4" OF COMPARTMENT 360' LINK #WK-282664-000 _V o
— NYS MECHANICAL CODE 506,507,508 � �I
6 BURNER RANGE 1 36 x2$" R 2 20"—42 CENTER 450' LINK #WK-282663-000 — ASTM E2336 — 2016 •C
LINK HOUSING 804548 V Y Q o
'
TILT SKILLET 1 34"x25" F 2 27.5"-46" FRONT EDGE AIM CENTER - THE BUILDING AND FIRE CODES OF NEW YORK STATE - 2020
MANUAL RELEASE #B875572 = ,g
2" GAS VALVE #B120075 Q CEO ,,,,q z q
A FIRE EXTINGUISHER WITH A MINIMUM RATING (L ;�1 ° CO
OF CLASS K MUST BE INSTALLED WITHIN THE
VICINITY OF THE COOKING AREA. o-
T
~y�I— — —— — — — —— — — — — — — — — — — — — — — — — — — — — — — — — — — a 6
22"x14" DUCT i i 22"x14" DUCT L TIGHTS I N
ADP ADP I I ADP ADP 28'-0" HOOD (TYP) I o
- -® - - - = - - - - � — rl— I w � Z♦ t t _
- - - - -- --� - - 0 - -- -- -- - - - - - CONTROL
450° 3 HAD450°450' — -- -- 450I 450° a L- -1- - - - - - - - - - - - - - - -- - - VENT PLUG U] ms z
ADP ADP ADP — — — — — — ADP
-' (TYP.) m Q
— — — — — — — — — —— —— — — — — — — — — — — — — — — —— — —— — — i' '
C7 '� J
31%21
I- -I F_ -I1 SALAMANDER r- ___1 %"xY" REDUCER F_ -I I I a z
�► ADP �► �► I I ''' cn
F F GRW GRW I— R R F F RANGE GUARD I I Q
FRYEREL N z5
GUARD LPR LPR 1 a n = Z
38"x38" I RPSM 3 W w < 3
o' Uj CO OVEN
6 W w 2 GAS PULL Q a N o
L m � °�° 33"x24" 36"x28n 36"x28" 36n " I STATION
MIN. TO - a _ d 6 BURNER 24"x36" 2 X '4" VALVE I o
Ul, � RADIANT 6 BURNER STEAM i
EDGE OF ,�, o M o CHAR-BROILER RANGE RANGE STEAMER TILT SKILLET KETTLE (EXIST.)
HOOD ON X X NO-SHELF
BOTH SIDES
FLOOR
FRONT VIEW
SCALE:%"=1'-O"
AES MANUFACTURER: COMPONENTS: NOTES: _ m
oZ 3
RANGE GUARD: _RG 1.25 GAL. (1�_RG 2.5 GAL. _RG 4 GAL. (�_RG 6 GAL. RANGE GUARD — RG 2.5 GALLON- x Fryers to have High Limit Control to shut off fuel at 425'. Z oN � s�o Z�?0
MAX. FLOW POINTS = 8 (8 USED) x Detectors shall be located over every piece of equipment. o"rrw�E3E
Piping Material BLACK SCH 40 Max. Rise 12' KW
TOTAL PIPE VOLUME NOT TO EXCEED 139 CUBIC INCHES x The System installed as per manufacturers specs and the AHJ.
W2J T,�,ggws UKNH
A The System has been installed as per UL300. -Za -mm, Z
RG 6.0 GAL. Supply Pipe Size 3 4" Branch Pipe Size 1 2" DROPS 3 8" MAX. PIPE LENGHT 63.4 Fr. Y P <W� =w��= Q
�> " RANGE GUARD — RG 6.0 GALLON x The following functions to operate upon system discharge: 'Noo.o Mzl �X,Na
RG 2.5 GAL. Supply Pipe Size 1 2 Branch Pipe Size 3 8 DROPS 3 8" * Supply air damper closes * Gas fuel shuts off in kitchen oZ N zgo3 3` -
MAX. FLOW POINTS = 18 (15 USED) PPY P ww=^N ��
Gas Valve Type: MECH Size 2" Manufacturer ASCO (EXISTING) * Exhaust fan remains on * Electric fuel shut off under hood =oWa &wg "W'o
TOTAL PIPE VOLUME NOT TO EXCEED 400 CUBIC INCHES 'oWog ���ao� a�wo
Detector Temperature Rating: 360' 450' MAX. PIPE LENGTH 75 FT. * All systems to activate simultaneously in same hazard area. <=as a�«a� e�oS
* Fire Alarm shall activate.
Hood Size: 28'-0" Duct Size: (2)2) 22"x14" RG-2.5 GAL. CYLINDER #60-120002-001 x Manual Pull Station shall be located a minimum of 10 ft. from 2
RG-6.0 GAL. CYLINDER #60-120005-001 hood & a maximum of 20 ft. from hood and 4 ft from floor. v ey H
EQUIPMENT SURFACE NOZZLE ..
QTY. TIP#/QTY. LOCATIONS CONTROL HEAD B120099 x All fuel sources are GAS unless otherwise noted.
TYPE AREA HEIGHTS # �' 1.
DUCT 2 22"x14" ADP 4 0"-6" 0"-6" IN OPENING ADP NOZZLE #87-120011-001 r a
F NOZZLE #87-120012-001 CODE REFERENCES: (TYPE 1 GREASE HOOD) -0 � }
PLENUM 1 28'-0' ADP 4 0"-6" FROM END OF PLENUM - z o
LPR NOZZLE #87-120022-001 o 0
FRYER 2 14"x23.5" F 2 27"-45" 45' TO 90' THIS INSTALLATION IS IN CONFORMANCE WITH: CL
R NOZZLE #87-120014-001 — NFPA 17A — 2017 a�
RAD. CHAR—BR. 1 33"x24" GRW 2 24"-48" 45' TO 90' a� cLn
GRW NOZZLE #87-120013-001 — NFPA 10 — 2018
6 BURNER RANGE 1 36"x28" LPR 2 16"-20" CENTER 369 LINK #WK-282664-000 — NYS MECHANICAL CODE 506,507,508 U 0°
SALAMANDER 1 31"x21" ADP 1 — TOP 4" OF COMPARTMENT 450' LINK #WK-282663-000 — ASTM E2336 — 2016 'E �I
6 BURNER RANGE 1 36"x28" R 2 20"-42" CENTER LINK HOUSING #804548 — THE BUILDING AND FIRE CODES OF NEW YORK STATE — 2020 g C.
TILT SKILLET 1 32"x24" F 2 27.5"-46" FRONT EDGE AIM CENTER MANUAL RELEASE #13875572 V a
NOTE:
2" GAS VALVE #13120075 >,001C1 G�EQUIPMENT CHANG N m z
„-�V
A FIRE EXTINGUISHER WITH A MINIMUM RATING =: O xf?I lN3G�'REQ.UIRED�; o O
CD
OF CLASS K MUST BE INSTALLED WITHIN THE
SAID C0 ZRO EAD7 �1
VICINITY OF THE COOKING AREA. Sq y=TANKS== _ a
Component Description
A x s
TOP OF f ,' CENTER OF
CYLINDER VALVE ; Y DISCHARGE PORT
-10�I NOMINAL
CYLINDER
DIAMETER
Figure 2-1. Dimensions of Cylinder and Valve Assembly, P/N B-12X3XX
Refer to Figure 5-26 for Cylinder Valve details.
Table 2-1. Cylinder and Valve Assembly Specifications
Cylinder and Valve Maximum Mmeaslons
Assembly Part Number Model
(old P/N) Flow Number A H C
60-120001-001 RG-1.25G 4 15-1/4 in. 13-3/4 in. 8 in.
(Bi20001) (387 mm) (349 mm) (203 mm)
21 in. 19-5/8 in. 9 in.
(534 mm) (498 mm) (230 mm)
60-120003-001 RG-4GS 12 19 in. 17-1/2 in. 12-1/4 in.
(B120003) (483 mm) (444 mm) (311 mni)
60-120006-001 RG-4GM 12 24-3/8 in. 23 in. 10 in.
(13120006) (619 mm) (584 mm) (254 mm)
® 35-1/8 in. 33-3/4 in. 10 in.
(892 mm) (857 mm) (254 mm)
Note: It is permisible to use old and/or new cylinders included in this manual on a Range Guard
system.
P/N 60-9127100-000 2-3 Aprll 2009
Component Description
CYLINDERSTRAP—. .,.vu-*u, ,m
.a;
C
Figure 2-3. Shelf Bracket, P/N 100013
Table 2-3. Mounting Bracket Dimensions
Dimensions
Part No. Model
A B C
100013 RG-6G 11 in. 10-1/8 in. 21-1/8 in.
RG-4GM (279 mm) (258 mm) (537 mm)
2-1.1.1.1 Floor Mount Bracket Kit, P/N 100010
A Floor Mount Bracket Kit is used for mounting the RG-6G/RG-4M cylinder to the floor. The Floor
Mount Bracket Kit requires Wall Mounting Bracket P/N 100013.
3181n.DIAMETER
BOLTS TO ATTACH
TO WALL MOUNTING 318 in.DIAMETER
BRACKET BOLTS TO ATTACH
TO WALL MOUNTING
BRACKET
P
5 C
6\B�
Figure 2-4. Floor Mount Bracket Kit, P/N 100010
Table 2-4. Floor Mounting Kit Specifications
Dimension A Dimension B Dimension C
3 in. (76 mm) 9-5/8 in.(245 mm) 6-9/16 in.(168 mm)
P/N 60-9127100-000 2-5 April 2009
Component Description
2-1.1.1 CYLINDER BRACKETS
I♦— A —♦I CYLINDER STRAP CYLINDER STRAP
O
'IIIIIIIIIIf11fIIt1Utt1 �2tt1ltltlillllilllliiltli(tili -
_..�,, fiTii „,i`-FT"S"�Eimnn.•.�,- lGIIt1I1111111ft11111t111itittlliliftt71itI111t1111111pNi'`
:la
O �
O O
B i B
I
I
O
It--C—►I
FRONT VIEW SIDE VIEW
Figure 2-2. Mounting Brackets
Table 2-2. Mounting Bracket Dimensions
Dimensions
Part No. Model
A B C
9197430 RG-125G 3 in. 9-3/8 in. 1-3/8 in.
(76 mm) (238 mm) (35 mm)
4-1/2 in. 12 in. 2-1/2 in.
(114 mm) (305 mm) (64 mm)
9197414 RG-4GM 4-1/2 in. 20-1/2 in. 2-1/2 in.
(114 mm) (521 mm) (64 mm)
9197415 RG-4GS 4-1/2 in. 11-1/2 in. 2 in.
(114 mm) (290 mm) (51 mm)
April 2009 2-4 P/N 60-9127100-000
C,on,pomwmt Description
Table 2-6.Range Guard Nozzles
Nozzle Type Pan Number Flow Number Grooves
(Old Part Number)
IgpWiloaft 87-120011-001 i 1 ..............
(BI2001 1)
87-120012-001 2 2
(BI20012)
87-120013-001 1 3
(BI20013)
87-120014-001 1 4 jL—;
(BI20014)
DM Nozzle 87-120015-001 3 0
(BI20015)
LPF Nozzle 87-120022-001 2 1 &4
(Bl2OD22)
87-120024-001 1 Disc&Core
(BI20024)
--A
Note: It is permissible to use old and/or new nozzles included in this manual in a Range Guard
system.
AprJI 2009 2-8 P/N 60-9127100-WO
Component Description
2-3.3 Mechanical Gas Valve.P/N B12007X
A Mechanical Gas Valve is required on systems used to protect gas-fueled appliance(s). Upon system
actuation,the control stem closes, stopping the gas flow to the appliance(s).
Note: Only Mechanical Gas Valves that are specifically UL listed and identified by part number in
this manual may be used with the Range Guard system.
CONTROL STEM
y
INLET _ OUTLET
Figure 2-42. Mechanical Gas Valve,P/N B 12007X
Table 2-17. Mechanical Gas Valve Sizes
Pipe size Part Number
3/4 in.(19 mm) B 120071
i in. (25.4 mm) B120072
1-1/4 in.(32 mm) B120073
1-1/2 in.(38 mm) B120074
B120075
2-1/2 in.(64 mm) B120076
3 in.(76 mm) B 120077
Apri12009 2-38 P/N 60-9127100-000
Component Description
2-2 CONTROLS
2-2.1 UNIVERSAL CONTROL HEAD (UCH) Control System, P/N B120099
The UCH Control System, P/N B 120099, is used for actuating the Range Guard Cylinder and Valve
Assembly.The UCH Control System can be attached to the System Valve Actuator, P/N B 120042 for
direct cylinder mounting,or to a wall for remote mounting.Knockouts are provided to accommodate
either type of mounting.The controller can be operated with:
• Automatic mechanical detection (fusible-links and thereto-bulb links),
• Automatic electrical operation, and
• Remote and local manual operation.
(240 met)
i ;I I I� ;•..-
3-3/4 in. 8-3/16 in.
(95 mm) (208 mm)
Figure 2-15. UCH Control System, P/N B120099
P/N 60-9127100-000 2-13 April 2009
Component Description
2-2.4 Remote Manual Releases
2-2.4.1 REMOTE MANUAL RELEASE, P/N B875572 (UCH ONLY)
The Remote Manual Release,shown in Figure 2-35,is provided as a means of manually actuating the
system from a remote location. The Remote Manual Release is attached to the UCH Control System
with 1/1 6-Inch control cable.To actuate the system at the Remote Manual Release, pull out the safety
pin and pull hard on the handle.
Each Remote Manual Release is supplied with a separate nameplate. This nameplate must be
attached to the mounting surface 1-inch above or below the Remote Manual Release.
3-5/8 in.
(92.2 mm)
kk
7-4
1-1/2 in.
/(38 mm)
r
Figure 2-35. Remote Manual Release, P/N B875572
P/N 60-9127100-000 2-31 April 2009
Component Description
2-2.3.2 UNIVERSAL-LINK HOUSING SIT,P/N 120064
The Universal-Link Housing Kit, shown in Figure 2-29,consists of the following:
Table 2-12. Universal Link Housing Kit, P/N 120064
Item Quantity
11-1/2 in.(292 mm)Detector Housing 1
Crimp Sleeves 2
"S"Hooks 2
The items above are used to attach the Fusible-Link or Thermo-Bulb Links to the 1/16-inch cable
leading to the UCH Control System or A+Control Box.The Universal-Link Housing can be configured
as an End-of-Line or In-Line bracket.
1/16 in.CABLE
TO CONTROL SYSTEM
(NOT SUPPLIED)
"S"HOOKS
CRIMP
SLEEVE
.1Z92mcnl� �
THERMO-BULB LINK I✓�►112tn LOCKNUT
OR FUSIBLE-LINK ! (NOT SUPPLIED)
(NOT SUPPLIED) I_ THERMO-BULB LINK
OR FUSIBLE-LINK
(NOT SUPPLIED)
CRIMP
SLEEVE 112 in.EMT
EXAMPLE OF END-OF-LINE CONNECTOR EXAMPLE OF IN-LINE
UNIVERSAL HOUSING KIT "S"HOOK (NOT SUPPLIED) UNIVERSAL HOUSING KIT
Figure 2-29. Example of End-of-line and In-line Universal Link Housing Kit, P/N 120064
PIN 60-9127100-000 2-25 April 2009
Component Description
2-2.3.7 CORNER PULLEY, P/N WS-844648-900
The Comer Pulley is used to change the direction of the control cable runs. The cable's protective
conduit(1/2-inch EMT)is attached to the Comer Pulleys with the coupling nuts provided.The Corner
Pulley is equipped with a ball-bearing pulley for minimum resistance to the cable travel.
3 in.
(76.2 mm)
3 in.
(76.2 mm)
Figure 2-33. Comer Pulley,P/N WK-844648-900
P/N 60-9127100-000 2-29 April 2009
Component Description
2-2.1.6 NUCROSWITCH KIT, P/N B120039,B120039-501 (FOR UCH)
The Microswitch Kit is a single pole, double-throw switch (see Figure 2-21 and Table 2-7).Included
in the kit is the microswitch,pigtail assembly and four mounting screws (two short and two long).
Note: Microswitch Kit P/N B 120039-501 includes pigtail assembly with white stripes.
The wire leads are 24-inches(610 mm)in length.Four Microswitch Kits can be mounted in the UCH
Control System. There are two mounting locations to accommodate the four Microswitch kits (two
stacked at each mounting location), with EMT ports for each mounting location. This allows for the
use of two electrical junction boxes for separation of signal lines and AC lines.
These are used when it is necessary to open or close electrical circuits. The following are examples,
but not limited to:
• Electric appliance shutdown
• Make up air shutdown
• Electric gas valve shutdown
• Shuntbreaker/relay
Note: Not for alarm initiation.
Electrical appliances usually have a higher amp rating than the switches.In this case,such appliances
shall not be wired directly to the microswitch.A magnetic contactor or relay must be used.
To wire the microswitch for UCH, refer to Figure 4-30.
ELECTRICAL CONNECTOR
_INCQ COM NO
MICROSWITCH
Figure 2-21. Microswitch Kit,P/N B120039
Table 2-7. Microswitch Electrical Ratings
125/250 Vac 20.5 Amps
250 Vac 1-1/2 HP
125 Vac 1/2 HP
Aprll 2009 2-18 P/N 60-9127100-000
System Design
3-6 VENTILATION
3-6.1 Plenums
Table 3-29.Plenum Protection
Items Parameters ADP Nozzle
No Filter 1 10 ft.x 4 ft.(3 m x 1.2 m)Max. 1 -located at one end of the plenum
"V"Filter 10 ft.x 4 ft. (3 m x 1.2 m) 1 -located at one end of the plenum
20 ft.x 4 ft.(6 m x 1.2 m) 2-located at end of plenum pointing inwards
10 ft.x 4 ft.(3 m x 1.2 m) 1 -located at one end of the plenum
20 ft.x 4 ft.(6 m x 1.2 m) 2-located at end of plenum pointing inwards
1 When no filters are present,the nozzle protecting the plenum is used to discharge the wet chemical on the under-
side of the hood.In this case,the hood may not exceed a length of 10 ft.(3 m)or a width of 4 ft. (1.2 m).
Plenums larger than 10 ft. (3.0 m)x 4 ft. 11.2 m)may be protected by adding additional ADP nozzles
for ach additional 10 ft. (3.0 m)of lenum length„and each additional 4ft. (1.2 m)of plenum width.
and/or at the ends of the plenum pointing
toward eac other(see Figure 3-28).Each nozzle wild provide coverage for a maximum of 10 ft. (3 m)
of plenum length and 4 ft. (1.2 m)of plenum width.
ADP nozzles must be centrally located in the plenum with their discharge directed along the length of
the plenum and located in relation to the filters as shown in Figure 3-28.Refer to Figure 3-28 for filter
height.
P/N 60-9127100-000 3-33 April 2009
System Design
3-6.'1'.1.2 Ducts 50 to 100 inches in Perimeter
Two ADP nozzles,P/N 87-120011-001,pointing in the same direction are required for protection of
ducts with perimeters greater than 50 inches and less than or equal to 100 inches. Ducts can be of
unlimited length(refer to Figure 3-30).
For other option of ducts up to 75 perimeter inches(See Figure 3-32).
Note: All Range Guard systems are listed by UL and ULC for use with the exhaust fan either on or
off when the system is discharged.
DUCT
HOOD
X X
%X 1/zX 1/X �/ 1/d 1/2d MAX.DIAMETER 31.83 in.(809 mm)
I I NOZZLES TO BE ALONG ONE
25 in.(635 mm) CENTERLINE AT THE 114 POINTS.
MAX.SIDE ♦ ♦ NOZZLES TO BE 0-6 in.(0-152 mm)
UP FROM ENTRANCE OF VERTICAL DUCT
MAX.DIAGONAL 11.78 in.(300 mm)
MAX.DIAGONAL TYP(2)ADP NOZZLES
11.78 in.(300 mm)
SQUARE RECTANGULAR /ROUND
YG
• ADP NOZZLE
I
I 010 6 in.
_ rto52 mm)
DUCT ENTRANCE
% OF VERTICAL DUCT
I
T OF HORIZONTAL DUCT
I �
2.4 in.(51 mm-102 mm) ADP NOZZLE AIM POINT
NOZZLE TIP TO DUCT HIP
VERTICALIHORIZONTAL DUCT
Figure 3-30. Duct Protection Using Two ADP Nozzles, P/N 87-1200 1 1-00 1
April 2009 3-36 P/N 60-9127100-000
System Design
3-4.22 Tilt SkilletS (Braising Pans)
Table 3-28. F Nozzle Coverage Area
Items Parameters
Maximum Hazard Area 24 in.x 24 in.(610 mm x 610 nun)
Nozzle Aim Midpoint of hazard area and placed so it does not
interfere with appliance operation
Nozzle Location—At the front perimeter line of the 27-1/2 in.(699 nun)Min.
appliance 46 in.0168 mm)Max.
Note:Appliance cover cannot interfere with distribution
of agent from the nozzle.
F NOZZLE
I
COVER MUST NOT
INTERFERE WITH
EDGE OF
DISCHARGE PATTERN
I
JI
� / 1
� % I
� 1
i
� / 1
I
I
(I
L CENTERLINE OF
HAZARD ZONE
THE NOZZLE IS TO BE PLACED TOWARD THE FRONT OF THE APPLIANCE
TO MINIMIZE THE POTENTIAL FOR THE SKILLET OR BRAISING PAN
COVER TO INTERFERE WITH THE NOZZLE DISCHARGE.
Figure 3-24. Tilt Skillet(Braising Pan)
P/N 60-9127100-000 3-29 April 2009
System Design
3-4.9 Four Burner Ranges
Table 3-13. R Nozzle Coverage Area—Four Burner Range
Items Parameters
Maximum Hazard Area 28 in.x 28 in.(711 mm x 711 mm)
Nozzle Aim Midpoint of Hazard Area
Nozzle Location—Anywhere within the area of a circle 20 in. (508 mm)Min.
generated by a 9 in.(229 mm)radius about the midpoint 42 in. (1067 mm)Max.
Note: Shape of burner not important.
181n.(457 mm)DIA.
I
42 In.(1067 mm)MAX.
1 (FROM TOP OF RANGE)
i A'R'NOZZLE MAY BE
�... LOCATED ANYWHERE WITHIN
THE SHADED AREA
201n.(508 mm)MIN. _ AIM POINT.MIDPOINT OF
(FROM TOP OF HAZARD AREA
RANGE)
28 in.(711 mm) 14In.(356 mm)MAX.
MAX.HAZARD BURNER CENTERLINE
AREA LENGTH i TO CENTERLINE
141n.(356 mm)MAX.
BURNER CENTERLINE
TO CENTERLINE
�---- 28 In,(711 mm)MAX.
HAZARD AREA WIDTH
Figure 3-10. R Nozzle Coverage for a 4-Burner Range
P/N 60-91271004M 3-15 April 2009
System Design
3-4.10 Two Burner Ranges
'Fable 3-14. R Nozzle Coverage Area—Two Burner Range
Items PM=Cters
Maximum Hazard Length 28 in.(711 mm)
Nozzle Aim Midpoint of hazard area
Nozzle Location-Anywhere within the area of a circle 20 in. (508 mm)Min.
generated by a 9 in. (229 mm)radius about the midpoint 42 in. (1067 mm)Max.
Note:Shape of burner not important.
I 18 in.(467 mm)DIA.
1 — 42 in.(1067 mm)MAX.
1 (FROM TOP OF RANGE)
( A`R'NOZZLE MAY BE
1 LOCATED ANYWHERE WITHIN
I THE SHADED AREA
1
I
1
I
I
I
20 In.(508.mm)MIN. AIM POINT.MIDPOINT OF
(FROM TOP OF RANGE) HAZARD AREA
281n.(711 mm)MAX. 14 in.(356 mm)MAX.BURNER
HAZARD AREA CENTERLINE TO CENTERLINE
LENGTH
Figure 3-11. R Nozzle Coverage for a 2-Burner Range
April 2009 8-16 P94 60-9127100-000
System resin
3-4.13 Upright sroil ,SA�A�An>ar R
Table 3-19.ADP Nozzle Coverage Area
Items Parameters
Broiler Compartment With Maximum Internal Horizontal 30-1/4 in.x 34 in. (768 mm x 864 mm)
Dimensions
Nozzle Aim Through grill toward the center of the grease drain-off
opening
Nozzle Location Within the top 4 in. (102 mm)of space in the broiler
compartment Commonly mounted near the front
opening and directed inside the broiler
o EXHAUST
BROILER JRM
G — DUCT
COMPARTMENT VE
GRILL
4 in. 102 mm
MAX. ► 4 30-114 In. h34 in.(864 mm)�
768 mm MAX.
GREASE
o -4-- GREASE DRA PAN DRAIN-OFF
FRONT
(BROILER DOOR REMOVED) RIGHT SIDE
NOTE: DIMENSIONS SHOWN ARE INSIDE BROILER COMPARTMENT
ADP NOZZLES SHOULD BE MOUNTED ON THE PERIMETER OF THE BROILER
TOP(SHADED AREA). IT SHOULD BE DIRECTED THROUGH THE GRILL
TOWARD THE CENTER OF THE GREASE DRAIN-OFF OPENING. NOZZLE
DISCHARGE SHALL NOT BE OBSTRUCTED BY ANY STRUCTURAL PART OF
THE BROILER.
Figure 3-15. ADP Nozzle Placement for Upright Broilers
April 2009 3-20 P/N 60-9127100-000
System Design 4,
3-4.12 Four Burner Ranges (LPR). PIN B120024
that has a back shelf or all,
age provides protection for a range top 4
The low proximity range top cover
broiler integral to the regular range.
A,
n
Table 3-16.LPR Nozzle Coverage Area—Four Burner Range
Parameters
Items
24 in.x 24 in. (610 Trim x 610 mm)
!lHazard Hazard
Midpoint of hazard area
Maximum
e
Fig we Refer
Location
im R er to Table 3_17
Nozzle LocatLon—Dimension A In Figure 3-13 Refer to Table 3-17
Table 3-17. LPR Nozzle Parameters
Burner Spacing Centerline to Centerline, Nozzle Height Wimension A)
(Dimension B in Figure$-13) (centrally over the range and under sheWbrailer)
Note: Shape of burner not Important-
14 in.(356 nun) =6in. (406 mm)Min.
20 in. (508 mm)May-
Between 12 in.and 14 in.(305 nun and 432 mm) 16 in(406 nun)Min.
(432 mm)Max-In
(406
10 in. and 12 in. m 305 mm) 16 In.(406 mm)
Between 1254 mm and 305 mm)
V�
DIMENSION"A" AN LPR NOZME MAY BE
F
(NOZZLE HEIGHT LOCATED OVER THE CENTER
MEASUREDTO 1OF THE HAZARD AREA.SEETOP OF BURN— TABLE FOR NOZZLE HEIGHTS.
ApA POINT:MIDPOINT OF
to HAZARD AREA
24 In. DIMENSION"B"
MAX.HAZARD
AREA LENGTH
DIMENSION"a"
4-- 24 in.(610 mm)MAX.
HAZARD AREA V610TH
Figure 3-13. LPR Nozzle Coverage for a 4-Burner Rang e (LPRI
7100-0
P/N 60-9127100
System Design
3-4.15 Gas Radiant/Electric Charbroiler
Table 3-21. GRW Nozzle Coverage Area
Items Parameters
Maximum Cooking Surface 21 in.x 24 in.(533 nun to 610 mm)
Nozzle Aim Midpoint of the hazard area above cooking surface
Nozzle Location(located at an angle of 45°or more from 24 in.(610"mm)Min.
the horizontal) 48 in.(1219 mm)Max.
A GRW NOZZLE MAY BE LOCATED
Afi1 MHERE VWTM THE GRID
481n.(1219 mm) DIAGONAL FROM
MAX. AIM POINT
48 in.(1219 mm) 481n.(1219 mm)
MAX. MAX, A GRW NOZZLE MAY BE
LOCATED ANYWHERE
WITHIN THE GRID
i
i
24 in.1:810 mm) AIM POINT:MIDPOINT
AIL OF HAZARD AREA
M NOZZLE LOCATION 9 �F1
W OR MORE FROM
HORIZONTAL \ .91
21 in.(533 mm) AIM POINT:
MAX. MIDPOINT OF \\
HAZARD AREA \
RADIANT LAYER
LA,
GAS FLAME �� I
r 21 In.(533 mm)MAX.
f---- 241n.(610 mm)
APPLIANCE AREA
MAX.
FRONT VIEW SIDE VIEW
Figure 3-17. Gas Radiant/Electric Charbroder
April 2009 `3-22 P/N 60-9127100-000
System Design
3-4.4 14 in.x 14 in. (356 mm x 356 mm) Deep Fat Fryer
Table 3-5.F Nozzle Coverage Area
Items Parameters
Maximum Hazard Area 14 in.x 14 in. (356 mm x 356 mm)
Maximum Appliance Area(with drip board) 14 in.x 24-1/2 in.(356 mm x 622 mm)
Nozzle Aim Midpoint of hazard area
Nozzle Location(from top of appliance at an angle of 450 or more 27-1/2 in.(686 mm)Min.
from the horizontal) 45 in.(1143 mm)Max.
AN F NOZZLE MAY BE LOCATED
ANYWHERE WITHIN THE GRID AN F NOZZLE MAY BE
LOCATED ANYWHERE
WITHIN THE GRID
451n.(1143 mm) DIAGONAL FROM
MAX AIM POINT 1
1
1
1
46 in.(114 mm) 45 in.(�mm)
z �
s OFF
NOZZLE LOCATION ' ��� 1.E
45'OR MORE FROM
HORIZONTAL
MIDPOINT OF `%
HAZARD AREA
2T-112 In.
(60 mm)MIN
AIM POINT:
1 R MIDPOINT OF
\ HAZARD AREA
14 in.(358 mm) 24.112 HAZARD AREA
MAX 7 (622 mm)MAX
1 \ DRIPBOARD14
DRIP BOARD \a- 14 in.(356 mm)MAX.
24112 in.(622 mm)MAX
APPLIANCE AREA
14 14 In.(356 mm)MAX
FRONT VIEW SIDE VIEW
Figure 3-5. 14 in.x 14 in. (356 mm x 356 mm)Deep Fat Fryer
P/N 60-91271004= 3-9 April 2009
r
1
F
~4 O
— — — — — — — -
- - —— — -
-— — —
22 --
"x14" DUCT 22x14 DUCT I I " " SEAL TIGHTS I W
r
ADP ADP I I ADP ADP 28'-0" HOOD ` ) I a
*
--�- - - - - � - - -- - - -� — -- -- - - - - -Ev r - - - - -- � - - - � CONTROL , I w
450' 450' ' 450' 450' 360- I I ^ —— —— 450' 360" H� Z
L- -I- -- .- - - - - - - - - - - - - - �I— J — VENT PLUG Z
ADP ADP ADP ►ADP
31"x21" o In
JW
—I— F_ 1 SALAMANDER r 1 °xY" REDUCER r 1 I I a+ z
ADP � � � � •� _
F F GRW GRW I— R R F F RANGE GUARD I I Q
FRYER Z
GUARD LPR LPR
38"x38" Ico
RPSM a
`o CONVECTION I PULL Q o o
6 o >- 0 36"x28" 2" GAS I STATION
m ,U m 33"x24" 36"x28" " " " " 36" - 0 YO
MIN. TO a 6 BURNER 24 x36 34 x25 x9 VALVE I �� �
;n ;r, RADIANT 6 BURNER STEAM t TA .�
EDGE OF K; o Ki o CHAR-BROILER RANGE RANGE STEAMER TILT SKILLET KETTLE (EXIST.) I CO S. CFI
HOOD ON x 4 NO-SHELF
BOTH SIDES ;a J
FLOOR
FRONT VIEW �2s� 0775y Iv
SCALE:%"=1'-O" RO \OBI
AES MANUFACTURER: COMPONENTS: NOTES: od W
00
1 RG 6 GAL RANGE GUARD - RG 2.5 GALLON x F ers to have Hi h Limit Control to shut off fuel at 425% o < oi; Jr Z==o
RANGE GUARD: _RG 1.25 GAL. �1�RG 2.5 GAL. _RG 4 GAL. �� ry 9
MAX. FLOW POINTS = 8 (8 USED) x Detectors shall be located over every piece of equipment. C, 0 N o g �
Piping Material BLACK SCH 40 ,Max. Rise _JZ_ " TOTAL PIPE VOLUME NOT TO EXCEED 139 CUBIC INCHES x The System installed as per manufacturers specs and the AHJ. ����� o<WQ� go o
RG 6.0 GAL. Supply Pipe Size 3 4 Branch Pipe Size 1 2 DROPS 3 8 MAX. PIPE LENGHT 63.4 FT. x The System has been installed as per UL300. 8o<Win ZW�-Z i,"�
" x The following functions to operate upon system discharge: �N1W ONO i==w'
RG 2.5 GAL. Supply Pipe Size 1 2 Branch Pipe Size 3 8 DROPS 3 8 RANGE GUARD - RG 6.0 GALLON * * 077O0 211�003 430W
Supply air damper closes Gas fuel shuts off in kitchen oz ",z WMW6 o=
Gas Valve Type: MECH Size 2" Manufacturer ASCO (EXISTING) MAX. FLOW POINTS = 18 (15 USED) * Exhaust fan remains on * Electric fuel shut off under hood IPH Vim= PW, WYWnW
OwnMW
TOTAL PIPE VOLUME NOT TO EXCEED 400 CUBIC INCHES * QXR5 mgHg az z
Detector Temperature Rating: 360° 450° All systems to activate simultaneously in same hazard area. �<�as �ga�a� 8�0�
MAX. PIPE LENGTH 75 FT. * Fire Alarm shall activate.
Hood Size: 28'-0" Duct Size: (2) 22"x14" x Manual Pull Station shall be located a minimum of 10 ft. from t
RG-2.5 GAL. CYLINDER #60-120002-001 hood & a maximum of 20 ft. from hood and 4 ft from floor. Q,
EQUIPMENT SURFACE NOZZLE rn
QTY. TIP#/QTY. LOCATIONS RG-6.0 GAL. CYLINDER #60-120005-001 x All fuel sources are GAS unless otherwise noted.
TYPE AREA HEIGHTS CONTROL HEAD #B120099 •may a
DUCT 2 22"x14" ADP 4 0"-6" 0"-6" IN OPENING ADP NOZZLE #87-120011-001 Z r
PLENUM 1 28'-0" ADP 4 0"-6" FROM END OF PLENUM F NOZZLE #87-120012-001 CODE REFERENCES: (TYPE 1 GREASE HOOD) o �,
FRYER 2 14"x23.5" F 2 27"-45" 45' TO 90' LPR NOZZLE #87-120022-001 (� a 0
RAD. CHAR-BR. 1 33"x24" GRW 2 24"-48" 45' TO 90' R NOZZLE #87-120014-001 THIS INSTALLATION IS IN CONFORMANCE WITH: mco
6 BURNER RANGE 1 36"x28" LPR 2 16"-20" CENTER GRW NOZZLE 87-120013-001 - NFPA 17A - 018 .0
# - NFPA10 - 2018 � m
SALAMANDER 1 31"x21" ADP 1 - TOP 4" OF COMPARTMENT 360' LINK #WK-282664-000 - NYS MECHANICAL CODE 506,507,508 V �I
" " 450' LINK #WK-282663-000 - ASTM E2336 - 2016 .� a N
6 BURNER RANGE 1 36'x2$ R 2 20"-42 CENTER O o
LINK HOUSING #804548 - THE BUILDING AND FIRE CODES OF NEW YORK STATE - 2020, Y Q
TILT SKILLET 1 34"x25" F 2 27.5"-46" FRONT EDGE AIM CENTER V r,
MANUAL RELEASE #B875572 Lo
M
2" GAS VALVE #6120075 MUM RA a o o
A FIRE EXTINGUISHER WITH A MINI TING C rn
OF CLASS K MUST BE INSTALLED WITHIN THE �V
VICINITY OF THE COOKING AREA. a