HomeMy WebLinkAbout50466-z Page 1 of 2 32 SS �s Current 02/13/2024 �Jj Renewables Element Energy LLC Engineering 7470 Sound Avenue, Mattituck, NY, 11952 Subject: Structural Certification for Installation of Residential Solar Job: Kabakov Residence Project Address: 1735 Park Avenue, Mattituck, NY, 11952 Attn.: To Whom It May Concern Observation of the condition of the existing framing system was performed by an audit team of Element Energy LLC. After review of the field observation data, structural capacity calculations were performed in accordance with applicable building codes to determine adequacy of the existing roof framing supporting the proposed panel layout. Please see full Structural Calculations report for details regarding calculations performed and limits of scope of work and liability. The design criteria and structural adequacy are summarized below: Design Criteria Code: 2020 NYSBC, IBC 2018, IEBC 2018, ASCE 7-16 Ult Wind Speed: 128.0 mph Ground Snow: 25.0 psf Min Snow Roof: N/A Exp:09/30/2025 ��-OF NEW J, A. Q'p.F Current Renewables Engineering Inc. Professional Engineer info@currentrenewableseng.com ti SFOA 106-7 F �1P Signed on:02/13/2024 1760 Chicago Ave Ste J13, Riverside, CA 92507 (951)405-1733 info@currentrenewablesenq.com Page 2 of 2.. Summaries: Check 1 : Shingle roofing supported by 2x8 Rafter @ 16 in. OC spacing. The roof is sloped at approximately 43 degrees and has a max beam span of 13.0 ft between supports. Roof is adequate to support the imposed loads. Therefore, no structural upgrades are required. 1760 Chicaqo Ave Ste J13, Riverside, CA 92507 (951)405-1733 info@currentrenewablesenq.com ROOF MOUNT SOLAR PERMIT PACKAGE CODE INFORMATION THE INSTALLATION OF SOLAR ARRAYS AND PHOTOVOLTAIC E p n I LI /` K A p /` KO`/ POWER SYSTEMS SHALL COMPLY WITH THE FOLLOWING CODES: 2020 NEW YORK STATE BUILDING CODE w �' 2020 NEW YORK STATE FIRE CODE 12. 150KW DC GRID TIED PHOTOVOLTAIC SYSTEM 2020 NEW YORK STATE BUILDING CODE f 1735 PARK AVE, MATTITUCK, NY 11952 2020 NEW YORK STATE RESIDENTIALCODE `t, ?1 MAR 2 1 2024 2020 NEW YORK STATE MECHANICAL CODE .� =-•i 2020 NEW YORK STATE PLUMBING CODE 2020 NEW YORK STATE FUEL&GAS CODE 2020 NEW YORK STATE ENERGY CONSERVATION CODE '..: BUILDING INFORMATION 2017 NATIONAL ELECTRICAL CODE(NEC) THESE DRAWINGS ARE SUBJECT TO COPYRIGHT PROTECTION BY US LAW. ORM IS 2 STORY HOUSE SINGLE FAMILY RESIDENCE SMOKE AND CARBON MONOXIDE ALARMS : YES EXPRESSLY ORBIDDEN IN WITHOUT - EXPRESSLY FORBIDDEN WITHOUT PRIOR CONSTRUCTION TYPE:V-B OCCUPANCY:R3/U AUTOMATIC FIRE SPRINKLER SYSTEM NO R II TE BLESENGILFROMG INC. AHJ :TOWN OF SOUTHOLD ROORCOMP SHINGLE APN:1000123000200030000 PV SYSTEM SUMMARY: WIND SPEED 128 Current SYSTEM SIZE(DC) STC:405 x 30= 12.150KW DC SNOW LOAD 25 Rene-wables PTC: 381.37 x 30=11.4411KW DC EXPOSURE CATEGORY D Engineering SYSTEM SIZE(AC) 8.700KW AC @ 240V CURRENT RENEWABLES MODULES (30)HANWHA Q CELL:Q.PEAK DUO BLK ML-G10+405 Of NEW y ENGINEERING INC. (�OOc Rj A• �q O^� 1760 CIVERSI ECE SUITE -J 4 /�+ J-13,RIVERSIDE CA 92507 PHONE(951)405-1733 MICRO-INVERTERS ENPHASE: IQ8PLUS-72-2-US * * AERIAL VIEW VICINITY VIEW INWW.CRENG.CD MICRO-INVERTERS CITY 30 E:: W TILT 43°,43°,43°,43° CONTRACTOR INFO AZIMUTH 78°,258°, 168°, 168° ��`� 105793 ROOF COMP SHINGLE AR�F 'SSIONP� RAFTER/TRUSS SIZE 2"X8" RAFTER @ 16"O.C. 61 ExpATTACHMENT TYPE QUICKBOLT 17667SS WITH IRONRIDGE XR-100 RAIL AM D 0211420 E2SY55 STAMPED 02/14/2024 EXISTING 200 AMPS MSP WITH 200 AMPS MAIN _ s SOUN MAIN SERVICE PANEL 7470 AVENUE,MATTITUCK, BREAKER ON TOP FED INTERCONNECTION LINE SIDE TAP _�-r's' NEW 31)7791953 com OCPD RATING 50 AMPS ( (,r`� Licence- 689 (MASTER ELECTRICIAN) Licence-HI-67461 UTILITY PSEGLI (SUFFOLK HOME IMPROVEMENT) GENERAL NOTES: Solar Individual 1. LOCAL UTILITY PROVIDER SHALL BE NOTIFIED PRIOR TO USE AND ACTIVATION OF ANY SOLAR PHOTOVOLTAIC INSTALLATION Permit Package • - - 2. THIS PROJECT SHALL COMPLY WITH LOCAL ORDINANCES- 3. PROPER ACCESS AND WORKING CLEARANCE WILL BE PROVIDED SHEET INDEX EM I LIA KABAKOV 4. ALL ELECTRICAL WORK SHOWN ON THESE PLANS WILL BE COMPLETED BY THE UNDERSIGNED 5. ALL APPLICABLE PV EQUIPMENT LISTED AND COMPLIANT WITH UL2703,UL1741 AND UL1703 PV-1.0 COVER PAGE 6. ALL ROOF PENETRATIONS TO BE SEALED WITH A HIGH PERFORMANCE ROOF SEALANT SUCH AS GeoCel 2300 CLEAR SEALANT 12.15OKW Grid Tied 7. THE SYSTEM WILL NOT BE INTERCONNECTED UNTIL APPROVAL FROM THE LOCAL JURISDICTION AND THE UTILITY IS OBTAINED PV-2.0 SITE PLAN Photovoltaic System 8. THE SOLAR PHOTOVOLTAIC INSTALLATION SHALL NOT OBSTRUCT ANY PLUMBING,MECHANICAL,OR BUILDING ROOF VENTS- 9. IF THE EXISTING MAIN PANEL DOES NOT HAVE VERIFIABLE GROUNDING ELECTRODE,IT IS THE NECESSARY TO INSTALL A SUPPLEMENTAL PV-2.1 ROOF PLAN GROUNDING ELECTRODE• PV-3.0 STRUCTURAL 1735 PARK AVE, 10. EACH MODULE WILL BE GROUNDED UL 2703 OR UL 1703 APPROVED USING THE SUPPLIED CONNECTION POINTS IDENTIFIED ON THE MATTITUCK,NY 11952 MODULE AND THE MANUFACTURER'S INSTALLATION INSTRUCTIONS'• PV-4.0 ELECTRICAL 3LD 11. A LADDER SHALL BE IN PLACE FOR THE INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS Rev Description Date 12. MAX HEIGHT OF MODULES OFF OF ROOF FACE:<6". PV-5.0 ELECTRICAL SLD A INITIAL DESIGN 1 2/1 412 0 2 4 13. PHOTOVOLTAIC SYSTEM WILL COMPLY WITH 2O17 NEC.- PV-6.0 BOMVI 14. PHOTOVOLTAIC SYSTEM INVERTER IS UNGROUNDED.NO CONDUCTORS ARE SOLIDLY GROUNDED IN THE INVERTER,AND SYSTEM COMPLIES WITH 690.35.• PV-7.0 SIGNAGE OPPORTUNITY EMILIAKABAKOV 15. MODULES CONFORM TO AND ARE LISTED UNDER UL 1703. 16. INVERTER CONFORMS TO AND IS LISTED UNDER UL 1741.• PV-7.1 PLACARD PROJECT# 8623 17. ELECTRICAL EQUIPMENT AND MATERIAL TO BE LISTED,LABELED,AND INSTALLED PER THE NEC,THE INSTALLATION PV-8,0 MICROINVERTER CHART DATE DRAWN 2/1412024 STANDARDS/MANUFACTURER'S RECOMMENDATIONS AND IF REQUIRED A RECOGNIZED ELECTRICAL TESTING LABORATORY. 18. CONDUITS EXPOSED TO SUNLIGHT ON ROOF SHALL BE LOCATED NOT LESS THAN 7/8"ABOVE ROOF SURFACE. PV-9.0 SAFETY PLAN DRAWN BY E.R 19. IN EXPOSED LOCATIONS,WIRING AND CABLING SHALL BE IN CONDUIT OR CABLE SHALL BE RATED FOR EXPOSURE;TYPE NM CABLE SHEET# PV-1.0 ALLOWED IN PROTECTED LOCATIONS.WITHIN ATTIC SPACES,ALLOWED TO RUN TYPE NM(ROMEX)10/3 OR 1213 CONDUCTORS THROUGH PV-10.0 SAFETY PLAN TITLE OPEN SPACE OR TYPE THHN IN MINIMUM 3/4"ALUMINUM CONDUIT PV-11.0+ SPEC. SHEETS 20. MATERIALS,EQUIPMENTAND INSTALLATION SHALL COMPLY WITH THE REQUIREMENTS,STANDARDS,RULES AND REGULATIONS OF THE COVER PAGE FOLLOWING AND BE MOST SUITABLE TO THE PURPOSE INTENDED: NOTR324.6.1 PATHWAYS: WIND SPEED 128 LEGEND NOT LESS THAN TWO MINIMUM 36-INCH WIDE PATHWAYS ON SEPARATE ROOF PLANES, SNOW LOAD 25 ENLARGE VIEW /FROM LOWEST ROOF EDGE TO RIDGE,SHALL BE PROVIDED ON ALL BUILDINGS. EXPOSURE CATEGORY D AT LEAST ONE PATHWAY SHALL BE PROVIDED ON THE STREET OR �OF NEw L UM UTILITY METER DRIVEWAY SIDE OF THE ROOF.FOR EACH ROOF PLANE WITH A PHOTOVOLTAIC ARRAY,A MINIMUM 36 INCH-WIDE PATHWAY FROM THE LOWEST ROOF EDGE TOR RIDGE �� 00�'Rj A C�� �� MSP MAIN SERVICE PANEL SHALL BE PROVIDED ON THE SAME ROOF PLANE OR STRADDLING THE SAME AND ADJACENT ROOF PLANES.PATHWAYS SHALL BE AC DISCONNECT OVER AREAS CAPABLE OF SUPPORTING FIRE FIGHTERS ACCESSING THE ROOF.PATHWAYS SHALL BE LOCATED IN AREAS rEAJ WITH MINIMAL OBSTRUCTIONS SUCH AS VENT PIPES,CONDUIT,OR n c❑ COMBINER MECHANICAL EQUIPMENT. PROPERTY LINE C' 106793 R324.6.2 SETBACK AT RIDGE: MODULE FOR PHOTOVOLTAIC ARRAYS OCCUPYING NOT MORE THAN 33 100, PERCENT OF THE PLAN VIEW TOTAL ROOF AREA,NOT LESS THAN I I ESsv AN 18 INCH CLEAR SET BACK IS REQUIRED ON BOTH SIDES OF A 7 O ROOF OBSTRUCTIONS THESE DRAWINGS ARE SUBJECT TO HORIZONTAL RIDGE. I _ EXp:9/30/2025 COPYRIGHT PROTECTION BY US LAW. FOR PHOTOVOLTAIC ARRAYS OCCUPYING MORE THAN 33 1 REPRODUCTION IN ANY FORM IS PERCENT OF THE PLAN VIEW TOTAL ROOF AREA,NOT LESS THAN A { STAMPED 0 211 4/2 0 2 4 ROOF ACCESS POINT EXPRESSLY FORBIDDEN WITHOUT PRIOR 36-INCH CLEAR SET BACK IS REQUIRED ON BOTH SIDES OF A (, WRITTEN APPROVAL FROM CURRENT HORIZONTAL RIDGE. c 102'-5" ,I l RENEWABLES ENGINEERING INC. R324.6.4 EMERGENCY ESCAPE AND RESCUE OPENING:PANELS If ROOF OBSTRUCTION AND MODULES INSTALLED ON DWELLINGS SHALL NOT BE PLACED u I THE PORTION OF A ROOF THAT IS BELOW AN EMERGENCY ESCAPE SHED Current AND RESCUE OPENING.A 36-INCH-WIDE PATHWAY SHALL BE PROVIDED TO THE EMERGENCY ESCAPE AND RESCUE OPENING. Ie {' Renewables A -PATHWAY ON STREET i POOL Engineering OR DRIVEWAY SIDE OF ROOF j ;: ;? Ij PATIO 36"ROOF g ACCESS POINT B -FIRE ACCESS POINT lL y CURRENT RENEWABLES (E)MAIN ENGINEERING INC. (E) UTILITY SERVICE PANEL 1760CHICAGOAVESUITE 36"ACCESS PATHWAYS W/Eml � I METER PHONE: FENCE/GATE `, ' " p p p I� PHONE:(ENG.05-1733 1 WNNV.CRENG.CO 18"ACCESS PATHWAYS , O O 0 (N)AC UM MSP I {� DISCONNECT AC NOTES: 1. MINOR FIELD ADJUSTMENTS ALLOWED BASED .';31't. _14-, CONTRACTOR INFO ON ACTUAL SITE CONDITION AND N I FENCE/ MEASUREMENTS. I ''' I GATE (N)COMBINER 2. THE 30 SECOND SHUTDOWN REQUIREMENT IS INCORPORATED INTO THE 2017 NEC AND UL STANDARD 1741. `n 3. EXISTING ROOF VENT SHOULD NOT BE I I " C25Y59 COVERED. I I ELEMENT ENERGY LLC. 7470 SOUND AVENUE,MATTITUCK, I . I NEW YORK,11952 q.. , PH:(631)779 7993 services@e2sys.com DRIVEWAY 113'-3" I (MLASTER E ECTRICIAN) I ''. ��.•... I Licence-HI-67461 (SUFFOLK HOME IMPROVEMENT) ROOF LINE Solar Individual } Permit Package EMILIA KABAKOV 12.150KW Grid Tied Photovoltaic System 100, I 36" ROOF PROPERTY LINE ACCESS POINT 1735 PARK AVE, MATTITUCK,NY 11952 Rev Description I Date A INITIAL DESIGN 2/14/2024 PARK AVE OPPORTUNITY EMILIA KABAKOV PROJECT# 8623 PARK AVE DATE DRAWN 2114/2024 S I T E P LA N DRAWN BY PV- 1 ISHEET* PV-2.0 TITLE SCALE: 3/128" = 1'-0" SITE PLAN ARRAY AREA LEGEND EAVETO ROOF ROOF TOTAL ROOF ROOFTYP2 AZIMUTH #OF RIDGE ARRAY AREA AREA AREA MODULES DIMENSION AREA SION (Sq.Ft.) (Sq.Ft.) COVERED COVERED( uM UTILITY METER #1 COMP SHINGLE 78 4 11 84.56 2002 4.22 #2 COMP SHINGLE 258 1 13 1 11 274.82 2002 1 13.73 1 3168 MSP MAIN SERVICE PANEL #3 COMP SHINGLE 168 6 1 11 126.84 2002 6.34 #4 COMP SHINGLE 168 7 11 147.98 2002 7.39 c AC DISCONNECT COMBINER MODULE OROOF OBSTRUCTIONS THESE DRAWINGS ARE SUBJECT TO COPYRIGHT PROTECTION BY US LAW. REPRODUCTION IN ANY FORM IS EXPRESSLY FORBIDDEN WITHOUT PRIOR WRITTEN APPROVAL FROM CURRENT RENEWABLES ENGINEERING INC. OF NEyy yo (E)MAIN SERVICE PANEL RI A. Current `� oe� l4� �� Renewa tiles F * Engineering (E) UTILITY METER UM MSP CURRENT RENEWABLES ENGINEERING INC. 1� \ (N)AC DISCONNECT AC �A 3 , 1760 CHICAGO AVE SUITE f J-13,RIVERSIDE CA 92507 FO^ 1067C9 w`3N �� PHONE:(951)-405-1733 C 1 1-6" p'��FE$JIO 1 VWJW.CRENG.CO (N) COMBINER Exp:9/30/2025 STAMPED 0 2/1 412 0 2 4 CONTRACTOR INFO (N)#30 HANWHA Q CELL:Q.PEAK DUO BLK ML-G10+405 ME n* ROOF#4 EZSYS ELEMENT ENERGY LLC. 7470 SOUND AVENUE,MATrITUCK, NEW YORK,11952 ROOF#1 PH:(631)779 7993 services@e2sys.com Licence-ME-52689 (MASTER ELECTRICIAN) ROOF#3 t_6�l Licence-HI-67461 (SUFFOLK HOME IMPROVEMENT) Solar Individual ROOF#2 STRUCTURAL NOTES : Permit Package 1.THESE PLANS ARE STAMPED FOR STRUCTURAL CODE COMPLIANCE OF THE ROOF FRAMING SUPPORTING THE EMILIA KABAKOV PROPOSED PV INSTALLATION ONLY. 2. THESE PLANS ARE NOT STAMPED FOR WATER LEAKAGE. 12.150KW Grid Tied 3. PV MODULES, RACKING, AND ATTACHMENT COMPONENTS Photovoltaic System MUST FOLLOW MANUFACTURER GUIDELINES AND REQUIREMENTS. 1735 PARK AVE, 4. PLEASE SEE THE ACCOMPANYING STRUCTURAL MATTITUCK,NY 11952 CALCULATIONS REPORT FOR ADDITIONAL INFORMATION. 5. PRIOR TO COMMENCEMENT OF WORK, THE SOLAR Rev Description Dale INSTALLER SHALL VERIFY THE ROOF FRAMING INFO BEFORE A INITIAL DESIGN 211412024 PARK AVE INSTALLATION AND NOTIFY THE E.O.R. IF THERE IS ANY INCONSISTENCY BETWEEN SITE VERIFICATION AND OPPORTUNITY EMILIA KABAKOV FOLLOWING: 2x8 RAFTERS @ 16" OC SPACING WITH MAX PROJECT# 8623 UNSUPPORTED SPAN EQUAL OR LESS THAN 13 FT. DATE DRAWN 2/1412024 R O O F P LAN DRAWN BY PV- 2 SHEET# PV-2., TITLE SCALE: 1/8" = 1'-0" ROOF PLAN ROOF ROOF ROOFING FRAMING FRAMING OC PENETRATION MAX NO' TILT TYPE ATTACHMENT TYPE TYPE SIZE SPACING PATTERN PENETRATION MAX SPACING OVERHANG ROOF 1 43 COMP SHINGLE QUICKBOLT 17667SS RAFTER 2"X8" 16" STAGGERED 48" ROOF 2 43 COMP SHINGLE QUICKBOLT 17667SS RAFTER 2"X8" 16" STAGGERED 48" ROOF 3 43 COMP SHINGLE QUICKBOLT 17667SS RAFTER 2"X8" 1611 STAGGERED 48" 24" ROOF 4 43 COMP SHINGLE QUICKBOLT 17667SS RAFTER 2"X8" 16" STAGGERED 48" THESE DRAWINGS ARE SUBJECT TO COPYRIGHT PROTECTION BY US LAW. REPRODUCTION IN ANY FORM IS EXPRESSLY FORBIDDEN WITHOUT PRIOR WRITTEN APPROVAL FROM CURRENT RENEWABLES ENGINEERING INC. Current w HANWHA Q CELL:Q.PEAK Ren�ewables DUO BLK ML-G10+405 to Engineering IRONRIDGE XR-100 RAIL CURRENT RENEWABLES WASHER 16"X 3",EPDM ENGINEERING INC. BONDED SS QUICKBOLT 17667SS 1760 CHICAGO AVE SUITE TABLE 2: PENETRATION PHONE: E:(951IDECA92507 PHONE:(951)405-1733 GUIDE FOR INSTALL WWW.CRENG.CO TWO OR MORE ROWS OF PANELS CONTRACTORINFO 3"FLASHING COMP SHINGLE CZSYS9 2"X8" RAFTER @ 16"O.C. ELEMENT ENERGY LLC. 7470 SOUND AVENUE,MATTRUCK, I I I I I I I I I I I I I I I I I I I I NEW K.11952 PH:(631)779 9 / services@e2sys.com STRUCTURAL SCREW, Licence-ME-52689�'(0)C E 16"-18x5.25" (MASTER ELECTRICIAN) Licence-HI-67461 ��oOE.Rj A. I qo 'P� (SUFFOLK HOME IMPROVEMENT) * c^ * STACKED STAGGERED FULLY STAGGERED Solar Individual Permit Package C- W ONE ROW OF PANELS 2 = EMILIA KABAKOV CFO 106793 � AiPOFfSS10NP� 12.150KW Grid Tied Exp:9/30/2025 HANWHA Q CELL:Q.PEAK Photovoltaic System DUO BILK ML-G10+405 I I I I I I I I I I I I STAMPED 02114t2024 1735 PARK AVE, MATTITUCK, NY 11952 FULLY STAGGERED STACKED/STAGGERED Rev Description I Date @16 A INITIAL DESIGN 12/14/2024 Rp��R (E)COMP SHINGLE 2 fig' *CHECK TABLE 1 FOR MAX PENETRATION SPACING AND PENETRATION PATTERN FOR EACH ARRAY. 0C. OPPORTUNITY EMILIA KABAKOV ]PROJECT# 8623 DATE DRAWN 2/14/2024 DRAWN BY E.R SHEET# PV-3.0 TITLE STRUCTURAL BACKFEED FUSE SIZING OF NEW MAX. CONTINUOUS OUTPUT 1.21A @ 240V MA/1/j ypp 36.30 X 1.25 = 45.38AMPS 50A FUSES-OK D W i L1J (E)UTILITY METER 099128 (N) ENPHASE (E)200A RATED ��A 4PANEL CTRICP� COMBINER BOX MODEL MAIN 1PH,120/ICE 40V60HZ ROFESSIONP�' NO#X2-IQ-AM1-240-4 (E)200A/2P MAIN � STAMPED02114/2024 (10)IQ8PLUS-72-2-US CELL BREAKER MICROINVERTERS MODE WIRE LESS (TOP FED) M COMMS BRANCH-1 THESE DRAWINGS ARE SUBJECT TO 10 HANWHA Q CELL:Q.PEAK N IQ GATEWAY COPYRIGHT PROTECTION BY US LAW. DUO BLK ML-G10+405 REPRODUCTION IN ANY FORM IS T EXPRESSLY FORBIDDEN WITHOUT PRIOR ----- ----1 (N)15A'� WRITTEN APPROVAL FROM CURRENT • RENEWABLES ENGINEERING INC. I (N)60A FUSED (10)IQ8PLUS-72-2-US I I I AC DISCONNECT ' MICROINVERTERS I (N)20A•/7\ I 1 SQUARE D D322NR6 • —(N)LINESIDE TAP VIA UL I I I WITH 50A FUSES, •� LISTED CONNECTOR Current BRANCH-2 (N)20A_ I I KNIFEBLADE, Renewabie5 10 HANWHA Q CELL:Q.PEAK N ' \ I I LOCKABLE,NEMA 3R, • DUO BLK ML-G10+405 T —� (N)2o./-�` I I UL LISTED Engineering I I �� TO UTILITY CURRENT RENEWABLES (10)IQ8PLUS-72-2-US ------------- I I a'fb ENGINEERING INC. MICROINVERTERS I , OVERHEAD 1760 CHICAGO AVE SUITE I (--—————— °`Ib FEED J-13,RIVERSIDE CA 92507 PHONE:(951}405-1733 BRANCH-3 t! I W✓W.CRENG.CO 10 HANWHA Q CELL:Q.PEAK N DUO BLK ML-G10+405 T r J 3-#8 AWG,THWN 3-#6 AWG,THWN j 1 -#8 EGC,THWN 1 -#8 EGC,THWN I J IN 3/4"OR LARGER PVC IN 3/4"OR LARGER PVC L——————————————— CONTRACTOR INFO CONDUIT CONDUIT 2-#12 AWG SKU:Q-12-RAW-300,THHN 1-#6 GEC,COATED COPPER _ 1 -#6 AWG, BARE COPPER GROUND FREE AIR BONDED EXISTING (E)GROUNDING ELECTRODE LIFER TIE IN CONDUCTOR #6 BARE COPPER © n MODULE MANUFACTURER Qcells E2SYS6 Q.PEAK DUO ELEMENT ENERGY LLC. MODULE MODEL BLK ML-G10+ 7470 SOUND AVENUE,MATTITUCK, 405 NEW YORK,11952 MODULE(W) 405 PH:(631)779 7993 services@e2sys.com MODULE PTC(W) 381.37 Licence-ME-52669 (MASTER ELECTRICIAN) MODULE Isc(A) 11.17 NOTE: Licence-HI-67461 MODULE Voc(V) 4S.34 1)CONDUIT AND CONDUCTORS SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS (SUFFOLK HOME IMPROVEMENT) MODULE Imp(A) 10.83 AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS. Solar Individual 2)ALL CONDUCTORS NOT UNDER ARRAY ARE TO BE IN CONDUIT MINIMUM 7/8"ABOVE ROOF WITH MODULE Vmp(V) 37.39 PROPER JUNCTION BOX AT EACH END PER 690.31A Permit Package WIRE SCHEDULE EMILIA KABAKOV STARTING ADJUSTMENT MAXIMUM STARTING TEMPERATURE 12.150KW Grid Tied AWG CURRENT FACTOR FOR ADJUSTED CURRENT RACEWAY CONDUCTOR ALLOWABLE TEMPERATURE CORRECTION Photovoltaic System EQUIPMENT WIRE LOCATION WIRE APPLIED TO MORE THAN 3 CONDUCTOR APPLIED TO # Qom' SIZE AMPA RATING (�C) CONDUCTORS IN FACTOR CONDUCTORS AMPACITY CONDUCTORS 310.15(B)(1)(16) RACEWAY 310.15(B)(2)(a) 310.15(B)(3)(a) IN RACEWAY 1735 PARK AVE, MATTITTITUCK, NY 11952 1 DC MODULE TO MICROINVERTER ROOF/FREE-AIR 2 12 30 90, 11.17 0.96 1 28.80 13.96 Rev Description Date 2 AC MICROINVERTER TO COMBINER ROOF/FREE-AIR 2 12 30 90° 12.10 0.96 1 28.80 15.13 A INITIAL DESIGN 2/14/2024 3 AC COMBINER TO AC DISCONNECT EXTERIOR WALL 3 8 55 90° 36.30 0.96 1 52.80 45.38 OPPORTUNITY EMIUA KABAKOV 4 AC AC DISCONNECT TO POI EXTERIOR WALL 3 6 75 90° 36.30 0.96 1 72.00 45.38 PROJECT# 8623 DATE DRAWN 2/1 412 0 2 4 DRAWN BY E.R SHEET# PV-4.0 TITLE ELECTRICAL 3LD BACKFEED FUSE SIZING pF NEW MAX. CONTINUOUS OUTPUT 1.21A @ 240V �Q3\ MA yO,A 36.30 X 1.25 = 45.38AMPS 50A FUSES-OK * O �0 D W m 099128 2 (E)UTILITY METER (N) ENPHASE (E)200A RATED N�OA CTRIGP� MAIN SERVICE PANEL Rp SS1pNP COMBINER BOX MODEL 1PH,120/240V 60HZ NO#X2-IQ-AM1-240-4 (E)20OA/2P MAIN STAMPED 02/14/2024 (10)IQ8PLUS-72-2-US CELL BREAKER U MICROINVERTERS WIRE LESS (TOP FED) MODEM COMMS THESE DRAWINGS ARE SUBJECT TO BRANCH-1 P COPYRIGHT PROTECTION BY US LAW. 10 HANWHA Q CELL:Q.PEAK N IQ GATEWAY REPRODUCTION IN ANY FORM IS DUO BLK ML-G10+405 • EXPRESSLY FORBIDDEN WITHOUT PRIOR WRITTEN APPROVAL FROM CURRENT N)15A. • • RENEWABLES ENGINEERING INC. .,�. (N)60A FUSED (10)IQ8PLUS-72-2-US AC DISCONNECT MICROINVERTERS (N)20A/r'\ SQUARE D D322NRB Current y� -(N)LINESIDE TAP VIA UL (N)20A WITH 50A FUSES, • • LISTED CONNECTOR BRANCH-2 :4N' �• KNIFEBLADE, �n v��b�e5 10 HANWHA Q CELL:Q.PEAK LOCKABLE,NEMA 3R, Engineering DUO BLK ML-G10+405 (N)20 e� UL LISTED TO UTILITY CURRENT RENEWABLES .�i (10)IQ8PLUS-72-2-US ENGINEERING INC.0.fb OVERHEAD 1760 CHICAGO AVE SUITE MICROINVERTERS 01 b • FEED PHo RIVERSIDE CA 732507 E BRANCH-3 WWW.CRENG.CO 10 HANWHA Q CELL:Q.PEAK"THHN DUO BLK ML-G10+405 3-#8 AWG,THWN 3-#6 AWG,THWN 1 -#8 EGC,THWN 1 -#8 EGC,THWN IN 3/4"OR LARGER PVC IN 3/4"OR LARGER PVC CONTRACTOR INFO CONDUIT CONDUIT 2-#12 AWG SKU:Q-12-RAW-30 , 1 -#6 AWG, BARE COPPER GROUND (E)GROUNDING ELECTRODE CONDUCTOR #6 BARE COPPER CZSYS6 MODULE MANUFACTURER Qcells Q.PEAK DUO ELEMENT ENERGY LLC. MODULE MODEL BLK ML-G10+ 7470 SOUND AVENUE,MATiITUCK, 405 NEWYORK,11952 PH:(631)779 7993 MODULE(W) 405 services@e2sys.com MODULE PTC(W) 381.37 Licence-ME-52689 (MASTER ELECTRICIAN) MODULE Isc(A) 11.17 NOTE: Licence-HI-67461 HOME IMPROVEMENT) MODULE Voc(V) 45.34 1)CONDUITAND CONDUCTORS SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS MODULE Imp(A) 10.83 AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS. Solar Individual 2)ALL CONDUCTORS NOT UNDER ARRAY ARE TO BE IN CONDUIT MINIMUM 7/8"ABOVE ROOF WITH Permit Package MODULE Vmp IV) 37.39 PROPER JUNCTION BOX AT EACH END PER 690.31A 9 WIRE SCHEDULE EMILIA KABAKOV STARTING ADJUSTMENT MAXIMUM STARTING TEMPERATURE 12.150KW Grid Tied AWG CURRENT FACTOR FOR ADJUSTED CURRENT Photovoltaic System RACEWAY CONDUCTOR ALLOWABLE TEMPERATURE CORRECTION EQUIPMENT WIRE LOCATION WIRE APPLIED TO MORE THAN 3 CONDUCTOR APPLIED TO # QTY. SIZE AMPAB)(1CITY RATING ('C) CONDUCTORS IN FACTOR CONDUCTORS AMPACITY CONDUCTORS 310.15(B)(16) RACEWAY 310.15(B)(2)(a) 310.15(B)(3)(a) IN RACEWAY TTIT PARK AVE, MATTITUCK, NY 11952 1 DC MODULE TO MICROINVERTER ROOF/FREE-AIR 2 12 30 90° 11.17 0.96 1 28.80 13.96 Rev Descripton I Date 2 AC MICROINVERTER TO COMBINER ROOF/FREE-AIR 2 12 30 90° 12.10 0.96 1 28.80 15.13 A INITIAL DESIGN 1 2/14/2024 3 AC COMBINER TO AC DISCONNECT EXTERIOR WALL 3 8 55 90° 36.30 0.96 1 52.80 45.38 4 AC AC DISCONNECT TO POI EXTERIOR WALL 3 6 75 90, 36.30 0.96 1 72.00 45.38 OPPORTUNITY EMIUAKABAKOV PROJECT# 8623 DATE DRAWN 2/14/2024 DRAWN BY E.R SHEET# PV-5.0 TITLE ELECTRICAL SLD MATERIAL LIST pFNE�.yy • r�P�p�E MA �pf'- r— E. � ELECTRICAL EQUIPMENTS 5� � W m Z QN• PART TYPE PART NUMBER DESCRIPTION 099128 30 MODULE Q.PEAK DUO BLK ML-G10+ 405 HANWHA Q CELL: Q.PEAK DUO BLK ML-G10+ 405 2� A CTRIGP� 30 MICROINVERTER ENPHASE IQ8PLUS-72-2-US ENPHASE ENERGY INC. ENPHASE IQ8PLUS-72-2-US ROFESSIDNP� STAMPED 02/14/2024 1 COMBINER X2-IQ-AM1-240-4 ENPHASE COMBINER BOX X2-IQ-AM1-240-4 1 FUSED AC DISCONNECT D222NRB 60A RATED 240VAC NEMA 311 UL LISTED 2 TAP CONNECTORS IPC TAP IPC INSULATION PIERCING CONNECTORS THESE DRAWINGS ARE SUBJECT TO COPYRIGHT PROTECTION BY US LAW. REPRODUCTION IN ANY FORM IS EXPRESSLY FORBIDDEN WITHOUT PRIOR WRITTEN APPROVAL FROM CURRENT RENEWABLES ENGINEERING INC. 46 Current Rlenewables Engineering CURRENT RENEWABLES ENGINEERING INC. 1760 CHICAGO AVE SUITE J-13,RIVERSIDE CA 92507 PHONE:(951"051733 WM.CRENG.CO BREAKER / FUSES QTY. PART TYPE PART NUMBER DESCRIPTION CONTRACTOR INFO 1 FUSES 50A FUSES GENERAL 50A FUSES 3 COMBINER BREAKER 20A 2-POLE BREAKER(S) GENERAL 20A 2-POLE BREAKER(S) ® 01 CZSYS6 ELEMENT ENERGY LLC. 7470 SOUND AVENUE,MATiITUCK, NEW YORK,11952 PH:(631)779 7993 services@e2sys.com Licence-ME-52689 (MASTER ELECTRICIAN) RACKING Licence-HI-67461 (SUFFOLK HOME IMPROVEMENT) QN. PART TYPE PART NUMBER DESCRIPTION Solar Individual 22 RAILS & SPLICES XR-100-168A XR100, RAIL 168" CLEAR Permit Package 2 RAILS & SPLICES XR100-BOSS-01-M1 BONDED SPLICE, XR100 EMILIA KABAKOV 80 CLAMPS & GROUNDING UFO-CL-01-Al UNIVERSAL MODULE CLAMP, CLEAR 40 CLAMPS & GROUNDING UFO-STP-32MM-M1 STOPPER SLEEVE, 32MM, MILL 12.150KW Grid Tied 10 CLAMPS & GROUNDING XR-LUG-03-Al GROUNDING LUG, LOW PROFILE Photovoltaic System 72 ATTACHMENTS 17667SS QUICKBOLT 1735 PARK AVE, MATTITUCK,NY 11952 Rev Description Date A INITIAL DESIGN 2/1 412 0 2 4 OPPORTUNITY EMILIA KABAKOV PROJECT# 8623 DATE DRAWN 211 412 02 4 DRAWN BY ER SHEET# PV-6.0 TITLE BOM OF NEIV P OQE MAIV,iQ9 O CO �� CG LU 099128 Z M 2 EQUIPPED PHOTOVOLTAIC■ � ■ � SHUTI•WN N�OA�O CTR1ONP FESS STAMPED 02H4/2024 690.12 THESE DRAWINGS ARE SUBJECT TO COPYRIGHT PROTECTION BY US LAW. REPRODUCTION IN ANY FORM IS — EXPRESSLY FORBIDDEN WITHOUT PRIOR WRITTEN APPROVAL FROM TURN RAPID PV SYSTEM ` , • RENEWABLES ENGINEERING NC.ENT SHUTDOWN SWITCH TO RATED AC OUTPUT CURRENTAMPS THE "OFF" POSITION TO AC • ■ •■ ■ ` • ' 1 • Current SHUT DOWN PV SYSTEM 690.14,690.15,690.54 16Renewables AND REDUCE SHOCK _ Engineering HAZARD IN THE ARRAY "WA�I.I CURRENT RENEWABLES 'Y' A POWER kURCES ENGINEERING INC. 690.56(C)(1)(B) 1760 CHICAGO AVE SUITE SECOND SOURCE PHOTO- • • VOLTAIC SYSTEM J-13,RIVERSIDE CA 92507 RATED / / OUTPUT ■ CURRENT ■ • ' AMPS ■ PHONE:(951HO5-1733 WAW.CRENG.CO AC NORMAL OPERATING VOLTAGE - 240 VOLTS 690.54 CONTRACTOR INFO — — OPTIONAL SOLAR LOAD CENTER ARRAY EZSYS9 ELEMENT ENERGY LLC. �/0 7470 SOUND AVENUE,MATTRUCK, NEW YORK,11952 PH:(631)779 7993 services@e2sys.com _ Licence-ME-52689 =mom• L _ (MASTER ELECTRICIAN) ■ ■ OUTPUT ■ • • (SUFFOLK HOME IMPROVEMENT) • NOT • . I I NEC 690.31(G)(3)&(4),CRC R324.7 Solar Individual • ■ ■ Permit Package ENT DEVICE • _ (UNLESS BUSBAR IS FULLY RATED) L - EMILIA KABAKOV 705.12(D)(2) PHOTOVOLTAIC POWER SOURCE 12.150KW Grid Tied EVERY 10'ON CONDUIT AND ENCLOSURES Photovoltaic System NOTES: 1735 PARK AVE, 1. NEC ARTICLES 690 AND 705 AND NEC SECTION R324 MARKINGS MATTITUCK, NY 11952 SHOWN HEREON. Rev Description Date 2. ALL MARKING SHALL CONSIST OF THE FOLLOWING: A INITIAL DESIGN 2/1 412 0 2 4 A. UV RESISTANT SIGN MATERIAL WITH ENGRAVED OR MACHINE PRINTED LETTERS OR ELECTRO-PLATING. B. RED BACKGROUND COLOR WHITE TEXT AND LINE OPPORTUNITY EMILIA KABAKOV WORK. PROJECT# 9623 C. AERIAL FONT. DATE DRAWN 2/14/2024 3. ALL SIGNS SHALL BE SIZED APPROPRIATELY AND PLACED IN DRAWN BY E.R THE LOCATIONS SPECIFIED.SIGNAGE CANNOT BE SHEET# PV-7.0 HAND-WRITTEN. TITLE 4. SIGNS SHALL BE ATTACHED TO THE SERVICE EQUIPMENT WITH SIGNAGE POP-RIVETS OR SCREWS. 4.OF NE�,� CO OBE MA/1/jp_ O'S� * 4U E; _ r � D W � _ 099128 Z BOA CTRIGP� Ro Ss1oNP� STAMPED 02/14/2024 CAUTION REMOTELY LOCATED DISCONNECT SWITCH AND METER THESE DRAWINGS ARE SUBJECT TO COPYRIGHT PROTECTION BY US LAW. REPRODUCTION IN ANY FORM IS EXPRESSLY FORBIDDEN WITHOUT PRIOR WRITTEN APPROVAL FROM CURRENT RENEWABLES ENGINEERING INC. Current Renewables Engineering LU CURRENT RENEWABLES Q ENGINEERING INC. Y 1760 CHICAGO AVE SUITE J-13,RIVERSIDE CA 92507 Q PHONE:(951)-405-1733 CL W WW.CRENG.CO F_ CONTRACTOR WO PV ARRAY CZSYS6. ELEMENT ENERGY LLC. 7470 SOUND AVENUE,MATTITUCK, NEW YORK,11952 PH:(631)779 7993 services@e2sys.com Licence-ME-52689 MAIN SERVICE PANEL (MASTER ELECTRICIAN) Licence-HI-67461 (SUFFOLK HOME IMPROVEMENT) COMBINER Solar Individual AC DISCONNECT UTILITY METER Permit Package LLIPHOTOVOLTAIC BACK-FED CIRCUIT BREAKER IN MAIN ELECTRICAL EMILIA KABAKOV PANEL IS AC DISCONNECT PER NEC690.17 12.150KW Grid Tied Photovoltaic System 1735 PARK AVE, MATTITUCK,NY 11952 Rev Description Date A INITIAL DESIGN 2/14/2024 OPPORTUNITY EMILIA KABAKOV PROJECT# 8623 DATE DRAWN 2/14/2024 DRAWN BY E.R SHEET# PV-7.1 TITLE PLACARD 1•-10 ' 11 -20 21 -30 31 -40 41 -50 51 -60 M ICROI NVERTER CHART 1 2 THESE DRAWINGS ARE SUBJECT TO COPYRIGHT PROTECTION BY US LAW. REPRODUCTION IN ANY FORM IS EXPRESSLY FORBIDDEN WITHOUT PRIOR WRITTEN APPROVAL FROM CURRENT RENEWABLES ENGINEERING INC. 3 Current UM MSP Rene awes AC Engineering CURRENT RENEWABLES 4 ENGINEERING INC. 1760 CHICAGO AVE SUITE J-13,RIVERSIDE CA 92507 PHONE:(951)-405-1733 WNW.CRENG.CO 5 CONTRACTORINFO Ann* EZSYS6 6 ELEMENT ENERGY LLC. 7470 SOUND AVENUE,MATrITUCK, NEW YORK,11952 PH:(631)779 7993 services@e2sys.com Licence-ME-52689 (MASTER ELECTRICIAN) Licence-HI-67461 (SUFFOLK HOME IMPROVEMENT) 7 Solar Individual Permit Package EMILIA KABAKOV 8 12.150KW Grid Tied Photovoltaic System 1735 PARK AVE, MATTITUCK,NY 11952 Rev Description Date 9 A INITIAL DESIGN 2/1 412 0 2 4 OPPORTUNITY EMILIA KABAKOV PROJECT# 8623 DATE DRAWN 2/1 412 02 4 DRAWN BY E.R 10 SHEET# PV-8.0 TITLE MICROINVERTER CHART SAFETY PLAN MARK UP KEY INSTRUCTIONS: UM UTILITY METER THESE DRAWINGS ARE SUBJECT TO COPYRIGHT PROTECTION BY US LAW. 1. USE SYMBOLS IN KEY TO MARK UP THIS SHEET. REPRODUCTION IN ANY FORM IS MSP MAIN SERVICE PANEL EXPRESSLY FORBIDDEN WITHOUT PRIOR 2.SAFETY PLAN MUST BE MARKED BEFORE JOB WRITTEN APPROVAL FROM CURRENT STARTS AS PART OF THE PRE-PLAN RENEWABLES ENGINEERING INC. 3. DOCUMENT ALL ADDITIONAL HAZARDS ON THIS PAGE �c AC DISCONNECT &MAKE NOTES ON THE JHA SHEET c❑ COMBINER Current IN CASE OF EMERGENCY O Rene Wables P PERMANENT ANCHOR NEAREST HOSPITAL OR OCCUPATIONAUINDUSTRIAL CLINIC MSP Engineering O TEMPORARY ANCHOR 46 NAME: AC CURRENT RENEWABLES C IL NEENG INC. INSTALLER LADDER 176o HICAGO AVE SUITE J-13,RIVERSIDE CA 92507 ADDRESS: PHONE:(951HO5-1733 S❑ STUB-OUT NNWV.CRENG.CO SAFETY COACH CONTACT INFORMATION NAME: ® SKYLIGHT ADDRESS: NO LADDER ACCESS (STEEP GRADE CONTRACTOR INFO 0 OR GROUND LEVEL OBSTRUCTIONS) ALL EMPLOYEES ON SITE SHALL BE MADE AWARE OF THE RESTRICTED ACCESS SAFETY PLAN AND SIGN INDICATING THAT THEY ARE im w r*1 AWARE OF THE HAZARDS ON-SITE AND THE PLAN FOR CONDUIT EZSYS9 WORKING SAFELY. GAs GAS SHUT OFF NAME SIGNATURE 7470 SOUND AVENUE,MATTRUCK, zo WATER SHUT OFF NEWYORK,11952 PH:(631)779 7993 O services@e2sys.com DROP Licence--ME-52689E-589 (MASTER ELECTRICIAN) OLicence-HI-67461 POWER LINES (SUFFOLK HOME IMPROVEMENT) Solar Individual Permit Package EMILIA KABAKOV 12.150KW Grid Tied Photovoltaic System 1735 PARK AVE, MATTITUCK, NY 11952 Rev Description I Dale A INITIAL DESIGN 1 2/14/2024 DATE: TIME: OPPORTUNITY EMILIAKABAKOV PROJECT# 9623 DATE DRAWN 2/14/2024 DRAWN BY E.R SHEET# PV-9.0 TITLE SAFETY PLAN JOB HAZARD ANALYSIS Crew leader to fill out all sections below, hold a pre-job safety meeting with all personnel, and upload this completed document and the Safety Plan to Site Capture Ladder Access Public Protection Weather and Environment Restroom facilities Ladders must be inspected before each use. 0 The safety of the Client and the Public must be maintained at all 0 The site supervisor shall forecast the weather conditions at the 0 Employees shall have access to restroom facilities with Extension ladders must be set up on a firm and level surface at times. job site,prior to crew arrival,in order to mitigate any hazards hand-washing stations.Use of onsite restroom is at the client's a 4-to-1 rise to run angle(or 75 degrees)and the top must be • The Client and the Public shall be prevented from entering the associated with inclement weather(heat,cold,wind,rain,etc.) discretion(location is annotated below).If client does not give THESE DRAWINGS ARE SUBJECT TO secured to the structure.Extension style ladders placed on work zone through the use of barriers and/or signage,as • The site supervisor will utilized a portable wind meter permission,location of suitable restroom facilities with COPYRIGHT PROTECTION BY US LAW. uneven;loose or slippery surfaces must additional) have the required. anemometer to verify actual onsite wind conditions,b hand-washing stations offsite will be provided.The onsite REPRODUCTION IN ANY FORM IS PP rY Y q (anemometer) fY Y 9 P EXPRESSLY FORBIDDEN WITHOUT PRIOR base firmly anchored or lashed so the base will not slip out. 0 Company,Client and Public property shall be protect from checking at the ground and on any elevated work surface(ex, supervisor will identify location and make arrangements to WRITTEN APPROVAL FROM CURRENT • Extension ladders must be used with walk-through devices or falling objects. rooftop)prior to work start,at midday and prior to solar panel ensure all employees have access at any point. RENEWABLES ENGINEERING INC. the ladder must extend 36"above the stepping off point. Pets(including dogs)shall be secured by their owners prior to staging on a roof. 9 Restroom facilities will be circle one):Onsite-Offsite • A-frame ladders must only be climbed with the ladder spreader work start. • Elevated work involving the moving or maneuvering of solar If Offsite,add location name and address: bars locked in the open position;A-frame ladders shall not be 0 The client should not leave pets,family members,or others in panels shall cease at 25mph(sustained wind)until wind Current climbed while in the closed position(ex,closed and used while the charge or care of Employees,Contractors,or Temporary subsides. Incident Reporting Procedure C C leaned against a structure). Workers. Forecasted weather maximum temp(degrees F): arle nt Contact your Site Supervisor les • Additional notes: 0 Crew leader responsible for communication with the client: Engineering Name: Mobile Equipment Client and public is excluded from work area by barricades(N/A, • Only Qualified operators Will operate equipment;operators must Yes,No): Heat Related Illness Prevention Phone: CURRENT RENEWABLES maintain a certification on their person for the equipment being Employees shall have access to potable drinking water that is ENGINEERING INC. 1760 CHICAGO AVE SUITE operated. Training and Pre-Job Safety Briefing fresh,pure,and suitably cool.The water shall be located as • Contact your Manager J-13,RIVERSIDE CA 92507 • Type(s)of mobile equipment(Type/Make/Model): All employees onsite shall be made aware of the specific close as practicable to the areas where employees are working. PHONE:(951)-405-1733 hazards of this project and review this HJA during a pre-job Water shall be supplied in sufficient quantity at the beginning of Name: WWW.CRENG.CO • Qualified operator(s): briefing,and their signature indicates awareness of site the work shift to provide at least one quart per employee per conditions and the plan to eliminate any hazards identified prior hour for drinking for the entire shift.Employees may begin the Phone: Material Handling and Storage to and during the project. shift with smaller quantities of water if they identify the location • Materials will be staged/stored in a way that does not present a and have effective means for replenishment during the shift to 0 Contact your Site Supervisor CONTRACTOR INFO hazard to client,personnel or public.Materials stored on the Crew leader(name/title): allow employees to drink on quart or more per hour.The roof will be physically protect from failing or sliding off. I frequent drinking of water shall be encouraged. Name: • Crew member(name/title): Shade shall be present when temperature exceeds 80 degrees Fall Protection Fahrenheit.When the outdoor temperature in the work exceeds Phone: • A site-specific plan for fall prevention and protection is required With:Crew member(name/title): 80 degrees Fahrenheit,employees shall have and maintain one C�SYS prior to starting work and must remain onsite at all times until or more areas with shade at all times. Your full name,phone number,office location,brief description 6 work is complete;a fall rescue plan must be outlined and Crew member(name/title): New employees must be acclimatized.New employees will be of what happen and when. discussed among the crew prior to work start. r monitored by their Crew Leader(site supervisor)for the first two ELEMENT ENERGY LLC. • First-person-Up(FPU)must install their anchor and connect • Crew member(name/title): (2)weeks of employment or longer when necessary. NOTE ADDITIONAL HAZARDS NOT ADDRESSED ABOVE 7470 SOUND AVENUE,MATrrrUCK, before an other task,including installing other anchors.The Employees will be allowed and encouraged to implement add as man as necessary b using additional sheets NEW YORK.11952 Y g g9 P ( Y rY Y g ) PH:(631)779 7993 Last-Person-Down(LPD)must be the only person on a roof Crew member(name/title): scheduled breaks during each shift.Employees must take services@e2sys.com uninstalling fall protection. cool-down breaks in the shade any time they feel the need to do Licence-ME-52689 • FPCP(name and title): Airborne Contaminants: so to protect them from overheating.Supervisors are (MASTER ELECTRICIAN) Asbestos-containing(Transite)piping(ACP)-Do not disturb REQUIRED to allow employees any break period they need Define the Hazard: Method/steps to prevent incident: Licence-HI-67461(SUFFOLK HOME IMPROVEMENT) FPU and LPD(name and title): (move,drill,cut fracture,etc.) during high heat conditions. • Asbestos-containing thermal insulation(ACI)and 0 Cool Vests are encouraged for all employees at all times during Solar Individual Electrical Safety Asbestos-containing duct wrapping(ACW)-do not disturb,no periods of high heat. Permit Package The Electrical Qualified Person(EQP)is required onsite to attic or crawlspace access is allowed if work to be performed Identify the location of the closet Occupational/Industrial Clinic Define the Hazard: Method/steps to prevent incident: perform electrical work. could cause exposure to personnel,client or public. or Hospital in case a crew member becomes ill. • All electrical work Will be performed with equipment in an EMILIA KABAKOV electrically safe condition(de-energized)unless approval has 0 If yes,list specific tasks and protection in place: What is the specific plan to provide and replenish sufficient water for been granted prior to work. all employees on site? 12.15OKW Grid Tied • Service drops and overhead electrical hazards will be 0 If offsite replenish is necessary,where will you go to replenish Define the Hazard: Method/steps to prevent incident: indentified and protected from contact,as neccessa water(location/address): Photovoltaic System • EQP(name and tile): • Who will replenish the drinking water(name): 1735 PARK AVE, MATTITUCK,NY 11952 Define the Hazard: Method/steps to prevent incident: Rev Description I Date A INITIAL DESIGN 1 2/14/2024 OPPORTUNITY EMILIA KABAKOV PROJECT# 9623 DATE DRAWN 211 412 02 4 DRAWN BY E.R SHEET# PV-10.0 TITLE SAFETY PLAN O.PEAK DUO BLK 01PEAK DUO BLK ML-G10+ SERIES t ■Mechanical Specification ML G 10+ SERIES Qee'Is Fp°°� 74.0in•41.10 mm x x 3ncutling frame) (1879 runt x 7045 runt 32 runt) Weight 48.51bs P20kg) t Front Cover 0.13 In(32 mm)thermally pre-stressed glass �• �•4�asoal 385-410 Wp 1132 Cells Back Cover with anti-rettection technology_ 'e$.a THESE DRAWINGS ARE SUBJECT TO _ posnefilm _ tZ COPYRIGHT PROTECTION BY US LAW. 20.9/o Maximum Module Efficiency Frame Black anodised aluminium ESIN ANY FORM IS EXPRESSLY REPRODUCTION FORBIDDEN WITHOUT PRIOR Cell 6.22 nlonocrysta8ine OANTUM solar half cIIs _ WRITTEN APPROVAL FROM CURRENT Junction box 2.09-3.98in•126-236in x 0.59-0.71m � (53-101mm-32-60mm x 15-18mm),IP67,with bypass diodes RENEWABLES ENGINEERING INC. _ .-.-_-.. ---- .._ -`----- _-- ----.'- --_--__- - -. - - ------__ Cable 4mm2Solar cable.(+)z4921n(1250mm1(-Iz49.2 in 0250mm) Connector Staublt MC4;IP68 �-T 4sasar Current . MODEL O.PEAK DUO BILK ML-G10+ °+s-wsa T - - - - --- ------ --- ---- -- - - ---- ----- - ■Electrical Charadenstics a _ -� � - yes t- e -- - - - --- - - -- - - - - - - POWERCLASS _ _ __ _ _ __385 __390 395 400 405 410n neeing MINIMUM PERFORMANCE AT STANDARD TEST CONDITIONS,STQ(POWER TOLERANCE*5 W/-O Wl Power at MW P„W [W] 385 390 395 400 405 410 Breaking the 20%efficiency barrier E sir°rcCircuit cnrrenr --- _ lc [A] -- 1104 -- tto7 - - ,uo ,Lw -ttn - n2o �,I LIII OANTUM DUO ZTechnoi with zero a cell layout E °�"9-u"V ge' V. M 4519 45.23 4527 4530 4534 4537 CURRENT RENEWABLES Technology gap y --- ENGINEERING INC. boosts module efficiency up to 20.9%. Cuvent at MPP -_ I- [A] 10.59 10.65 10.71 10.77 10.83 Y 10.89 1760 CHICAGO AVE SUITE Voltage at MPP V_ M 3636 36.62 36.88 37.13 3739 37.64 J-13,RIVERSIDE CA 92507 Efficency' rl 1%] z19.6 219.9 z20.1 z20.4 2:20A z209 PHONE:(951)-405-1733 A reliable investment WWW.CRENG.CO ER Inclusive 25-ye ar product warranty MINIMUM PERFORMANCE AT NORMAL OPERATING CONDITIONS,NMOT� p rriy and 25-year linear j4mraagr performance warranlyr. Powaat MPP P,ce rM 288.8 292.6 2963 3001 3032 307.6 E Short Chcutt Currant 4c- [A] _ Sao 8.92 B95 8.97- Roo - 9.03 E Open Groat Voltage Va M-- -4262 42.65 42.69 42-72 4276 4279 _ CONTRACTORINFO Enduring high performance f Current at MPP I_ [A] 835 B.41 BAG EL51 8.57 8.62 Voltage at MPP V_ M 34.59 34.81 35.03 3525 35.46 35.68 Long-term yield security with Anti LeTID Technology, 'Measurement tolerances P_t3%:IsS Q 35%at STC 1000 W/m�,25t2°C,AM 1.5 according to IEC 60904-3.2800 W/M�.NMOT,spectrum AM 1,5 - Antl PID Technology'and Hot-Spot Protect I Qce11s PERFORMANCE WARRANTY •T-_ _--_ - -•-PERii6lli CE AT LOW IRRADIANCE ^,/ Extreme Weather ratio `"--�mi4 -� -_---«�_- Atleast 98%ofnorrdnel power_ C25YSI J T[/ g 08 .e..,a.� Olaingfirstrac Thereaaermax Hi h-tech aluminiumallo frame,certified for xs _____________ 05%degrambonPeryear.At9 Y least 93S%ofnominal Po hi hsnow 0Pa and wind loads 4000Pa. # is ELEMENT ENERGY LLC. g (54O ) ( ) up to l0 years.At least 86%of.; Fnommalpowervpto2syears. � 7470 SOUND AVENUE.MATTITUCK,;Y- NEW YORK.11952 e'�'"a r�t,'7All data within measurement[�`-- - PH:(631)779 7993 ;•hPY•y:'�;'...r': tolerances Full wananbes in Innovative all-weather technology E ,), ,._ -y: accardancew9,mewarrrant services@e2sys.com ° Dr6.T.;-'ID}-Ka temaortneowllssalas „ Licence-ME-52689 Optimal yields,whatever the weather with excellent low-light k orgenisabon oryour respective (MASTER ELECTRICIAN) XXX and temperature behaviour. YEARS -try. aoo 18RAOIAN(2:rwan') EA -67461 6 busbar 12 busbar cell technology cell technology -smaaa,ammo°r�°,,,�.r.,,,.swc°mr»,�-m,u. T ( Licence-HIPPO �����a®°��,��°�m�q�� q SUFFOLK HOME IMPROVEMENT) tiig s potram4nmp®clym2021(Febnm 2(ol) mmpara-rmS'rCmnammep5C,10oowh� ^1 n The most thorough testing ITEMPERATURECOEFFlCIENTS- - - _- - -__ -- - - - 6 Solar Individual programme in the industry Temperature Coeffcentof1. a [%/K] +0.04 Temperature Coefficient ofVa R [%/K] -0.27 9 E Permit Package Ocells Is the first solar module manufacturer to pass the Temperature Coefficient of P� y [%/K] -034 Nominal Module Operating Temperature NMOT rF] 109t5.4 V (43±3°c) most comprehensive quality programme in the Industry.The new'Quality Controlled PV°of the independent certification d' EM I LIA KABAKOV institute TUV Rheinland. p ■Properties for System Design o Maximum System Voltage Vm M 1000(IEC)/1000(UL) PV module classification Class II Maximum Series Fuse Rating _ [A DC] 20 Fire Rating based on ANSULIL 61730 __ TYPE 2 a 12.150KW Grid Tied 'See data sheet on rear for runher information. Max.Design Load,Push/PuIP [Ibs/ftq 75(360OPa)/55(2660Pa) Permitted Module Temperature 40°F up to+185°F � 'APrtestmndhwls according to lECrt562804-120t5,memod A(-t500V,96n) Max.Test Load,Push/Pulls [Ibs/ftj 113(540o Pa)/84(4000Pa) on Continuous Dury (-40°C up to*85°CJ a Photovoltaic System 9 See installation Manual ■Qualifications and Certificates ® 1735 PARK AVE, UL 61M.CEcomplia„L s MATTITUCK,NY 11952 klualiry controlled PV-T0V Rheinland, 9 IEC 61215:2016,IEC 67T302016, Al ° US Patent No.9,893,215(velar cells). SA® hDRAWNBY scription Date \\\ * I C � AL DESIGN 2I14I2024 locus° B The ideal solution for. ,w •:ozx` o� O l7 Rooftop allays On r6vA,.un`a �'wd EMILIA KABAKOV ° ° residential buildings m"`m' r� ®� 8623 Ocells pursues minimizing paper output in consideration of the global environment. 2/14f2024 nmstamneeonmmucaanmmoe rdmea comaom taco°l�sernre ro runna'vil4,m°e4n on�p4.edlrsuamw°r tors podan Qeells E.R 0 aLS 4merlm 1r 4a05ecv,anCane,0rb.6lle%00,tMn CA92618,USAI rEL•1 JN97U 59961 EMNL hpc-mpui.�paxhmmIVRE aww°re�mmPV-11.0 TITLE MODULE SPEC ENPHASE. 1�11 IQ8 and IQ8+ Microinverters INPUT DATA Commonly used module pairings' W; - 235-350 235-440 ! To meet compatibility,PV modules must be within maximum input DC voltage and maximum module I listed below. Module compatibility - Module compatibility can be checked at https://enphase.comAnstallers/microinverters/calculator MPPT voltage range - - -V 27-37 _ - .- -- 27-45 .- --- -- THESE ARE TO NGS CT Operating range V 16-48 16 58 COPYRIGHT PIROTECTION BYEUS LAW. Minimum m/Maximustartvoltage V - 22/4.8 - 22/58 - REPRODUCTION IN ANY FORM IS _ _ EXPRESSLY FORBIDDEN WITHOUT PRIOR Maximum input DC voltage V 50 _ 60 WRITTEN APPROVAL FROM CURRENT RENEWABLES ENGINEERING INC. r. Maximum continuous input DC current A 10 12 - Maximum input DC short-circuit current A - 25 - - -Maximum module l� A 20 Current e�`ntt Overvoltage loss DC port - II Rey e d•ab1l es DC port backfeed current mA 0" - Engineering lg - PV array configuration - I I ungrounded array;no additional DC side protection required;AC side protection requires maximum 20 A per branch circuit OUTPUT DATA(AN UNITS 108-60-2-US 108PLUS-72-2-US CURRENT RENEWABLES ENGINEERING INC. Peak output power VA 245 : - 300 1760 CHICAGO AVE SUITE J-13,RIVERSIDE CA 92507 Maximum continuous output power VA 240 290 PHONE:(951)-405-1733 WA W.CRENG.CO -' - - Nominal grid voltage(L-L) V - - 240,split-phase(L-L),1 0' - - - _ IQ8 and IQ8+ Microinverters - Easy to install. - - -Minimum and Maximum grid voltages _ V- -- - -" - - -- - -- -- .211-264 Lightweight and compact with plug' Maximum continuous output current A 1.0' 121 Our newest 108 Microinverters are the industry's first microgrid-forming,software-defined acid-play connectors CONTRACTOR I N FO microinverters with split-phase power conversion capability to convert DC power to AC Nominal frequency Hz - 60 power efficient) The brain of the semiconductor-based microinverterIs our proprietary Power line communication(PLC) - P Y- P P arY - - Extended frequency range Hz 47-68 application-specific integrated circuit(ASIC),which enables the microinverter to operate in between components AC short-circuit grid-tied or off-grid modes.The chip is built using advanced 55-run technology with high-speed • Faster installation with simple two-wire Arms' 2 [Mon digital logic and has superfast response times to changing loads and grid events,alleviating cabling three cycles £ constraints on battery sizing for home energy systems. Maximum units per 20 A(L-L)branch. "1l3 - 73 _ - C SYS 6 circuit' - High'productivity and.reliability - - - -- - Produce Power even when the grid is - Total harmonic distortion % -" - -<5" _" down' Overvolt eclassAC port III ELEMENT ENERGY LLC. III _ 7470 SOUND AVENUE,MAT'T(TUCK. _ a9 i� NEW YORK,11952 t r PH:(631)779 7993 • More than one million cumulative hours AC port backfeed current i mA 30 services@e2sys.com of testing _ Licence-ME-52689 _ - Power factor setting - - - 1.0 1 + (MASTER ELECTRICIAN) t _ __ Class II double insulated enclosure - - - - - - - Grid-tied power factor(adjustable) - 0-85 leading-0.65lagging Licence-HI-67461 Part of the Enphase Energy System, I08 Series Microinverters redefine Optimized for the latest high-powered - (SUFFOLK HOME IMPROVEMENT) IQ8 Series Microinverters integrate with the reliability standards with more than one PV modules Peak efficiency 97.E IQ Battery,IQ Gateway,and the million cumulative hours of power-on CEC weighted efficiency % 97 Solar Individual Enphase App monitoring and analysis testing,enabling an industry-leading Micr rid-formin Permit Package ft soware. limited warranty of up to 25 years. g Nighttime power consumption mW - - 23 25 Compliant with the latest advanced MECHANICAL DATA grid support.. EMILIA KABAKOV Ambient temperature range - -40'C to 60'C(-40'F to 140°F) - - Remote automatic updates for the latest grid requirements Relative humidity range 4%to 100%(condensing) 12.150KW Grid Tied rr Configurable to support a wide range DC connector type MC4 Photovoltaic System of grid profiles Dimensions(H x W x D) 212 mm(8.3 in)•175 mm(6.9 in)x 302 mm 0.2 in) Connect PV modules quickly and easily I08 Series Microinverters are UL Listed Meet CA Rule 21(UL 1741-SA)and IEEE® Weight 1.08 k (2.381bs) 1735 PARK AVE, to IQB Series Microinverters using the as PV rapid shutdown equipment and 1547;2018.(UL 1741-SB 3r1 Ed.) g _ g MATTITUCK,NY 11952 included Q-DCC-2 adapter cable with conform with various regulations,when Cooling Natural convection-no fans _ plug-and-play MC4 connectors. Installed according to the manufacturer's Nam Approved for wet locations Yes Rev Description Date instructions. - - - -- - - - - - - ---- - " - - - - - -- -- - -- - -- -- --- ----- --— -- - - 2/14/2024 108 Microinverters cannot be mired with Pollution degree PD3 A INITIAL DESIGN previous generations of Enphase mlcroinverters 007 Series,1065eries,and won)in the same- Enclosure - Class ll double-insulated,corrosion-resi stant polymeric enclosure system. - - - • 10 Gateway is required to change the default Environmental category/UV exposure rating NEMA Type 6/Outdoor OPPORTUNITY EMILIA KABAKOV •Meets UL 1741 only when Installed with 10 System Controller 2 grid prof7le at the time of installation to meet PROJECT# 8623 '•108 and I08•support split-phase,240 V Installations only. ' local Authority Having Jurtsdictlon(AHJ) requirements_ DATE DRAWN 2/1 412 0 24 0 2023 Enphase Energy.All rights reserved.Enphase,the a and CC logos,l0,and certain other marks fisted at (t)Noenlorced DCVAC recta. (2)Nominal vottagerengecan be adanded beyonenormnanf required by me etnay. DRAWN BY E.R httpsJ/enphase.com/tmdemark-usage-guidelinm aretrademarks of Enphase Energy,Inc.in the US and other mumries-Data subject tochanga. lOiSP-12A-DSH-00207-2.0-EN-US-2023-10-13 (3)Lhnn mayvary.Rotor to lone requuGmerns to dannethenumberof ad=Invorterm perbranch In your area. IOBSP-I2A-DSH-00207-2.0-EN-US-2023-10-13 SHEET# PV-11.1 TITLE MICROINVERTER SPEC IQ Combiner 4/4C Data Sheet Enphase Networking MODEL NUMBER IQ Combiner 4 IQ Combiner4 with IQ Gateway printed circuit board for integrated revenue grade PV production metering(ANSI C12.20±0.5%) X-IQ-AM7-240-4 and consumption monitoring(±2.5%).Includes a silver solar shield to match the IQ Battery and IQ System Controller 2 and to i X2-IQ-AM 1-240-4(_IEEE 1547:2018) deflect heat. IQ Combiner 4C IQ Combiner 4C with IQ Gateway printed circuit board for integrated revenue grade PV production metering(ANSI C12.20±0.5%) X-IQ-AM1-240-4C and consumption monitoring(±2-5%).Includes Mobile Connect cellularmodem(CELLMODEM-M1-06-SP-05),a plug-and-play IQ Combiner 4f4C The IQ Combiner 4/4C with IQ Gateway and X2-IQ-AM7-240-4C(IEEE 1547:2018) industrial-grade cell modem for systems uplo 60 microiriverters.(Available in the US,Canada.Mexico,Puerto Pico,andthe US Virgin Islands,where there Is adequate cellular service in the installation area.)Includes a silver solar shield to match the integrated LTE-Ml cell modem (included IQ Battery and IQ System Controller and to deflect heat. THESE DRAWINGS ARE SUBJECT TO ACCESSORIES AND REPLACEMENT PARTS (not included,order separately) COPYRIGHT PROTECTION BY US LAW. only with IQ Combiner 4C)consolidates REPRODUCTION IN ANY FORM IS Supported microinverters IQ6,IQ7,and IQ8.{Do not mix IQ617 Microinverters with IQ8) - EXPRESSLY FORBIDDEN WITHOUT PRIOR interconnection equipment into a single Communications Kit - WRITTEN APPROVAL FROM CURRENT RENEWABLES ENGINEERING INC. -— -- -- enclosure_ It streamlines IQ Microinverters and COMMS-CELLMODEM-Ml-06 IncludesCOMMS-KIT-01 and CELLMODEM-M7-06-SP-05 with 5-year Sprint data plan CELLMODEM-MI-06-SP-05 -4G based LTE-M7 cellular modem with 5-year Sprint data plan - storage installations by providing a consistent, CELLMODEM-MI-06-AT-05 4G based LTE-M7 cellular modem with 5-year AT&T data plan }'Circuit Breakers Supports Eaton BR210,BR215,BR220,BR230,BR240,BR250,and BR260 circuit breakers. CUrre n l r_9 eENP=;asE pre-wired solution for residential applications. . BRK-,oA-2-2aov Circuit breaker,2 pole,lOA,Eaton BR210A&M BRK-15A-2-240V Circuit breaker,2 pole,15A,Eaton BR215 enea.bl es I' BRK-20A-2P-240V Circuit breaker,2 pole,20A,Eaton BR220 ;$ It offers up to four 2-pole input circuits and BRK-15A-2P-240V-B Circuit breaker,2 pole,ISA,Eaton BR2156 with hold dawn kit support Engineering Eaton BR series busbar assembly. BRK-20A-2P-24ov-B Circuit breaker,2 pole,20A,EatonBR220B with hold down kit support XA-SOLARSHIELD-ES Replacement solar shield for IQ Combiner 4/4C XA-PLUG-120-3 Accessory receptacle for Power Line Carrier in IQ Combiner 4/4C(required for EPLC-01) CURRENT RENEWABLES ENGINEERING INC. 1" X-IQ-NA-HD-125A Hold-down kit for Eaton circuit breaker with screws 1760 CHICAGO AVE SUITE I - - - - - - - - - -- - _ J-13,RIVERSIDE CA 92507 'Consumption monitoring CT -A pair of 200A split core current transformers PHONE:(951}405-1733 _ Smart ;(CT-200-SPLIT/CT-200-CLAMP) WWW.CRENG.CO i ELECTRICAL SPECIFICATIONS Includes IQ Gateway for communication and control Rating Continuous duty • Includes Mobile Connect cellular modem - -- - -- -- - - - - - ---- ----- - - - - - System voltage 120/24OVAc,60 Hz (CELLMODEM-MI-06-SP-05),included only with - - - -- - --- — - - - - - - - — - -- CONTRACTOR INFO I� Eaton BR—senes-busbar rating- IQ Il IQ Combiner 4C - — ---- -- - - - - - - - -- - - ;. Includes solar shield to match Enphase IQ Battery Max continuous current rating 65A ;r; - -- --- - -rating - - -- - - - aesthetics and deflect heat 'Max continuous current rating(input from PV/storage) 64A • Supports Wi-Fi,Ethernet,or cellular connectivity Max.fuse/circuit rating(output) 90A 01 r5 j Optional AC receptacle available for PLC bridge .Branch circuits(solar and/or storage) Up to four 2-pole Eaton BR series Distributed Generation(DG)breakers only(not included) - - - J P w� • Provides production metering and consumption ,Max.total branch circuit breaker rating(input) BOA of distributed generation/95A with IQ Gateway breaker included ` i +' monitoring 'IQ Gateway breaker 10A or 15A rating GE/Siemens/Eaton included SOUND ELEMENTVE AVENUE.M TPIT-- - - - - - ---- - 7470 A U A UCK, ERGY LLC. Production metering CT 200A solid core pre-installed and wired to IQ Gateway NEW YORK,11952 r Simple MECHANICAL DATA PH:(631)779 7993 - - - - -'-- services@e2sys.com X-IQ-AM7 240-0C �_ Dimensions(WxHxD) 37.5 cm x 49.5 cm x 16.8 cm(14.75 in x 19.5 in x 6.63 in).Height is 53.5 cm(21.06 in)with mounting brackets. Licence-ME-52689 --�: _ i Mounts on Single stud With centered brackets - - - - - - - - -- - - - - -- -- - (MASTER ELECTRICIAN) X2-IQ-AM1-240-4C(IEEE 1547:2018) (_ Supports bottom,back and side conduit entry Weight 7.5 kg(16.5lbs) Licence-HI-67461 Allows up to four 2-pole branch circuits for 240VAC Ambient temperature range -40°C to+46°C(-40°Fto 1151F) (SUFFOLK HOME IMPROVEMENT) I plug-in breakers(not included) Cooling Natural convection,plus heat shield Solar IrldIVIdUaI _ 5: • 80A total PV or storage branch circuits Enclosure environmental rating Outdoor,NRTL-certified,NEMA type 3R,polycarbonate construction Permit Package s Wire sizes 20A to SOA breaker inputs:14 to 4 AWG copper conductors Bailable 60A breaker branch input:4 to 1/0 AWG copper conductors •Main lug combined output:10 to 2/0 AWG copper conductors EM I LIA KABAKOV r•' Neutral and ground:14 to 1/0 copper conductors Durable NRTL-certified NEMA type 3R enclosure Always follow local code requirements for conductor sizing.1 Five-year limited warranty Altitude up to 3,000 meters(9,842 feet) - 1 2.1 5OKW Grid Tied 1 Two years labor reimbursement program coverage INTERNET CONNECTION OPTIONS Photovoltaic System f: included for both the IQ Combiner SKU's Integrated Wi-Fi IEEE 802.11b/g/n X-IQ-AM7-240-4.•�==- =-a. ,�- -- ULIISted Cellular CELL.MODEM-Ml-06-SP-05,CELLMODEM-M1-06-AT-05(4G based LTE-Mlcellularmodem).Note that an Mobile Connect 1735 PARK AVE, • X2-IQ-AMl-240-4 and X2-IQ-AMl-240-4C comply with cellular modem is required for allEnphase Energy System installations. MATTITUCK,NY11952 X2-IQ AM7 240 4(IEEE 1547:2018) IEEE 1547:2018(UL 1741-SB,3rtl Ed.) Ethernet Optional,IEEE 802.3,Cat5E(or Cat6)UTP Ethernet cable(not included) COMPLIANCE Rev Description IDate A INITIAL DESIGN 2/14/2024 IEEE U� O Compliance.IQ Combiner Rule 21(UL 1741-SA)I IEEE 1547:2018-UL 1741-SB,311 Ed.(X2-IQ-AM1-240-4 and X2-IQ-AM1-240-4C) i CAN/CSA C22.2 No.107.1,Title 47 CFR,Part 15,Class B,ICES 003 Production metering:ANSI C12.20 accuracy class 0.5(PV production) OPPORTUNITY EMILIA KABAKOV LSO Consumption metering:accuracy class 2.5 To learn more about Enphase offerings,visit enahase.com -' f EN PHAS E. I PROJECT# 6623 `/ Compliance.IQ Gateway UL 60601-1/CANCSA 22.2 No.61010-1 IQ-C-4-4C-DS-0103-EN-US-12-29-2022 C 2022 Enphase Energy.All rights reserved.Enphase,the Enphase logo,IQ Combiner 4/4C,and other names are trademarks of DATE DRAWN 2/1 412 02 4 Enphase Energy.Inc.Date subject to change. IQ-C-4-4C-DS-0103-EN-US-12-29-2022 DRAWN BY E.R SHEET# PV-11.2 TITLE COMBINER SPEC /fir IRON RIDGE XR Rail° Family XR Rail° Family The XR Rail@ Family offers the strength of a curved rail in three targeted sizes. Each size supports specific Solar Is Not Always Sunny design loads,while minimizing material costs. Depending on your location,there is an XR Rail8 to match. Over their lifetime,solar panels experience countless THESE DRAWINGS ARE SUBJECT TO extreme weather events. Not just the worst storms in years, . COPYRIGHT PROTECTION BY US LAW. ears. High winds capable of � REPRODUCTION IN ANY FORM IS but the worst storms in 40 Y g p _ _ ~�_ EXPRESSLY FORBIDDEN WITHOUT PRIOR ripping panels from a roof,and snowfalls weighing \_ _ ---- — enough to buckle a panel frame. ® — — — _ WRITTEN APPROVAL FROM CURRENT RENEWABLES ENGINEERING INC. ® - - ` XR Rails@ are the structural backbone ®� XR10 ` xRioo ,� Current ®� �� logo RenewableS preventing these results.They resist uplift, ����®�® ,: protect against buckling and safely �� � ®� t' XR10 is a sleek,low-profile mounting XR100 is a residential and commercial XR1000 is a heavyweight among Engineering and efficient) transfer loads into the �Q� ® rail,designed for regions with light or 4b mounting rail.tt supports a range of solar mounting rails.It's built to handle i"' +? - � no snow.It achieves spans u to 6 feet, wind and snow conditions,while also extreme climates and spans up to 12 building structure.Their superior �' '=;-.;...� P P spanning capability requires fewer }�" while remaining light and economical. maximizing spans up to 10 feet. feet for commercial applications. CURRENT RENEWABLES I, ENGINEERING INC. roof attachments reducing `R the 1:� __. 6'spanning capability 10'spanning capability - 12'spanning capability 1760 CHICAGO AVE SUITE -��'-' h -. Y Moderate load capability - J-13,RIVERSIDE CA 92507 number Of roof penetrations _ - Pability - Heavy load capability Extreme load capability p ~ ' ! ' y �® Clear&black anodized finish Clear&black anodized finish Clear anodized finish PHONE:(951}405 1733 and the amount of . WWW.CRENG.CO _ -- - r�`�� Internal splices available Internal splices available Internal splices available installation time. y "7 j Rail Selection CONTRACTOR INFO The table below was prepared in compliance with applicable engineering codes and standards.*Values are I based on the following criteria:ASCE 7-16, Gable Roof Flush Mount, Roof Zones 1 &2e, Exposure B, Roof [Misr Slope of 8 to 20 degrees and Mean Building Height of 30 ft.Visit IronRidge.com for detailed certification letters. EZSYS6 ELEMENT ENERGY LLC. 7470 SOUND AVENUE,MATTITUCK, NEW YORK,11952 Force-Stabilizing Curve 90 PH:(631)T79 7993 9 - ! _ services@e2sys.com Licence-ME-52689 Sloped roots generate both vertical and lateral 12O - - - (MASTER ELECTRICIAN) forces on mounting rails which can cause them to bend and twist The curved shape of XR Rails® None — ---� ca 1- Licence-IMPROVEMENT) is specially designed to increase strength in both 140 XR10 XR100� XR1000 (SUFFOLK HOME MPROVV EMENT) directions while resisting the twisting.This unique i b a feature ensures greater security during extreme 1so Solar Individual weather and a longer system lifetime. Permit Package «`: .. 90 �+ 120 ! EMILIAKABAKOV s , 20 140 _ 12.150KW Grid Tied ' 160 Photovoltaic System 90 30 1735 PARK AVE, 160 MATTITUCK,NY 11952 Compatible with Flat&Pitched Roofs Corrosion-Resistant Materials 90 Rev Description I Date XR Rails®are IronRidg0 offers All XR Rails®are made of 6000-series k :•, 40 A INITIAL DESIGN 2114/2024 compatible with a range of tilt leg aluminum alloy,then protected with an 160 FlashFoots and options for flat anodized finish.Anodizing prevents surface other pitched roof ■�■ roof mounting and structural corrosion,while also providing ® 80 160 OPPORTUNITY EMILIA KABAKOV attachments. applications. a more attractive appearance. 120 160 PROJECT# 8623 _- DATE DRAWN 2/14/2024 'Table is meant to be a simplified span chart for conveying general rail capabilities.Use approved certification letters for actual design guidance. DRAWN BY E.R SHEET# PV-11.3 2023.1ronRidge.Inc.All rights reserved.Visit www.fronridge.corn or call 1-8DO-227-9523 for more.information.Version 122 IL SPEC AHJ CONDENSED PERMIT PACKAGE Version 8 2023 176 7SS Part# Box Quantity 17664, 17666, 17b66NT 17664 5.25" Bolts (10) THESE DRAWINGS ARE SUBJECT TO COPYRIGHT PROTECTION BY US LAW. 17666 3" Microflashing® (10);5.25" Bolts (10) REPRODUCTION SSLY FORBIDDEN FORMWITH IS PRIOR LOW PROFILE Q B 1 WITH 3" WRITTEN APPROVAL FROM CURRENT 3 M I C RO F LAS H I N G® 17666NT 3" Microflashing® (25); 5.25" Bolts(25); 5/16" Serrated Hex RENEWABLES ENGINEERING INC. FOR ASPHALT, EPDM, & TPO ROOFS Flange Nuts (25) PATENT#8448407 17667SS 3"Microflashing® (25); 5.25" Bolts(25); L-Foot(25);5/16" Current Serrated Hex Flange Nuts(25) RenewablBs Engineering CURRENT RENEWABLES ENGINEERING INC. 1760 CHICAGO AVE SUITE .:_: - - •" - - - '-i J-13,RIVERSIDE CA 92507 �q.t PHONE:(951)-4051733 WWW.CRENG.CO .01 j =4=�,i•=. __ _ .. .-� Sr:.•�.t. '�.y�r3 "4:ca r} S• nF'_,.�.''rw- 'til T-�`Up` a l -- •-r . .:=:: - < '�t.�'`-;�=�?S'�v� '�'� --. -- '-''�;°�►,:.. -• - — y�.,.c..�,,o... ;�.;�' �.- ,. CONTRACTOR INFO AWA - - E2SYSL _7 ELEMENT ENERGY LLC. 74705 UNDAVENUE.MATrITLICK ,_.--y -""�+• �.;.^, �\ _ - NEWYORK.11952 Microflashing•© PH:(631)779 7993 p services@e2sys.rom . 1, ��r zy � Pam,, �Q�,• Licence E-52689 ELECTRICIAN) '...,•?",, '--�±i ''ter ' a]. i1c� (MASTER Licence-H 67461 _,....�' •'+,�,,, ,„.- ..".yffa.,+ ;, - (SUFFOLK HOME IMPROVEMENT) Solar Individual Permit Package EMILIA KABAKOV 12.150KW Grid Tied Photovoltaic System 1735 PARK AVE, —� MATTITUCK,NY 11952 ' ~ Rev Description I Date A INITIAL DESIGN 1 2/14/2024 ' - - - OPPORTUNITY EMILIA KABAKOV PROJECT# 8623 A DIVISION OF QUICKSCREWS INTERNATIONAL CORP DATE DRAWN 2/14/2024 5830 Las Positas Road,Livermore CA 94551 1 3948 Airway Drive,Rock Hill SC 29732 ® DRAWN BY E.R Phone:(844)671-6045 1 Fax:(800)689-7975 1 www.quickbolf.com SHEET# PV-11.4 QuickBOLT is a division of Quickscrews Internafional Corp. TITLE ATTACHMENT SPEC 28357 Industrial Blvd. ®lam I RON RI DGE Hayward,CA 94545 28357 Industrial Blvd. 1-800-227-9523 ®�,�, I R O N R I D G E Hayward,CA 94545 IronRidge.com IronRi ge.co 23 IronRidge.com Attn:Corey Geiger,COO,IronRidge Inc. The parameters and adjustments allowed in the span tables are defined as the following: Date:September r,2021 1. The Flush Mount System is designed as a Risk Category 11 structure as defined by ASCE 7-16 Table 1.5-1. THESE DRAWINGS ARE SUBJECT To Re:Structural Certification and Span Tables for the IronRidge Flush Mount System COPYRIGHT PROTECTION BY US LAW. REPRODUCTION IN ANY FORM IS 2. Wind speed shall conform to ASCE 7-16 Fig.26.5-1 B(for Risk Category 11)and applicable state&local EXPRESSLY FORBIDDEN WITHOUT PRIOR This letter addresses the structural performance and code compliance of IronRidg e's Flush Mount S tem. The count /ci amendments to the IBC. Nos ecial wind to o ra hic features are included and both to o ra hic WRITTEN APPROVAL FROM CURRENT p p � y 'r p p g p p g p RENEWABLES ENGINEERING INC. contents of the letter shall be read in its entirety before applying to any project design.The Flush Mount System is a coefficient(K,.t)and wind ground elevation factor(Ke)are taken as 1.0. proprietary rooftop mounting system used to support photovoltaic(PV)modules installed in portrait or landscape orientation and set parallel to the underlying roof surface. PV modules are supported by extruded aluminum XR Rails 3. Snow load used in the span tables is the ground snow and shall conform to ASCE specified Fig. and Current applicable state&local county/city amendments to the IBC.If the local jurisdiction specified snownow load is in the and secured to the rails with IronRidge mounting clamps.The XR Rails are side mounted to a selected roof format of a flat roof snow,it shall first be converted to a ground snow following the local building code/ Renewables attachment with 3/8"stainless steel bonding hardware and then attached directly to the roof structure or to a stanchion amendments before the application of the attached span tables.No special snow conditions are considered Engineering that is fastened to the underlying roof structure. Assembly details of a typical Flush Mount installation and its core including unbalanced,drifting,sliding,retention,or ponding snow.No rain-on-snow surcharge load is components are shown in Exhibit EX-0015. considered.The span tables do not apply to buildings which are intentionally kept below freezing,kept just above freezing,or unheated. CURRENT RENEWABLES ENGINEERING INC. The IronRidge Flush Mount System is designed and certified to the structural requirements of the reference standards 1760 CHICAGO AVE SUITE 4. The span tables reflect the ASCE 7 prescribed earthquake loads with the maximum magnitudes being: J-13,RIVERSIDE CA 92507 listed below,for the load conditions and configurations tabulated in the attached span tables. PHONE-(951�405-1733 (a)For ground snow no greater than 42psf:SS s 2.Og for Site Class A,B,C,&D. WNNV.CREN G.CO ASCEISEI 7-16 Minimum Design Loads for Buildings and Other Structures(ASCE 7-16) (b)For ground snow greater than 65psf:Ss<_1.0g for Site Class A,B,C,&D. • 2018 International Building Code(IBC-2018) (c)For ground snow between 42 and 65psf:SS<1.5g for Site Class A,B,C,&D. • 2020 Building Code of New York State(BCNYS-2020,Published in November 2019) CONTRACTOR INFO • 2015 Aluminum Design Manual(ADM-2015) 5. Roof zones are defined by ASCE 7-16 Figure 30.3-2A to Figure 30.3-21 and are organized into three groups in • Report SEAOC(Structural Engineer Association of California)PV2-2017 Wind Design for Solar Arrays which the zones share the same External Pressure Coefficients(GCp).Roof zones comprising each group along with each roof zone's size and location are depicted in Figures 2 and 3 below each span table. The tables included in this letter provide the maximum allowable spans of XR Rails in the Flush Mount System for 6. The maximum rail cantilever length,measured from the rail end to the nearest attachment point,shall the respective loads and configurations listed,covering wind exposure categories B,C,&D,roof zones provided in be the lesser of the following two conditions:40%of the allowable span provided for the respective load E P—SYS6 ASCE 7-16 for gable&hip roof profiles,and roof slopes of 8°to 45'.The tabulated spans are applicable when the &configuration condition from the span tables,or 36". ELEMENT ENERGY LLC. following conditions are met 7. Allowable span length in the charts may be multiplied by a factor of 1.08 if the rails are continuous over 7470 SOUND AVENUE.MATTITUCK, NEW YORK,11952 a minimum of three Spans. PH:(631)779 7993 1. Span is the distance between two adjacent roof attachment points(measured at the center of the services@e2sys.com 8. No splices are allowed in the rail cantilever.For each XR splice type install per the following requirements: Licence-ME-52689 attachment fastener). (MASTER ELECTRICIAN) Licence-HI-67461 a) XR Bonded Splice cannot be installed in the center 1/3 of interior spans,or the outer 2/3 of end Spans. (SUFFOLK HOME IMPROVEMENT) 2. Each module shall be supported by 2 rails(2 rail system)or 3 rails(3 rail system).Spans are calculated b) BOSS Splice can be installed at any location within a span. based on 2 rail systems,and conservatively deemed acceptable for 3 rail systems. Solar Individual 9. Shaded cells of the span tables indicate conditions in which UFO Mid Clamp connection capacity is exceeded.If Permit Package 3. The underlying roof slope,measured between the roof surface and horizontal plane,is 81 to 450. such conditions are encountered contact support@ironridge.com. EMILIA KABAKOV 4. The mean roof height,defined as the average of the roof eave height and the roof ridge height measured from grade,does not exceed 30 feet. 12.15OKW Grid Tied Photovoltaic System 5. A clearance from the underside of the array to the roof surface of 2"minimum shall be provided and the height of the array,the distance from the module top surface to the roof surface(defined as h2),shall not 1735 PARK AVE, exceed 10". MATTITUCK,NY 11952 Rev Description Date 6. Module length and area shall not exceed the maximum values listed on the respective span tables. A INITIAL DESIGN 2/14/2024 7. All Flush Mount components shall be installed in a professional workmanlike manner per IronRidge's Flush Mount Installation Manual and other applicable standards for the general roof construction practice. OPPORTUNITY EMILIA KABAKOV PROJECT# 6623 DATE DRAWN 2/14/2024 DRAWN BY E.R ©2021 IronRidge,Inc. NY Flush Mount System Certification Letter-1 @ 2021 IronRidge,Inc. NY Flush Mount System Certification Letter-2 SHEET# PV-11.5 TITLE CERTIFICATION 28357 Industrial Blvd. 28357 Industrial Blvd. /,�,r. IRON RIDGE I RON Rl DGE Hayward,CA 94545 Hayward,CA 94545 1-800-227-9523 1-800-227-9523 IronRidge.com IronRidge.com 10. Systems using CAMO module clamps shall be installed with the following guidance: a) For single module installations(orphan modules)using modules with a length greater than 67.5",CAMO The span tables provided in this letter are certified based on the structural performance of IronRidge XR Rails only with no THESE DRAWINGS ARE SUBJECT TO clamps shall not be installed in regions that experience ground snow loads of 70psf and greater.Such consideration of the structural adequacy of the chosen roof attachments,PV modules,or the underlying roof supporting COPYRIGHT PROTECTION BY US LAW. members.It is the responsibility of the installer or stem designer to verify the structural capacity and adequacy of the REPRODUCTION IN ANY FORM IS scenarios are shown by asterisks in the applicable span tables. P `7 - Y g 'Y P � q CY EXPRESSLY FORBIDDEN WITHOUT PRIOR b CAMO will function within a module's design load ratings.Be sure the specific module being used with aforementioned system Components in regards to the applied or resultant loads of any chosen array configuration. WRITTEN APPROVAL FROM CURRENT 9 9 P g RENEWABLES ENGINEERING INC. CAMO meets the dimensional requirements shown in the figure below and that the module selected is suitable for the environmental conditions of a particular project pF NEy,` 0 0 0 Sincerely, O Current . Renewa tiles Module - �� w - w 5:45: 6 Engineering 096519 ?O CURRENT RENEWABLES ROfESS10aI`�� _O/ '0 0' ENGINEERING INC. Frame Compo6b:5ty 1760 CHICAGO AVE SUITE X=1.2-22 mm - - - J-13,RIVERSIDE CA 92507 Y=15-40 mm PHONE:(951)-405-1733 Gang Xuan,PE WWWCRENG.CO Y� Senior Structural Engineer x Figure t CAMO Module Frame Dimensional Requirements CONTRACTOR INFO Span values for Exposed and Edge module conditions,as defined below,are included in the attached span tables and shall be used when each condition exists. The maximum allowable span for Exposed or Edge I M M modules shall be the lesser of the following two:(1)The span value for the Exposed or Edge module condition; C25Y5 (2)The span value determined by site wind speed and ground snow load.Additionally,irrespective of the lesser span,the shaded cells for the Exposed and Edge module conditions which reflect the UFO clamp usage limi'tatlon detailed in note 9 of page 2 shall apply to the respective condition. ELEMENT ENERGY I.L.C. 7470 SOUND AVENUE.MATTITUCK. NEW YORK,11952 PH:(631)779 7993 1. Exposed Module conditions: services6 Licence--ME-52E-52689 (MASTER ELECTRICIAN) Licence-HI-67461 A module is defined as Exposed(per Section 29.4A of ASCE 7-16)if the distance from any of its free (SUFFOLK HOME IMPROVEMENT) edges(an edge with no connectivity to other modules)to its facing roof edge(such as eave,ridge,rake,or Solar Individual hip)is greater than 0.5h(h is ASCE defined building height)AND if the distance from its free edge to any Permit Package other adjacent array or panel is greater than 4 feet. The allowable spans and cantilever shall only be applied to the portion of rail directly under Exposed EM I LIA KABAKOV Modules. 12.150KW Grid Tied 2. Edge Module conditions: Photovoltaic System A module is defined as an Edge Module when its distance from any side of the module to its facing 1735 PARK AVE, perimeter roof edge(such as eave,ridge,rake,or hip)is less than 2 times the height of the array(2h2) MATTITUCK,NY 11952 where h2 is measured from the roof surface to the top surface of the module. Rev Description Dale A INITIAL DESIGN 2/14/2024 The allowable spans and cantilever shall only be applied to the portion of rail directly under Edge Modules. Additionally,if the roof edge is the eave or ridge,only the rail nearest to that roof edge shall be considered for this span adjustment. OPPORTUNITY EMILIA KABAKOV PROJECT# 8623 DATE DRAWN 2/1 412 0 2 4 DRAWN BY E.R ©2021 IronRidge,Inc. NY Flush Mount System Certification Letter-3 ©2021 IronRidge,Inc. NY Flush Mount System Certification Letter-4 SHEET# PV-11.6 TITLE IRONRIDGE BONDING AND GROUNDING