HomeMy WebLinkAboutZ-29996FORM NO. 4
TOWN OF SOUTHOLD
BUILDING DEPA2~TMENT
Office of the Building Inspector
Town Hall
Southold, N.Y.
PRE EXISTING
CERTIFICATE OF OCCUPANCY
No: Z- 29996
Date: 02/04/04
THIS
Lo~ation of Property 53800 MAIN RD
(HOUSE NO.~
County Tax Map No. 473889 Section 061
Subdivision
2ERTIFIES that ~he building COMMERCIAL STRUCTURE
(STREET)
Block 0004
Filed ~ap No. Lot No. --
SOUTHOLD
HAMLET)
Lot 007.002
conforms substantially to the Requirements Eot a BUSINESS STRUCTURE
built prior to APRIL 9, 1957 pursuant to which CERTIFICATE OF
OCCI/PANCYAN31~BER Z- 29996 dated FEBRUARY 4, 2004
was issued, and conforms to all of the requirements of the applicable
provisions of the law. The occupancy for which this certificate is
issued is COMMERCIAL BUILDING WITH 2ND FLOOR APARTMENT*
The certificate is issued to MLRV CORP
of the aforesaid building.
(OWNER)
SUFFOLK COUNTY DEPARTMENT OF~EALTHA~PROVAL
ELECTRICAL CERTIFICATE NO.
PLUMBERS CERTIFICATION DATED
*PLEASE SEE ATTACHED INSPECTION REPORT.
N/A
N/A
N/A
Rev. 1/81
BUILDING DEPARTMENT
TOWN OF SOUTHOLD
HOUSING 20DE INSPECTION REPORT
SOUTNOLD
MAP NO.: LOT (B)
MLR¥ CORP
ACCOMPANI~ BY: SAME
ACCESSORY~STRUCTUBES:
VIOLATIONS: CRAPTER 45 N.Y STATE U~IFOR~ FIRE PREVENTION & BUILDING CODE
LOCATION DESCRIPTION ART.
SEC
Form No..6
TOWN DF SOUTIdOLD
BUILDING DEPARTMENT
TOWN HALL
7~-1802
A~PI~ICATION FOR CERTIFICATE OF OCCUPANCY
This application must be filled hi by typewriter or ink and submitted to.the Building DepartmenX with the following:
A. For new building or new use:
1. Final survey of property with accurate location of ali buil.dings, property lhies, streets, and unusual natural or
topographic features.
2. Final Approval from Health DepL of water supply a~d sewerage-disposal (S-9 forafl.
3. Approwl cfi electrical installation from Board o f.Fire Underwriters.
4,,'Sworn statement from plumber certifyingth~-l~!,golder used in system contains less than 2/10 of 1% lead.
5. Co~ ~m3n~ erci~ bu/lding, industr/at bui'lding, m~ti~[ residences, and similar buildings and installations, a certificate
of Code Compliance from architect or engineer responsible for the building.
6. S~bmit Pl~uming Board Approval of complated site plan reqmrements.
Bo
For existing bug[dings, (prior to, April. 9, 1957) non-conformino~, uses, or buil ding' ~,s and "pre-existing" land uses-.
1 Accurate survey of property showing all property lines, streets, building and, unus~l, rlatural or topograph/c
features. '-TM " '
2. A lproperly completed application and consent to inspect signed by the applicant: If~Certificate of Occupancy is
denied, the Building Inspector shall state the reasons therefor hi writing to the applicant.
Fees
1. Certificate of Occupancy - New dwelling $25.00, Additions to dwelling $25.00. Attemfions to dwelling $25.00,
Swimming pool $25.06, Accessory building $25.00. Additions to accessory building $25.00, Businesses $50.00.
2. Certificate of Occupancy on Pre-existing Building - $100.00
3. Copy o£Certificate of Occupancy - $.25
4. Updated Certificate o£Occupancy - $50.00
5. Temporary Certificate of Occupancy -Resident/al $15.00, Commercial $15.00 -
New Construction: Old or Pre-ecxisthig Building: I / (chec~c one/
Locationofmmperty: ~D-~ //~.~ ~ ,5~~'
House No. Street
Owner or Own~s of Property: ./~., ~7 ~,/'. ~ ~/~.,,
Suffolk County Tax Map No 1000. Section ~// Block ~ ¢
Subdivision
Permit No. Date of Perrdit.
Hamlet
Health Dept. Approval:
Planning Board Approval:
Request for: Temporary Certificate
Fee Submitted: $
Filed Map.
Applicant:
Lot:
Underwriters Approval: /
Final Certificate: (ch~ck one)
'/Applicant Signature
CONSENT TO INSPECTION
Owner(s) Name(s)
the undersigned, do(es) hereby state:
That the undersigned (is) (are) the owner(s) o~f the pr~n/hes m the Town of ~ ,~
Sonthold, located at ~ I~'~ /~,,3~ ~_g~. x.~e:5~D-ff~t'~g %
which is sh~ anddesign[ted ~)n~ the Suf/[.4lk ~.~unty Tax Map as District 1000,
Section ~/ ;Block ~)~/,L0t 7- a~ .
That the undersigned (has) (have) filed, or cause to be filed, an application in the
S onth_ol.d .TTowu Building Inspector's OftSce for the following: /3:Y~__r' _ c"~¢
That the undersigned do(es] hereby g~ve consent to the Building Inspectors of the
Torch of Southold to enter upon the above described property, including any and all
bu/ldings located thereon, to conduct such inspections as they may deem necessary with
respect to the aforesaid application, including inspections to determine that said premises
comply with al/of the laws. ordinances, roles and regulations of the Town of S outhold.
The undersigned, in consenting to such inspections, do(es) so with the knowledge
and understanding that any information obtained in the conduct of such inspections may
be used in subsequent prosecutions for violations of the laws, ordinances, roles or
regulations of the Town of Southold.
Dated:
(Print Name)
(Signature)
(Print Name)
Town Hall, 53095 Main Road
P.O. Box 1179
Southold., New York 1~.971-0959
October 23, 2003
BUZLD~N~~T
Fire In~ Report 2003
Fax (631) 765-9502
Telephone (631) 765-1802
Mr. Michael Liegey
MLRV Corp.
53800 & 53850 Main Road
Southold, NY 11971
Dear Mr. Liegey:
Thank you for the cooperation during the fire inspection of the premises 53800 and
53850 Main Road on October 22, 2003.
During the inspection the following violations were noted and should be corrected
immediately.
Party Shop East Side
There shall be an exit sign indicating the front door as an exit.
There shall be a minimum of one (1) set of emergency exit lighting positioned so as to
illuminate the exit paths in case of power interruption.
A fire extinguisher shall be available. A five-pound ABC type extinguisher would be
sufficient. The fire extinguisher shall be mounted in an accessible location and clearly
marked. The extinguisher shall be inspected monthly by a designated employee and
inspected and tagged yearly by an approved servicing company.
In public areas the minimum clear aisle width shall be 36 inches.
Party Shop West Side
There shall be an exit sign indicating the front door as an exit.
There shall be a minimum of one (1) set of emergency exit lighting positioned so as to
illuminate the exit paths in case of power interruption.
PartyShop(MLRV)-03-10-1 614-7.1 &7.2 Page I
A fire extinguisher shall be available. A five-pound ABC type extinguisher would be
sufficient. The fire extinguisher shall be mounted in an accessible location and clearly
marked. The extinguisher shall be inspected monthly by a designated employee and
inspected and tagged yearly by an approved servicing company.
In public areas the minimum clear aisle width shall be 36 inches.
Gallery
There shall be an exit sign indic,atir~g.the front door as an exit.
There shall be a minimum of one (1) set of emergency exit lighting positioned se as to'
illuminate the exit paths in case of power interruption
A fire extinguisher shall be available. A five-pound ABC type extinguisher would be
sufficient. The fire extinguisher shall be mounted in an accessible location and cleady
marked. The extinguisher shall be inspected monthly by a designated employee and
inspected and tagged yeady by an approved servicing company.
public areas the minimum clear aisle width shall be 36 inches.
Flexible cords and extension cords shall not be a substitute for permanent wiring.
Extension cords and flexible cords shall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be
subject to environmental damage or physical impact. Extension cords shall be used
only with portable appliances.
Open junction boxes, open breaker spaces, and open winng splices shall be prohibited.
Approved covers shall be provided for all switch and electrical outlet boxes.
Apartment 2nd Floor
A fire extinguisher shall be available. A two and one half-pound ABC type extinguisher
would be sufficient. The fire extinguisher shall be mounted in an accessible location
and clearly marked. The extinguisher shall be inspected monthly by a designated
emPloyee and inspected and tagged yearly by an approved servicing company.
Smoke detectors shal be provided in each sleeping area and outside the sleeping
areas.
Apartment Grade Level rear
This apartment is not permitted and shall be removed immediately.
All appliances shall be removed
Basement West Side
The minimum clear aisle width shall be 36 inches.
Par[yShop(MLRV)-03-10-1 614-7.1 & 7.2
Page 2
A working space of not less than 30 inches wide, 36 inches deep, and 78 inches high
shall be provided in front of electrical service equipment. No storage of any material
shall be stored within the designated working space.
A working space of not less than 30 inches wide, 36 inches deep, and 78 inches high
shall be provided in front of gas service equipment. No storage of any material shall be
stored within the designated working space.
The basement area shall be cleaned up and unnecessary ma~terials disposed of
proper Y~L'
Basement East Side
The minimum clear aisle width shall be 36 inches.
A working space of not less than 30 inches wide. 36 inches deep, and 78 inches high
shall be provided in front of electrica[~.ervice equipment. No storage of any material
shall be stored within the designated ~,(~rking space.
A working space of not less than 30 inches wide, 36 inches deep, and 78 inches high
shall be provided in front of gas service equipment. No storage of any material shall be
stored within the designated working space.
A working space of not less than 18 inches shall be provided around heating
equipment. No storage of any material shall be stored within the designated working
space.
The clothes dryer shall be vented properly.
Open junction boxes, open breaker spaces/and open wiring splices shall be prohibited.
Approved covers shall be provided for all switch and electrical outlet boxes.
Flammable and combustible liquids shall not be stored in the building.
The insulation shall be installed properly so as not to be a fire hazard.
The basement area shall be cleaned up and unnecessary materials disposed of
properly
East Building 2nd Floor Foyer
A fire extinguisher shall be available. A two and one half-pound ABC type extinguisher
would be sufficient. The fire extinguisher shall be mounted in an accessible location
and cleady marked. The extinguisher shall be inspected monthly by a designated
employee and inspected and tagged yearly by an approved servicing company.
in addition the following shall also be done.
PariySh0p(MLRV)-03-10-1 61~-7,1 & 7.2
Page 3
The stacked cut wood stored under the wooden steps from the second floor shall be
removed.
The opening between buildings shall be removed immediately. This is not permitted by
code and by zoning.
If you have any questions or the required modifications are completed, please contact
me at the above office.
Your truly,
Robert Fisher
Fire t~¢~lJector
Cc: Chief, Southold Fire Department
Pa~Shop(MLRV)-03-10-1
61-4-7.1&7,2
Page 4
ROAD