Vice President Re: Town of Southold Landfill
RobJ.DeGiorgio,RE.,CPESC
Vice President Landfill Gas Monitoring.Program, Fourth Quarter 2013
Stephen M.Dudar,P.E.
Vice President D&B No. 3175
Thomas P.Fox,P.G.
Vice President
William D.Merklin,P.E. Dear Mr. Bunchuck:
Vice President
Michael Neuberger,P.E.
Vice President On November 23, 2013, Dvirka and Bartilucci Consulting Engineers (D&B)
Ken-Vice President
P.E. completed the Fourth Quarter 2013 landfill gas monitoring event for the Town of .
"Vice President
Theodore S.Pytlar,Jr. Southold Landfill located on Middle Road(CR 48) in Cutchogue, New York. The
Vice President
Brian M.Veith,P.E. landfill;gas..,monitoring was.,conducted utilizing a GEM 2000 Plus Landfill Gas
Vice President Surveyor at.the.existing,15.gas monitoring wells (GMW-L,to,1,5.jocated along the.
Charles J:Wachsmuth,P.E.
'Vice President southern, eastern.-and northern boundary. of,the landfill,. waste mass). .Weather
Dir.of Architecture conditions on.November 23, 201.3',--were observed.to be clear-and approximately .
Andre H.Keel,R.A. 43 deees Fahrenheit with light-winds heading.east.
Senior Associates
Steven M.Cabrera
Christopher M.Clement Enclosed with: this letter are Figure 1 and Table 1. Figure 1 shows the
Ellen R.DeOrsay approximate locations of the gas monitoring wells-, and Table 1 lists .the gas
Matthew R DeVinney,P.E. monitoring wells and their corresponding temperature and d levels of o)(ygen;
Frank DeVita
Joseph A.Fioraliso,P.E. carbon,monoxide, lower explosive limit (LEL) for methane and hydrogen sulfide
Michael R.Hofgren 'as measured on November: 23, 2013. As indicated in Table .1, there 'was a
Christopher M.LeHanka detection of methane eater than 100%of the LEL'at as:irionitorin well GMW-
Richard W.Lenz,P.E. gr g g
Olga Mubarak)aramillo 6, located along the eastern boundary of the waste mass.'GMW-6 has exhibited a .
Philip R.Sachs,P.E. trend of•elevated LEL detections-for methane, often" over 100%, suggesting that
Daniel Shabat,P.E. gas migration is occurring beyond the boundary of the waste mass in this area. It.
Associates should be noted however, that GMW-6 is not located at the property boundary,
Rudolph F.Cannavale � � 1� h y Y,.
Christopher W.Francis which is approximately 250 feet to the north and 350 feet to the east of GMW-6.
Christopher Koegel,P.E. In addition, methane was not detected at.GMW=7,,located to the north-of GMW-6
James J.Magda
Michele Mastrangelo at the .northern ,property boundary,.,- or-:,within,. the: :scale , house, located
Roger W.Owens approximately,100 feet,to the.south o.f.GMW-6. The scale house is,the closest on-
Robbin A.Perrella site structure to-GMW-6, and'methane was,not:detected within•the�brawl s ace or
Edward J.Reilly . . - .. . - ... , �p.
stephenTauss occupied-area of the structure.,
Jason R Tonne ;
DVIRKA AND BARTILUCCI
CONSULTING ENGINEERS
James Bunchuck, Solid Waste Coordinator Page Two
Town of Southold DSW
December 19, 2013
In an attempt to mitigate the elevated methane levels detected in GMW-6, the Town installed
wind-driven turbine exhaust fans on the three landfill gas vents located nearest to GMW-6 and
within the landfill mass. The turbines were installed in September 2012, following the third
quarter 2012 landfill gas monitoring event. In order to determine the effectiveness of this
remedial measure, D&B has been measuring both the LEL and percent gas levels for methane at
GMW-6 since the third quarter of 2012. The current percent gas level in GMW-6 is 13.0%,
which is lower than last quarter's 13.9% and significantly lower than the 22.7% measured in the
third quarter of 2012 prior to the installation of the turbines. D&B will continue to monitor the
LEL and percent gas levels for methane at GMW-6.
Consistent with recent monitoring events, the remaining gas monitoring wells did not exhibit
LEL detections for methane. Carbon monoxide and hydrogen sulfide were not detected in any of
the gas monitoring wells, and oxygen levels were detected at and below typical atmospheric
levels.
The next quarterly round of monitoring is expected to be conducted during the First Quarter of
2014. If you have any questions,please contact me at(516) 364-9890, Ext. 3091.
Very yours truly,
a.4 1..�,
Anthony Caniano
Project Manager
AMC/PBt/cf, nc
Enclosures
cc: T. Fox (D&B)
P. Barusich(D&B)
43175\AMC 13 Undoc-08
t r � ���l�it�'U 11,,,rll�'+ jl,Its l ���"�'��`"'t�-��--`�_�-•ir:--'--.�.� �.
as..�____��t�'� �jk tf. ,r- .:rte^- "��--�`�''���`�-`�_�-•=.--� -�`- . ��t
ilk
DONE
'�. �_-_.����`r r r �r �t+� "�`-• -^��.�`���.•�„``-"�\�_ `_-•< r-,--� -moi,:,.-7�.�,
SROh,
E
+'����/r�y /rd
A j a' z".5�,�, �x3:,f/•'\y .r r ,rl ft 7 � b `i�. _I r ,,.�
i ' My.r4� II' f�!'f rillf�
11111i I till
BONN IN
� v a nl19
� 1 - MR
Im
AX
�-�
iC�ActtNK r�i-arai++c�cc-Ci -:+[.?�r•�ry,��•�� �`''
e
r >>is��.
,.��-"--� '�'•c"'�t,.r►-'+mac �' r��� ? `
_.••`�'r.""air fri� �3:n
1 1 /
r—�
SOLItHOLD LANDFILL
Dvirka CLITCHOGUE,NEW YORK
•
'd
• 'Bartilucci LAN DFIL L GAS MONITORING
D10.106 irneem and Architects,P.C.
•LOCATIN.MAP-
TABLE'1
TOWN OF SOUTHOLD LANDFILL
LANDFILL GAS MONITORING PROGRAM
FOURTH QUARTER 2013 MONITORING EVENT
Sampling Date: November 23,2013
Parameter Unit GMW-1TO
GMW-3 .GMW-4 GMW-5 GMW-6 GMW-7 GMW-8 GMW-9 GMW-10 GMW-11 GMW-12 GMW-13 GMW-14 GMW-15
Temperature °C 7.2 7.2 6.6 7.2 7.2 5.6 6.1 6.1 6.6 7.2 7.2 7.2 6.6 6.6
Oxygen % 19.9 21.1 21.2 13.5 1.5 19.1 20.7 21.3 21.7. 14.9 18.0 17.1 18.0 20.0
Carbon Monoxide m 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Lower Explosive Limit-Methanej% 0 0 0 0 >100* 0 0 0 0 0 0 0 0 0
H dro en Sulfide m 0 0 0 0 0 0 0 0 •0 0 0 0 0 0
NOTES:
*: Measured at 13.0%gas.
Typical atmospheric levels of oxygen range between 19.5%and 23.5%
°C =Degrees.Celsius
%=Percent
ppm=Parts Per Million
\\Dbfs1yobs\..•HazWaste\3175(Southold Land011)\4th Quarter 2013\Southold Landfill-Landfill gas monitoring Q42013 Page 1 of 1 12/6/2013