Loading...
HomeMy WebLinkAbout45371-Z rr o'%SgfFQL/ Town of Southold 12/21/2020 P.O.Box 1179 0 C* z 53095 Main Rd 04,t �ao�¢f Southold,New York 11971 CERTIFICATE OF OCCUPANCY No: 41709 Date: 12/21/2020 THIS CERTIFIES that the building GENERATOR Location of Property: 2060 The Long Way, East Marion SCTM#: 473889 Sec/Block/Lot: 30.-2-126 Subdivision: Filed Map No. Lot No. conforms substantially to the Application for Building Permit heretofore filed in this office dated 10/15/2020 pursuant to which Building Permit No. 45371 dated 10/26/2020 was issued, and conforms to all of the requirements of the applicable provisions of the law. The occupancy for which this certificate is issued is: accessorygenerator as applied for. The certificate is issued to Wiseman BM&R Rev Trt of the aforesaid building. SUFFOLK COUNTY DEPARTMENT OF HEALTH APPROVAL ELECTRICAL CERTIFICATE NO. 45371 12/2/2020 PLUMBERS CERTIFICATION DATED Aut orized Signature `Qg11fF0(,�� TOWN OF SOUTHOLD BUILDING DEPARTMENT TOWN CLERK'S OFFICE oy . SOUTHOLD, NY BUILDING PERMIT (THIS PERMIT MUST BE KEPT ON THE PREMISES WITH ONE SET OF APPROVED PLANS AND SPECIFICATIONS UNTIL FULL COMPLETION OF THE WORK AUTHORIZED) Permit#: 45371 Date: 10/26/2020 Permission is hereby granted to: Wiseman BM&R Rev Trt 2060 The Long Way East Marion, NY 11939 To: install generator as applied for. At premises located at: 2060 The Long Way, East Marion SCTM # 473889 Sec/Block/Lot# 30.-2-126 Pursuant to application dated 10115/2020 and approved by the Building Inspector. To expire on 4/27/2022. Fees: ACCESSORY $100.00 ELECTRIC $85.00 CERTIFICATE OF OCCUPANCY $50.00 AX Total: $235.00 i In ctor Form No.6 TOWN OF SOUTHOLD BUILDING DEPARTMENT TOWNL 7654801 ' APPLICATION FOR CERTIFICATE OF OCCUPANCY This application must be filled in by typewriter or ink and submitted to the Building Department with the following: A. For new building or new use: 1. Final survey of property with accurate location of all buildings,property lines,streets,and unusual natural or topographic features. 2. Final Approval from Health Dept.of water supply and sewerage-disposal(S-9 form). 3. Approval of electrical installation from Board of Fire Underwriters. 4. Sworn statement from plumber certifying that the solder used in system contains less than 2/10 of 1%lead. 5. Commercial building,industrial building,multiple residences and similar buildings and installations,a certificate of Code Compliance from architect or engineer responsible for the building. 6. Submit Planning Board Approval of completed site plan requirements. B. For existing buildings(prior to April 9,1957)non-conforming uses,or buildings and"pre-existing"land uses: 1. Accurate survey of property showing all property lines,streets,building and unusual natural or topographic features. 2. A properly completed application and consent to inspect signed by the applicantAf a Certificate of Occupancy is denied,the Building Inspector shall state the reasons therefor in writing to the applicant. C. Fees 1. Certificate of Occupancy-New dwelling$50.00,Additions to dwelling$50.00,Alterations to dwelling$50.00, Swimming pool$50.00,Accessory building$50.00,Additions to accessory`building$50.00,Businesses$50.00. 2. Certificate of Occupancy on Pre-existing Building- $100.00 3. Copy of Certificate of Occupancy-$.25 4. Updated Certificate of Occupancy- $50.00 5. Temporary Certificate of Occupancy-Residential$15.00,Commercial$15.00 Date. /New Construction: Old or Pre-existing Building: (check one) ✓Location of Property: 6 O O House No. Stree Ha et ✓Owner or Owners of Property: v Suffolk County Tax Map No 1000,Section (2b30 r 00 -Block D Z 00-Lot �Z -Oo 0 Subdivision Filed Map. Lot: Permit No. � � Date of Permit. Applicant: Health Dept.Approval: Underwriters Approval: Planning Board Approval: Request for: Temporary Certificate Final Certificate: (check one) Fee Submitted: $ A plicant Signature ®f soUly® Town Hall Annex Telephone(631)765-1802 54375 Main Road Fax(631)765-9502 P.O.Box 1179 sean.deviin(D_town.southold.ny.us Southold,NY 11971-0959 COW, BUILDING DEPARTMENT TOWN OF SOUTHOLD CERTIFICATE OF ELECTRICAL COMPLIANCE SITE LOCATION Issued To. Wiseman BM&R Rev Trt Address: 2060 The Long Way city:East Marion st: NY zip: 11939 Building Permit#: 45371 Section: 30 Block. 2 Lot: 126 WAS EXAMINED AND FOUND TO BE IN COMPLIANCE WITH THE NATIONAL ELECTRIC CODE Contractor: DBA: Laurel Lighting Inc License No: 4718ME SITE DETAILS Office Use Only Residential X Indoor X Basement Generator X Commerical Outdoor X 1st Floor Pool New X Renovation 2nd Floor Hot Tub Addition Survey Attic Garage INVENTORY Service 1 ph X Heat Duplec Recpt Ceiling Fixtures Bath Exhaust Fan Service 3 ph Hot Water GFCI Recpt Wall Fixtures Smoke Detectors Main Panel 200A A/C Condenser Single Recpt Recessed Fixtures CO2 Detectors Sub Panel A/C Blower Range Recpt Ceiling Fan Combo Smoke/CO Transfer Switch 200A UC Lights Dryer Recpt Emergency Fixtures Time Clocks Disconnect Switches 4'LED Exit Fixtures 11 Pump Other Equipment, 22kW Generac Generator w/200A Whole House Transfer Switch Notes: Generator Inspector Signature: C Date: December 2, 2020 S Devlin-Cert Electrical Compliance Form.xls %f SOblyo� L4 s 5 ! 2-0 V V # # TOWN OF SOUTHOLD BUILDING DEPT. 765-1802 INSPECTION [ ] FOUNDATION 1ST [" ] ROUGH PL13G. [ ] FOUNDATION 2ND [ 1,-INSULATION/CAULKING [ ] FRAMING/STRAPPING [ ] FINAL [ ] FIREPLACE & CHIMNEY [ ] FIRE SAFETY INSPECTION [ ] FIRE RESISTANT CONSTRUCTION [ ] FIRE RESISTANT PENETRATION [ ] ELECTRICAL (ROUGH) ELECTRICAL (FINAL) [ ] CODE VIOLATION [(�] PRE C/O REMARKS: OA/ DATE l 2/'2- 1'2-0 INSPECTOR ®),� FIELD INSPECTION REPORT DATE GOMIVTE1atTS FOUNDATION(IST) ---------------------- FOUNDATION --------------------FOUNDATION(2ND) rh ROUGH FRAMING& PLUMBING INSULATION PEA N.Y. r y STATE ENERGY CODE - 1 FINAL ADS• _��+r�r�;�•�:����;s=• z ' e l TOWN OF SOUTHOLD BUILDING PERMIT APPLICATION CHECKLIST e BUILDING DEPARTMENT Do you have or need the following,before applying? TOWN HALL Boaid-6fHealth SOUTHOLD,NY, 11971 4 sets of Building Plans TEL: (631)765-1802 _ Planning Board-approval FAX: (631)765-9502 �j Survey Southoldtdwnny.gov PERMIT NO. J Check Septic Form N.Y.S.D.E.C. Trustees C.O.Application Flood Permit Examined ,20 Single,&Separate I Truss Identification Form Storm-Water Assessment Form Conte Approved d ,20 U Mail to: Disapproved a/c -Phone: Expiration 20 Bu UIQ4fspector I , 0 CT 1 5 2020 APPLICATION FOR BUILDING PERMIT PITH,DING DEPT. Date �(� � 3 ,20 2!� INSTRUCTIONS a:This application MUST be completely filled in by typewriter or in ink and submitted to the Building Inspector with 4 sets of plans,accurate plot plan to scale.Fee according to schedule. _ b.Plot plan showing location,of lot and of buildings on premises,relati'on`ship to adjoining premises or public streets or areas,and waterways. c.The work covered by this application may not be commenced before issuance of Building Permit. d.Upon approval of this application,the Building Inspector will issue a Building Permit to the applicant. Such a permit shall be kept on the premises available for inspection throughout the work. e.No building shall be occupied or used in whole or in part for any purpose what so ever until the Building Inspector issues a Certificate of,Occupancy. f.Every building permit shall expire if the work authorized has not commenced within 12 months after the date of issuance or has not been completed within 18 months from such date.If no zoning amendments or other regulations affecting the property•have been enacted in the interim,the Building Inspector may authorize,in writing,the extension of the permit for an addition six months.Thereafter,a new permit shall be required. APPLICATION IS HEREBY MADE to the Building Department for the issuance of a Building Permit pursuant to the Building Zone Ordinancee-ofthe Town of Southold,Suffolk County,New York,and other applicable Laws,Ordinances or Regulations,for the construction of buildings,additions,or alterations or for removal or demolition as herein described.The applicant agrees to comply with all applicable laws,ordinances,building code,housing code,and regulations,and to admit authorized inspectors on premises and in building for necessary inspections. lJ i igdature of applicant or name,if a corporation) • �z��T (Mailing ad ess of ph6am) A�rJ State whether applicant is owner, lessee, agent, architect, engineer,general contractor, electrician,plumber or builder i�lA)/L)1;2 Name of owner of premises Wk] M MIEMA) 61 A- MA Q rUMA Al )SDC ,C 12U�E (As on the tax roll or latest deed) If applicant is a corporation, signature of duly authorized officer (Name and title of corporate officer) Builders License No. Plumbers License No. Electricians'License No. Other Trade's License No. 1. Location of land on which proposed work will be done: 2060 166 LN6-WAV 9R�f -MAkIM) House Number Street Hamlet County Tax Map No. 1000 Sectiom 630160 Block a o Lot IZ6, 600 Subdivision Filed Map No. Lot 2. State existing use and occupancy of premises and intended use and occupancy of proposed construction_: a. Existing use and occupancy b. Intended use and occupancy 6,kyj-@ 3. Nature of work(check which applicable):New Building Addition Alteration Repair Removal Demolition Other Work &E�r-Amm Q (Description) 4. Estimated Cost IDI Fee (To be paid on filing this application) 5. If dwelling,number of dwelling units Number of dwelling units on each floor If garage, number of cars 6. If business, commercial or mixed occupancy,-specify nature and•extent of each type of use. 7. Dimensions of existing structures,if any: Front OW) Rear n16 1) Depth 29 Height dj�° Number of Stories 1 Dimensions of same structure with alterations or additions: Front Rear Depth Height Number of Stories 8. Dimensions of entire new construction:Front Rear `-Depth Height Number of Stories 9. Size of lot:Front gy i Rear_ e6 j Depth 2 01 10.Date of Purchase %11 Z Name of Former Owner f ako /jt;� Tkl4q 11. Zone or use district in which premises are situated_ A-qv M 69I Lcg V f')S l f q&ff j 7�, t_M 4 f 12.Does proposed construction violate any zoning law, ordinance or regulation?YES NO 13. Will lot be re-graded?YES- ----NO—J—. Will excess_fill.be-removed-from premises?YES NO 14.Names of Owner of premises 'f3l N+k ,n}ia LJI9 Address 206b �4t l�dl�6 WA/Phone No. '1 q 1,6/, 27 Name of Architect Address G MAP-1#A Phone No Name of Contractor Address Phone No. 15 a.Is this property within 100 feet of a tidal wetland or a freshwater wetland? *YES NO V * W YES, SOUTHOLD TOWN TRUSTEES &D.E.C.PERMITS MAY BE�tEQUIRED. b.Is this property within 300 feet of a tidal wetland? *-YES NO �/ *IF YES,D.E.C. PERMITS MAY BE REQUIRED. 16.Provide survey,to scale,with accurate foundation plan and distances to property lines. 17. If elevation at any point on property is at 10 feet or below,must provide topographical data on survey. 18:Are there any covenants and`restrictions-with-respect to this property? *YES NO * IF YES,PROVIDE A COPY. STATE OF NEW'YORK) SS: COUNTY OF being duly sworn,deposes and says that(s)he is the applicant (Name of individual signing contract)above named, CONNIE D.BUNCH Notary Public,State of New York (S)He is the No.01SU6185050 (Contractor,Agent,Corporate Officer,etc.) Qualified in Suffolk County Commission Expires April 14,2 of said owner or owners,and is duly authorized to perform or have performed the said work and to make and file this application, that all statements contained in this application are true to the best of his knowledge and belief;and that the work will be performed in the manner set forth in the application filed therewith. 1 Swo to efore me day of 'v 20 Notary Public v Signature o Applicant a BUILDING DEPARTMENT-Electrical Inspector < Lir, TOWN OF SOUTHOLD Town Hall Annex- 54375 Main Road - PO Box 1179 Lv T x- � a> �. Southold, New York 11971-0959 .17 Telephone (631) 765-1802 - FAX (631) 765-9502 111rogerro-)southoldtownny aov -• seand@southoldtownny.gov APPLICATION FOR ELECTRICAL INSPECTION ELECTRICIAN INF RMATION (All Information Required) Date: Company Name: - Name: License No.: Gly/ email: Address: Afd "I C / �L Phone No.: S r 36 JOB SITE INFORMATION (All Information Re uired) Name: Address: Dn �„7b Cross Street: Phone No.: 'Bldg.Permit* If5 email: Tax Map District: 1000 Section: b D•aU Block: 4 Lot: 2 C ,Ca BRIEF DESCRIPTION OF WORK(Please Print Clearly) Circle All That Apply: Is job ready for inspection?, YES / NO Rough In Final Do you need a Temp Certificate?: YES / NO Issued On Temp Information: (All information required) Service Size 1 Ph 3 Ph Size: A #Meters Old Meter# New Service - Fire Reconnect-Flood Reconnect-Service Reconnected - Underground - Overhead #Underground Laterals 1 2 H Frame Pole Work done on Service? Y N Additional Information: PAYMENT DUE WITH APPLICATION Request for Inspection Form xls ��aSUfFOC4 C4k BUILDING DEPARTMENT-Electrical Inspector TOWN OF SOUTHOLD 1 Town Hall Annex- 54375 Main Road - PO Box 1179 o = Southold, New York 11971-0959 Telephone(631)-765-1802- FAX(631) 765-9502 ° roger[a southoldtownn . ov seand southoldtownn . ov APPLICATION FOR ELECTRICAL INSPECTION ELECTRICIAN INF RMATION (Ail Information Required) Date: /0 -,/3 �p Company Name: mhk4oxi ' Name: 17 f License No.; email: L e-,C 17/C Q6 r-00 Address: -d,(Ih l �'/ jeA, Phone No.: JOB SITE INFORMATION (All Information R uired) Name: �•mp �•/Mp'r / Address: 40- /,-74- -, d V Cross Street: Phone No.. r tom- Bldg.Permit#: _.._ ;��7 ) email: ••lS�rras>�UCe.r �f 2 orJ Tax Map,District: 1000, Section: �.,ap Block: Lot: BRIEF DES�C-RnIPT16N OF WORK�(Please-Print Clearly) Circle All That Apply: Is job ready for inspection?: YES / N Rough In Final Do you need a Temp Certificate?: YES / NO Issued On Temp Information: (All information required) Service Size 1 Ph 3 Ph Size: A #Meters Old Meter# New Service- Fire Reconnect-Flood Reconnect-Service Reconnected-Underground-Overhead #Underground Laterals 1 2, H Franie Pole Work done on Service? Y N Additional information: PAYMENT DUE WITH APPLICATION Request for Inspection ForTnAs — / — PERMIT# Address: Switches Outlets GFI's Surface Sconces HH's UC Lts Fans Fridge HW Exhaust Oven Dryer Smokes QW Service Carbon - Micro Generator VV �- Q Combo Cooktop Transfer AC AH Mini Y Special: Comments. l• Bunch, Connie From: Barry Wiseman <bwiseman@optonline.net> Sent: Friday, October 16, 2020 11:34 AM To: Bunch, Connie Subject: Re: Generator placement Attachments: Electric inspection application.pdf Our generator model is Generac 70432, 22kW. Application for electrical inspection is attached. Thanks, Barry Wiseman On 8/21/2020 10:36 AM, Bunch, Connie wrote: , That location is fine per Damon Rallis, Plans Examiner. Best Regards, Connie Bunch Southold Town Building Dept. From: Barry Wiseman [mailto:bwiseman@optonline.netl _ Sent: Friday,August 21, 2020 10:28 AM To: Bunch,Connie<Connie.Bunch @town.southold.ny.us> Cc: Rena<wisebodv@verizon.net> Subject: Generator placement Here is the proposed generator site my wife just discussed with you. There is a landscaped stand of trees and bushes there, the generator would not be at all visible from the road. i Z ° VIP .401 ow � •f`+ _ °�',� '�.$f� ear y d� .aP' Z7----T IJ'+°n �.( 'fit . Y'�l� •t �� Ah r a l r ri ° 6 F p I E*3rait7�a� }I�d�fl fiJ•TF'�'�i �,,�Ci!}� �i'7IQ»�I(14 . lr ab7 APPROVED AS NOTED DATE: B.P.#_L16_ 3 COMPLY WITH ALL CODES OF FEE NOTIFY BUILDING DEPARTMENT AT NEW YORK STATE & TOWN CODES 765-1802 8 A TO 4 P FOR THE AS REQUIRED AND CONDITIONS OF FOLLOWING INSPECTIONS: QI17UINlvt94 _ 1. FOUNDATION - TWO REQUIRED t 11 -FOR POURED CONCRETE ) 7UWWFtAM#dI30ARD 2. ROUGH -FRAMING FRAMING & PLUMBING S W'N TRUSTEES 3. INSULATION 4. FINAL - CONSTRUCTION MUST -® N BE COMPLETE FOR C.O. ALL CONSTRUCTION SHALL MEET THE REQUIREMENTS OF THE CODES OF NEW YORK STATE. NOT RESPONSIBLE FOR DESIGN OR CONSTRUCTION ERRORS. ELECTRICAL OCCUPANCY OR INSPECTION REQUIRED USE IS UNLAWFUL WITHOUT CERTIFICATE OF OCCUPANCY 10/16/2020 Generac Guardian 70432®22kW Standby Generator System 200A Service Disconnect+AC Shedding w/Wi-Fi ELECTRIC GENERATORS p Deliver to 11971 t�801Q1- Location "800-Help L/ Chance 3317 Portable Home Standby Commercial RV PTO Transfer Switches Accessories How-To Library Specials Essential Business Delays:Get order status&support now. Home/Shop by Brand/Generac Guardian/70432 ' _- "tG-',-'#,:-'�:-_ --•:i�-���mn,/r�c-�,^�4': ;�r,n,?' ^"a,�r,> ra'fa.��•t^s:E�7"i�'y�';"'a*,, .�•:' -:..`+z%.?�; ,-r;,'.,,�4V'zm.x ;r(. ,.i.k; :••ax,>t�'"^". ^;sr �<, .t -�i•-•. 7J-r v.4:.� � ,r:�''�,c�i. ro xf r sr 'b „-r;'•"_a.y-� " �� �� 'lir =-`•'sc c R1, ✓�;,n rJJ d}e.,.._�" _4 +>a5,-r.�..�„ K,r...,�'P,- tiz =r��...-`+;?a:- ;d,'' ;":-,•if;. ��,,.rV.. ..1• .` a.&.:;k;:., .! .�x�r �, F� iJ+k_, _i�.r s'�?':':;-•`'�^ <:C,,,,.� "vT- L,,y4j-,. .,►- -+,.4i __ . • ...�. �-_ij:"_..r.,r:v-�-a +�a^^cy.,ti�ar�;'L:r _S�kW"L-.°.'�"n0.''_�:'x�''Si!x�F+�-'ii:�caY;%�rzz ��:..i,r�,a_:-,ks�r�:;xrL,_!.<:�:.?�r%`v=e:S��y"•=n:Lrh+_•<,-•.�,t-;:?."a.•.t..�.:,�y;::�s_" .h',_a�}"%�'.,'r_-s_ . Generac Guardian® 22kW Standby Generator System (200A Service .._ r Disconnect +AC Shedding) w/ Wi-Fi y" p " Model:70432 GENERAC- **7 Write a ' Q&A — --, Ke (81) Review (11) r ---------- --- - — -— --- - - - -- - •• a Hover to zoom -$50047.00 Free Shipping&Lift Gate 0 ,�'s�ttrrrMvt7r - Backordered r Estimated Availability January 27,2021 'Shipping to 11971 Update Shipping Details Notify Me When In-Stock 0 View All Email Address � -' Remind Me �,� Standby Towable Skid Mount Light Towers Mobile Popular Brands Shop By Fuel Type Shop By Voltage Briggs&Stratton Propane(LP) 120/2401 P Cummins Natural Gas 120/240 313 Generac Diesel 120/208 3P r https://www.electricgeneratorsdirect.com/Generac-Guardian-70432-Standby-Generatorlp82547.html 1/6 10/16/2020 Generac Guardian 70432®22kW Standby Generator System 200A Service Disconnect+AC Shedding w/Wi-Fi ELIECTRIC dENERATORS Call ®Deliver to 11971 �s Q ' Change Location "8000-Help -U ng 3317 Portable Home Standby Commercial RV PTO Transfer Switches Accessories How-To Library Specials Product Reviews Product Q&A Recommended How-To Manuals Artinlnc Description Grade Style Run Watts Voltage Fuel Engine r ' ZZi��� 120/240 (A'117 " Rated Watts Single-Phase Why You Need a'Home Standby Gen... Specifications Product Specs Voltage 120/240 Single-Phase v Frequency 60 Hertz ---Rated-Watts ___-__---22000-Watts------ ----------------- Fuel Type LP/Natural Gas NG Power Capacity 19500 Watts LP Power Capac"tty 22000 Watts NG Fuel Consumption @ 228 ft'/hr Product Video Disclaimer.'PED isnot responsible for 50%Load any variances from the product in this video and the item you purchase.Please review all product specs NG Fuel Consumption @ 327 ft'/hr prior to purchase" 100%toad r LP Fuel Consumption @ 2.53 gallons/hr Features 50%Load r . g Standby Towable Skid Mount Light Towers Mobile Popular Brands Shop By Fuel Type Shop By Voltage Briggs&Stratton Propane(LP) 120/2401 P Cummins Natural Gas 120/240 3P Generac Diesel'' 120/208 3P ' httpsl/www.electricgeneratorsdirect.com/Generac-Guardian-70432-Standby-Generatorlp82547.html 216 10/16/2020 Generac Guardian 70432®22kW Standby Generator System 200A Service Disconnect+AC Shedding w/Wi-Fi RECTRI VENERATORS Call ®Deliver to 119716000-Help L/ �' EC Chancre Location 3317 Portable Home Standby Commercial RV PTO Transfer Switches Accessories How-To Library Specials Separately) ----------- -------------o[�is[erl--- ---- ------------mss----- • Frequency(Hz)monitoring design,no control wire required Grade Type Emergency --- -- ----•--Versatile-desi n,easily-prioritize-loads g &-lock-out non-- -- - -------_------_--. essential loads Wi-Fi Remote Monitoring Yes 5-Year Limited Warranty+24/7-365 Customer Support Engine ave-your-,questions-answered-when-it's-convenient-for-yD ----- — -- -- Engine Brand Generac OHVI Generac's G-Force Engine Starting System 12v Auto Start • Specifically designed for the demanding environment ------- -- ------------- standby generators endure cc 999 CC • Full pressure lubrication system w/2 year oil change Consumer Engine 5 Years — interval Warranty Operates On Clean Burning,Efficient Natural Gas or LP Commercial Engine 5 Years (Vapor) Warranty — • Connects to your existing LP or natural gas fuel supply Engine RPM 3600 RPM Low Oil Alert/Shutdown Yes True Power'Electrical Technology — • Less than 5%Total Harmonic Distortion(THD)-for utility --gradepower-- - -- -- -- - - - -- --- -- - — Overview-— - - Automatic Digital Voltage Regulation(+/-l%) Weight _ --_ 466 Pounds -- --- • Allows for faster response time&maximum motor starting Made in USA Yes ability --- —- ------ ------- Consumer Warranty 5 Years Evolution"2.0 Digital Controller Commercial Warranty 5 Years • Multilingual,2-Line LCD display for simple,straightforward Product Style Standby Generator - operation - ------------ - -- --- ---- -- • Programmable-exerciser lets you set how often&what Product Length 48 Inches time generator will self-test Product Width 25 Inches - � t 1 Standby Towable Skid Mount Light Towers Mobile Popular Brands Shop By Fuel Type Shop By Voltage Briggs&Stratton Propane(LP) 120/240-1 P Cummins Natural Gas 120/240 3P • r Generac Diesel 120/208-3P https:/www-electricgeneratorsdirebt.com/Generac-Guardian-70432-Standby-Generatorlp82547_htmi 3/6 GENERALMMEMMMMEM mla ® Installation Guidelines 60 Hz Air-Cooled Generators 9 kW to 22 kW 0 Loss of life.This product is not intended to be used in a critical life support application. Failure to adhere to this warning could result in death or serious injury. (000209b) I Register your Generac product at: WWW.GENERAC.COM 1-888-GENERAC (888-436-3722) Para espanol, visita: http://www.generac.com/service-supporUproduct-support-lookup Pour le frangais, visiter: http://www generac.com/service-support/product-support-lookup Use this page to record important information about this generator. Record the information found on the unit data label on this Model: page. For location of the unit data label, see owner's manual. The unit has a label plate affixed to the inside partition, to the left of the control panel console Serial: Always supply the complete model and serial numbers of the unit when contacting an Independent Authorized Service Prod Date Week Dealer(IASD)about parts and service. Operation and Maintenance: Correct maintenance and care of the generator ensures a minimum number of prob- Volts: lems and keeps operating expenses at a minimum. It is the operator's responsibility to perform all safety checks, to ver- ify all maintenance for safe operation is performed promptly, LPV Amps: and to have the equipment inspected periodically by an IASD. Normal maintenance, service, and replacement of parts are the responsibility of the owner/operator and are not NG Amps: considered defects in materials or workmanship within the terms of the warranty. Individual operating habits and usage may contribute to the need for additional maintenance or ser- Hz: vice. When the generator requires servicing or repairs, Generac Phase. recommends contacting an IASD for assistance.Authorized service technicians are factory-trained and are capable of handling all service needs. To locate the nearest IASD, Controller P/N: please visit the dealer locator at: www.generac.com/ServicelDea/erLocatorl. ,&WARNING CANCER AND REPRODUCTIVE HARM www.P65Warnings.ca.gov. (000393a) ii Installation Guidelines for 60 Hz Air-Cooled Generators Table of Contents Section 1: Safety Rules & General - Proximity to Utilities ...........................................17 Information Verify Wi-Fi Range .. ................................................17 Introduction ..........................................................1 Transportation Recommendations ..................17 Read This Manual Thoroughly ....................................1 Suitable Mounting Surface ...............................17 Safety Rules .............................................:...........1 Placement on Roofs, Platforms, and Other How to Obtain Service .................................................1 Supporting Structures ......................................17 General Hazards ..................................................2 Exhaust Hazards ..................................................3 Section 4: Generator Placement Electrical Hazards ................................................3 Generator Placement ........................................19 Fire Hazards .........................................................3 Fascia Installation (If Applicable) .....................19 Explosion Hazards ...............................................4 Battery Hazards ...................................................4 Section 5: Fuel Conversion/Gas General Rules .......................................................5 Connections Before You Begin ........................................................5 Fuel Requirements and Recommendations ....21 NEC Requirements ......................................................5 BTU Content .................... ........................................21 Standards Index ..........................................................5 Fuel Pressure ............................................................21 Fuel Conversion ................................................21 Section 2: Unpacking and Inspection Fuel Consumption .............................................22 General .................................................................7 Fuel Line Sizing .................................................22 Required Tools .....................................................7 Natural Gas Pipe Sizing ............................................23 Unpacking ............................................................7 LP Gas Pipe Sizing ...................................................23 Opening the Lid ...........................................................8 Installing and Connecting Fuel Lines ..............24 Enclosure Panel Removal ...................................8 Fuel Shutoff Valve .....................................................24 Remove Front Access Panel .......................................8 Flexible Fuel Line ......................................................24 Intake Side Panel Removal .........................................9 Sediment Trap ...........................................................24 Customer Connections and Loose Parts ..........9 Checking Fuel Line Connections .....................25 Rear Connections ................................................9 Checking Fuel Pressure ............................................25 Generator Main Line Circuit Breaker ...............10 Performing Fuel System Leak Test ...........................25 Parts Shipped Loose 10 Natural Gas Installation (Typical) .....................26 Auxiliary Shutdown Switch ........11 LP Gas (Vapor) Installation (Typical) ...............27 ....................... Section 3: Site Selection and Preparation Section 6: Electrical Connections Site Selection .....................................................13 Generator Connections ......................................29 Carbon Monoxide ..............................................13 Control Wiring ....................................................30 Carbon Monoxide Detectors ..........................13 Main AC Wiring ..................................................31 Potential CO Entry Points 14 Service Entrance Decals ...................................31 Protect the Structure .................................................14 Common Alarm Relay (Option) ........................31 Fire Prevention ...................................................15 Battery Requirements .......................................31 Distance Requirements .............................................15 Battery Installation ............................................32 Fire Codes, Standards, and Guidelines .....................16 Connecting Battery ....................................................32 Generator Maintenance .............................................16 Battery Disposal ................................................32 Fresh Air for Ventilation and Cooling ..............17 Water Ingress Avoidance ..................................17 Installation Guidelines for 60 Hz Air-Cooled Generators iii Table of Contents Section 7: Control Panel Startup/Testing ` Control Panel Interface .....................................33 Using the AUTO/MANUAL/OFF Buttons ....... .........33 Generator Setup .................................................33 Activation ...... . ....................................... ............ ...33 Cold Smart Start ........... ...........................................35 Setting The Exercise Timer .................................. ....35 Before Initial Startup .........................................35 Install Wizard ................ ...........................................35 Interconnect System Self Test Feature .....................36 Before starting, complete the following: .................. .36 Checking Manual Transfer Switch Operation ............................................................39 Electrical Checks ...............................................39 Generator Tests Under Load ............................39 Checking Automatic Operation ........................40 Installation Summary ........................................40 Shutting Generator Down While Under Load or During a Utility Outage ........................40 Section 8: Troubleshooting Generator Troubleshooting ..............................43 Section 9: Quick Reference Guide System Diagnosis ..............................................45 Section 10:Accessories Section 11: Diagrams Installation Drawing (10000010258 rev B-1 of 2) ...49 Installation Drawing (10000010258 rev B-2 of 2) ...50 iv Installation Guidelines for 60 Hz Air-Cooled Generators Safety Rules & General Information Section 1. Safety Rules & General Information Introduction Safety Rules Thank you for purchasing this compact, high perfor- The manufacturer cannot anticipate every possible cir- mance, air-cooled, engine-driven generator. It is cumstance that might involve a hazard. The alerts in this designed to automatically supply electrical power to oper- manual, and on tags and decals affixed to the unit, are ate critical loads during a utility power failure. not all inclusive If using a procedure, work method, or This unit is factory installed in an all-weather, metal operating technique that the manufacturer does not spe- enclosure intended exclusively for outdoor installation. cifically recommend, verify that it is safe for others and This generator will operate using either vapor withdrawn does not render the equipment unsafe. liquid propane (LP)or natural gas (NG). Throughout this publication, and on tags and decals NOTE: When sized correctly, this generator is suitable affixed to the unit, DANGER, WARNING, CAUTION, and for supplying typical residential loads such as induction NOTE blocks are used to alert personnel to special motors (sump pumps, refrigerators, air conditioners, instructions about a particular operation that may be haz- furnaces, etc.), electronic components (computer, ardous if performed incorrectly or carelessly Observe monitor, TV, etc.), lighting loads, and microwaves. This them carefully.Alert definitions are as follows: unit is also equipped with a Wi-Fio module, which enables the generator owner to monitor generator status ! from anywhere they have Internet access. Indicates a hazardous situation which, if not avoided, NOTE: Wi-Fi® is a registered trademark of Wi-Fl will result in death or serious injury. Alliance. The information in this manual is accurate based on (000001) products produced at the time of publication. The manu- facturer reserves the right to make technical updates, , corrections, and product revisions at any time without Indicates a hazardous situation which, if not avoided, notice. could result in death or serious injury. Read This Manual Thoroughly (000002) '�t,ItAl�Nl ,�R Consult Manual. Read and understand manual Q,,GAUTION completely before using product. Failure to Indicates a hazardous situation which, if not avoided, completely understand manual and product could result in minor or moderate injury. could result in death or serious injury.(000100a) (000003) If any section of this manual Is not understood, contact the nearest Independent Authorized Service Dealer NOTE: Notes contain additional information important to (IASD) or Generac Customer Service at 1-888-436-3722 a procedure and will be found within the regular text of (1-888-GENERAC), or visit www.generac.com for start- this manual. ing, operating, and servicing procedures. The owner is These safety alerts cannot eliminate the hazards that responsible for correct maintenance and safe use of the unit. they indicate. Common sense and strict compliance with the special instructions while performing the action or This manual must be used in conjunction with all other service are essential to preventing accidents. supporting product documentation supplied with the product SAVE THESE INSTRUCTIONS for future reference This How to Obtain Service manual contains important instructions that must be fol- When the unit requires servicing or repairs, contact Gen- lowed during placement, operation, and maintenance of erac Customer Service at 1-888-GENERAC (1-888-436- the unit and its components Always supply this manual 3722) or visit www.generac.com for assistance. to any individual that will use this unit. When contacting Generac Customer Service about parts and service, always supply the complete model and serial number of the unit as given on its data decal located on the unit. Record the model and serial numbers Installation Guidelines for 60 Hz Air-Cooled Generators 1 Safety Rules & General Information in the spaces provided on the front cover of this manual. General Hazards Electric shock. Only a trained and licensed electrician should perform wiring and connections to unit. Failure to follow proper installation requirements could result in 102ZOAAdeath,serious injury, and equipment or property damage. (000155a) Loss of life. Property damage. Installation must always comply with applicable codes, standards, laws and regulations. Failure to do so will result in death �► � - or serious injury.ry� (000190) Moving Parts. Do not wear jewel rywhen starting or operating this product. Wearing jewelry while starting or operating this product i could result in death or serious injury. (000115) Automatic start-up. Disconnect utility power and render unit inoperable before working on unit Failure to do so will result in death or serious injury. (000191) Moving Parts. Keep clothing, hair, and appendages away from moving parts. Failure to do so could result in death or serious injury. (000111) Electrocution.Potentially lethal voltages are generated by this equipment.Render the equipment safe beforea- WA �, .u, ., attempting repairs or maintenance. Failure to do so could result in death or serious injury. Hot Surfaces. When operating machine, do not (000187) 21'Emim". touch hot surfaces. Keep machine away from combustibles during use. Hot surfaces could 1N1�RNO result in severe burns or fire. (000108) Loss of life.This product is not intended to be used in a critical life support application. Failure to adhere to this warning could result ;Q,,VUANN1 in death or serious injury. (000209b) Equipment and property damage. Do not alter construction of, installation, or block ventilation for * 9_Mi _ generator. Failure to do so could result in unsafe Aoperation or damage to the generator. (000146) Accidental Start-up. Disconnect the negative battery cable, then the positive battery cable when working ti on unit. Failure to do so could result in death NJ or serious injury. (000130) Risk of injury. Do not operate or service this machine if not fully alert. Fatigue can impair the ability to service a a - this equipment and could result in death or serious injury (000215) .,AWAFNII Equipment damage.Only qualified service personnel may install,operate,and maintain this equipment. Failure to follow proper installation requirements could result in death,serious .a 090 injury, and equipment or property damage. Environmental Hazard.Always recycle batteries at an (000182a) official recycling center in accordance with all local laws and regulations. Failure to do so could result in environmental damage, death or serious injury. (000228) Equipment damage.This unit is not intended for use as a prime power source. It is intended for use as an intermediate power supply in the event of temporary power outage only. Doing so could result in death, serious injury,and equipment damage. (000247a) Injury and equipment damage. Do not use generator as a step. Doing so could result in falling, damaged parts, unsafe equipment operation, and could result in death or serious injury. (000216) 2 Installation Guidelines for 60 Hz Air-Cooled Generators Safety Rules & General Information • Inspect the generator regularly, and contact the nearest IASD for parts needing repair or replace- ! - ment. Electrocution. Verify electrical system is properly grounded before applying power. Exhaust Hazards Failure to do so will result in death or serious injury. (000152) Asphyxiation. Running engines produce ! carbon monoxide, a colorless, odorless, poisonous gas. Carbon monoxide, if not A Electrocution. Do not wear jewelry while avoided,will result in death or serious injury. working on this equipment. Doing so will (000103) result in death or serious injury. (000188) Equipment and property damage. Do not alter ! construction of, installation, or block ventilation for ower Electrocution. Water contact with a generator. Failure to do so could result in unsafe p operation or damage to the generator. source, if not avoided, will result in death (000146) or serious injury. (000104) Asphyxiation.Always use a battery operated carbon ! monoxide alarm indoors and installed according to A Electrocution. In the event of electrical accident, the manufacturer's instructions. Failure to do so immediately shut power OFF. Use non-conductive could result in death or serious injury. implements to free victim from live conductor.Apply (000178a) first aid and get medical help. Failure to do so will • The generator must be installed and operated out- result in death or serious injury. (000145) doors only. Fire Hazards Electrical Hazards , o / ;�,4i!�RN,1do 1I'II Fire risk. Fuel and vapors are extremely Electrocution. Contact with bare wires, flammable. Do not operate indoors. Doing so terminals, and connections while generator could result in death, serious injury, or is running will result in death or serious injury. property or equipment damage. (000281) (000144) WAR d A& W F!191 Fire hazard. Do not obstruct cooling and Not Electrocution. Never connect this unit to the electrical ventilating airflow around the generator. Inadequate system of any building unless a licensed electrician ventilation could result in fire hazard, possible has installed an approved transfer switch Failure to equipment damage, death or serious injury. (000217) do so will result in death or serious injury (000150) Fire and explosion. Installation must comply Electrical backfeed. Use only approved switchgear to with all local, state, and national electrical isolate generator from the normal power source building codes. Noncompliance could result in unsafe Failure to do so will result in death, serious injury, operation, equipment damage, death or serious injury. and equipment damage (000218) (000237) Installation Guidelines for 60 Hz Air-Cooled Generators 3 Safety Rules & General Information ,�,V1a��1RNiN,G .�. � ;/�►11V}�R�+f1NV�, Fire hazard. Use only fully-charged fire Risk of Fire. Hot surfaces could ignite extinguishers rated "ABC"by the NFPA. Discharged or combustibles, resulting in fire. Fire could improperly rated fire extinguishers will not extinguish result in death or serious injury. electrical fires in automatic standby generators. (000110) (000219) gW1Rrd1N . Battery Hazards Electrocution. Refer to local codes and standards for safety equipment required when working with a live electrical system. Failure ! ' to use required safety equipment could result in death or serious injury. (000257) � Electrocution. Do not wear jewelry while working on this equipment. Doing so will p �., ,.a,. result in death or serious injury. � (000188) Risk of Fire. Unit must be positioned in a manner that prevents combustible material accumulation underneath. Failure to do soair could result in death or serious injury. (000147) Explosion.Do not dispose of batteries in a fire.Batteries 44are explosive. Electrolyte solution can cause burns and Comply with regulations the Occupational Safety and blindness.If electrolyte contacts skin or eyes,flush with water Health Administration (OSHA) has established, or with and seek immediate medical attention. (000162) equivalent standards.Also, verify that the unit is applied, used, and maintained in accordance with the manufac- turer's instructions and recommendations. Do nothing ,�; URNNG that might alter safe application/usage and render the . Explosion.Batteries emit explosive gases while charging unit in noncompliance with the aforementioned codes, Keep fire and spark away.Wear protective gear when standards, laws, and regulations. working with batteries Failure to do so could result in death or serious injury (000137a) Explosion Hazards gWA�k�tYISN�`. ! Electrical shock. Disconnect battery ground Explosion and fire. Fuel and vapors are extremely terminal before working on battery or battery wires. Failure to do so could result in death flammable and explosive. No leakage of fuel is or serious injury. 000164 permitted. Keep fire and spark away. Failure to do ( ) so will result in death or serious injury. (000192) �AWAA- �, .- i Risk of burns. Batteries contain sulfuric acid and Explosion and fire. Connection of fuel source must be can cause severe chemical burns. Wear protective completed by a qualified professional technician or gear when working with batteries. Failure to do contractor. Incorrect installation of this unit will result in so could result in death or serious injury(000138a) death,serious injury,and property and equipment damage. (000151a) � Risk of burn. Do not open or mutilate batteries. . Batteries contain electrolyte solution which can Risk of fire.Allow fuel spills to completely dry cause burns and blindness. If electrolyte contacts before starting engine. Failure to do so will skin or eyes,flush with water and seek immediate result in death or serious injury. medical attention (000163a) (000174) 4 Installation Guidelines for 60 Hz Air-Cooled Generators Safety Rules & General Information • Always consult local code for additional require- dhments for where unit is being installed. Environmental Hazard.Always recycle batteries at an Incorrect installation can result in personal injury official recycling center in accordance with all local and damage to the generator. It may also result in laws and regulations. Failure to do so could result in the warranty being suspended or voided. All environmental damage, death or serious injury. instructions listed below must be followed including (000228) location clearances and pipe sizes. Always recycle batteries in accordance with local laws and regulations. Contact your local solid waste collection Before You Begin site or recycling facility to obtain information on local • Contact local inspector or city hall to be aware of all recycling processes. For more information on battery federal, state, and local codes which could impact recycling, visit the Battery Council International website installation. Secure all required permits before at: http://batterycouncii.org installing. • Fully comply with all relevant NEC, NFPA, and General Rules OSHA standards, as well as all federal, state, and local building and electric codes. This unit must be installed in accordance with current NFPA 37 and I NFPA 70 standards, and any other federal, state, Loss of life. Property damage. Installation must always and local codes for minimum distances from other comply with applicable codes, standards, laws and structures. regulations. Failure to do so will result in death Verify capacity of NG meter or LP tank in regards or serious injury. (000190) to providing sufficient fuel for both the generator and other household and operating appliances. NEC Requirements Electrical backfeed. Use only approved switchgear to Local code enforcement may require Arc Fault Circuit isolate generator from the normal power source. Failure to do so will result in death, serious injury, Interrupters (AFCIs) to be incorporated into the transfer and equipment damage. switch distribution panel. The transfer switch provided (000237) with this generator has a distribution panel which will accept AFCIs (pre-wired transfer switches only). , AR i� Siemens Part No. Q115AF - 15A or Q120AF - 20A can yx be obtained from a local electrical wholesaler and will Equipment damage. Only qualified service personnel may install,operate,and maintain this equipment. Failure to follow simply replace any of the single pole circuit breakers sup- proper installation requirements could result in death,serious plied in the pre-wired transfer switch distribution panel. injury,and equipment or property damage. (000182a) Standards Index � 41 "2"I[fiG Electrocution. Refer to local codes and '�" ` -A standards for safety equipment required when Loss of life.This product is not intended to working with a live electrical system. Failure be used in a critical life support application. to use required safety equipment could result Failure to adhere to this warning could result in death or serious injury. (000257) in death or serious injury. (000209b) Strictly comply with all applicable national, state, and �1AITI local laws, as well as codes or regulations pertaining to Consult Manual. Read and understand manual the installation of this engine-generator power system. completely before using product. Failure to Use the most current version of applicable codes or stan- completely understand manual and product dards relevant to the local jurisdiction, generator used, could result in death or serious injury.(000100a) and installation site. • Follow all safety precautions in the owner's man- NOTE: Not all codes apply to all products and this list is ual, installation guidelines manual, and other docu- not all-inclusive. In the absence of pertinent local laws ments included with the equipment. and standards, the following publications may be used as • Never energize a new system without opening all a guide (these apply to localities which recognize NFPA disconnects and breakers. and IBC) Installation Guidelines for 60 Hz Air-Cooled Generators 5 Safety Rules & General Information 1. National Fire Protection Association (NFPA) 70: The NATIONAL ELECTRIC CODE (NEC) 2. NFPA 10: Standard for Portable Fire Extinguishers * 3. NFPA 30: Flammable and Combustible Liquids Code* 4. NFPA 37: Standard for Stationary Combustion Engines and Gas Turbines* 5. NFPA 54: National Fuel Gas Code 6. NFPA 58: Standard for Storage and Handling Of Liquefied Petroleum Gases* 7. NFPA 68: Standard On Explosion Protection By Deflagration Venting * 8. NFPA 70E. Standard For Electrical Safety In The Workplace* 9. NFPA 110: Standard for Emergency and Standby Power Systems* 10. NFPA 211: Standard for Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances * 11. NFPA 220: Standard on Types of Building Construction * 12. NFPA 5000: Building Code 13. International Building Code** 14. Agricultural Wiring Handbook*** 15. Article X, NATIONAL BUILDING CODE 16. ASAE EP-364.2 Installation and Maintenance of Farm Standby Electric Power**** 17. ICC:IFGC This list is not all-inclusive. Check with the Authority Hav- ing Local Jurisdiction (AHJ) for any local codes or stan- dards which may be applicable to your jurisdiction. The above listed standards are available from the following internet sources: * www.nfpa.org ** www.iccsafe.org ***www.rerc.org Rural Electricity Resource Council P.O. Box 309 Wilmington, OH 45177-0309 **** www.asabe.org American Society of Agricultural & Biological Engineers 2950 Niles Road, St Joseph, MI 49085 6 Installation Guidelines for 60 Hz Air-Cooled Generators _ Unpacking and Inspection Section 2: Unpacking and Inspection,_ General Unpacking NOTE: Carefully inspect contents for damage after 1. Remove outer shipping carton. unpacking. Unpack and inspect unit immediately upon 2. See Figure 2-9. Remove wood frame. delivery to identify any damage which may have occurred in transit. Any claims for shipping damage need to be filed as soon as possible with freight carrier.This is espe- cially important if unit will not be installed for a period of time. • This standby generator is ready for installation with a factory supplied and pre-mounted base pad and has a weather protective enclosure intended for outdoor installation only. • If any loss or damage is noted at time of delivery, have delivery person(s) note all damage on the freight bill, or affix their signature under consignor's memo of loss or damage. • If a loss or damage is noted after delivery, separate damaged materials and contact carrier for claim procedures. • "Concealed damage" is understood to mean dam- 000427 age to contents of a package not evident at time of delivery, but discovered later. Figure 2-9. Crated Generator Required Tools 3. See Figure 2-2. Lid will be locked.A set of keys is attached to the cardboard sheet on top of unit.An • General SAE and Metric hand tools additional set is attached to pallet bracket on the —Wrenches front intake end of the unit. Remove keys from — Sockets cardboard and pallet bracket. — Screwdrivers • Standard electrician's hand tools — Drill and bits for mounting and routing conduits • 4 mm hex key (for access to customer connec- tions) • 3/16 in hex key (test port on fuel regulator, and E1/ E2/N/G electrical wiring connections) • Manometer(for fuel pressure checks) • Meter capable of measuring AC/DC voltage ander frequency 006729 • Torque wrenches Figure 2-2. Keys As Shipped NOTE: The enclosed keys provided with this unit are intended for service personnel only. Installation Guidelines for 60 Hz Air-Cooled Generators 7 Unpacking and Inspection IMPORTANT NOTE: DO NOT perform next step until Enclosure Panel Removal generator has been transported to installation site. Generator installation requires removal of front panel and 4. See Figure 2-3. Remove bolts and pallet brackets intake side panel Remove these panels when neces- (A). Exercise caution when removing generator. sary. Proceed as follows to remove the panels. Dragging it off pallet will damage base. The unit must be lifted from wooden pallet to remove. Remove Front Access Panel NOTE: Bolts and pallet brackets are provided only for See Figure 2-5. Remove front access panel (A) by lifting shipping purposes and can be discarded after removal. straight up and out once lid is open. NOTE: Always lift front access panel straight up before pulling away from enclosure (B and C). Do not pull panel away from the enclosure before lifting up (D). O 0 A 0® A 000426 Figure 2-3. Pallet Bracket Locations Opening the Lid 1. Use keys to open generator lid. �O 2. See Figure 2-4. Two locks (A) secure lid; one on each side. Press down on lid above side lock, and unlock latch to correctly open lid. p O �4 0 o® A O 009209 Figure 2-4. Opening the Lid 3. Repeat for other side. Lid may appear stuck if pres- sure is not applied from the top. NOTE: Always verify side locks are unlocked before attempting to lift lid. 009210 Figure 2-5. Remove Front Access Panel 8 Installation Guidelines for 60 Hz Air-Cooled Generators Unpacking and Inspection Intake Side Panel Removal Customer Connections-and Loose See Figure 2-6. The intake side panel (A) must be Parts removed to access battery compartment, fuel regulator, See Figure 2-7 and Figure 2-8 for customer connections and sediment trap. and loose parts location. Figure 2-10 illustrates parts 1. Raise lid and remove front panel. shipped loose. 2. Use a hex key to remove two mounting screws (B) and the hex screw on the L-bracket. 3. Lift intake panel up and away from generator. E 4. Inspect for any hidden freight damage. Contact o freight carrier if damage is present. NOTE: Always lift intake side panel straight up before 00 pulling away from enclosure. Do not pull panel away from enclosure before lifting up (D). Co - T� -�' B o e '0 ! ! A D ' B 001600 A Customer electrical connection area (behind access panel) B Fuel regulator with sediment trap C C Battery compartment(battery not supplied) D Positive(+)and negative(-)battery cables e o E Location of"Loose Shipped Parts" OFigure 2-7. Customer Connection Area and Loose Parts Location Rear Connections E A __ II Figure 2-6. Intake Side Panel Removal 002961 B�® 0o � � C D ® 001602 A Wi-Fi module B Main AC/Control wiring hole for 1-1/4 in conduit C Main AC/Control wiring hole for 3/4 in conduit D Fuel connection hole E Auxiliary shutdown switch Figure 2-8. Rear Connections NOTE: The generator is equipped with a Wi-Fi module. See Wi-Fi module owner's manual for further instruction. Installation Guidelines for 60 Hz Air-Cooled Generators 9 Unpacking and Inspection Generator Main Line Circuit Breaker Parts Shipped Loose See Figure 2-9. The 2-pole circuit breaker (generator disconnect) (A) is rated according to relevant specifica- tions. 00 II � 001803 A Keys B '4 a �001810 B Flexible fuel line C Battery terminal cap Figure 2-9. Generator Main Line Circuit Breaker D Rubber mounts (only for units including fascia) Breaker can be locked in OFF (OPEN) position for secu- E Fascia(if applicable) rity during maintenance or transfer switch service. Use F Decal—Service entrance warning(not shown) an appropriately-sized padlock (not included) with a shackle long enough to pass through both lock tabs (B). G Decal—Through conductors warning(not shown) H j Decal—Service disconnect(not shown) NOTE: DO NOT leave breaker disconnect locked in the OFF(OPEN) position during normal generator operation. owner's and Installation manuals(not shown) Leaving breaker in OFF (OPEN) position will prevent K Wi-Fi manual (not shown) generator from powering structure during a power outage L Wi-F!Quick Start Guide(not shown) when placed in AUTO mode. Figure 2-10. Parts Shipped Loose 10 Installation Guidelines for 60 Hz Air-Cooled Generators Unpacking and Inspection Auxiliary Shutdown Switch 'CAUTION Equipment Damage.The auxiliary shutdown switch is not to be used to power down the unit under normal operating circumstances. Doing so will result in equipment damage. (000399) All generators are equipped with an external means of shutting down the generator which complies with the lat- est NEC code requirement. The primary generator shut- down sequence is described in Control Panel Startup/ Testing. See Figure 2-11. An auxiliary shutdown switch is pro- vided on the exterior of the generator back panel. This switch shuts down the generator and disables restarts. I O OD 0 005491 Figure 2-11.Auxiliary Shutdown Switch (all models) NOTE: Whenever possible, perform primary shutdown procedure before disabling generator with auxiliary shut- down switch. See Figure 2-12. 16-22 kW generators also have an aux- iliary shutdown switch located inside the generator. 0 0 0 0 i 005492 Figure 2-12.Auxiliary Shutdown Switch (16-22kKo Generator will not start if either switch is OPEN (0). Con- troller displays an "Auxiliary Shutdown" alarm, and red LED "Alarm" light illuminates until switch or switches are CLOSED (1) and alarm is cleared by pressing OFF mode button, and then ENTER. Once cleared, generator can be placed back in AUTO or MANUAL. Installation Guidelines for 60 Hz Air-Cooled Generators 11 Unpacking and Inspection This page intentionally left blank. 12 Installation Guidelines for 60 Hz Air-Cooled Generators Site Selection and Preparation Section 3: Site Selection and Preparation w . Site Selection Carbon Monoxide Site selection is critical for safe generator operation. It is important to discuss these factors with the installer when ya4G:'as selecting a site for generator installation: Asphyxiation. Running engines produce • Carbon monoxide carbon monoxide, a colorless, odorless, poisonous gas. Carbon monoxide, if not • Fire prevention avoided, will result in death or serious injury. • Fresh air for ventilation and cooling (000103) • Water ingress prevention IMPORTANT NOTE: Move to fresh air immediately and seek medical attention if you feel sick, dizzy, or • Proximity to utilities weak while the generator is running or after it stops. • Suitable mounting surface Generator exhaust contains carbon monoxide (CO�—a The following pages describe each of these factors in poisonous, potentially lethal gas that cannot be seen or detail. smelled. The generator must be installed in a well ventilated area away from windows, doors, and NOTE: The term "structure" is used throughout this sec- openings.The selected location should not allow exhaust tion to describe the home or building where generator is gases to be drawn into structures where people or being installed. Illustrations depict a typical residential animals may be present. home. However, instructions and recommendations pre- sented in this section apply to all structures regardless of Carbon Monoxide Detectors type See Figure 3-1. CO detectors (K) must be used to monitor for CO and to warn individuals about the presence of CO. CO detectors should be installed and tested in accordance with the CO detector manufacturer's instructions and warnings. Contact local building inspection department for any applicable requirements concerning CO detectors. IMPORTANT NOTE: Common smoke alarms do NOT detect CO gas. Do not rely on smoke alarms to protect residents or animals from CO. The only way to detect CO is to have functioning CO alarms. Installation Guidelines for 60 Hz Air-Cooled Generators 13 Site Selection and Preparation Potential CO Entry Points Protect the Structure See Figure 3-1. Generator exhaust can enter a structure Verify structure itself is correctly caulked and sealed to through large openings, such as windows and doors. prevent air from leaking in or out Voids, cracks, or However, exhaust and CO can also seep into the openings around windows, doors, soffits, pipes, and structure through smaller, less obvious openings. vents can allow exhaust gas to be drawn into the structure. Some examples of potential entry points are described and included in, but not limited to, the accompanying table. C K C A A �J B A H / A E J A G 008781 Figure 3-1. Carbon Monoxide—Potential Entry Points ID Entry Point Description/Comments A Windows and doors Architectural details which can be(or are)opened to admit fresh air into the structure. B Garage door CO can leak into garage if door is open,or does not seal correctly when closed. C Attic vent Attic vents, ridge vents, crawl space vents,and soffit vents can all admit generator exhaust. D Basement windows Windows or hatches allowing ventilation to or from lower level of a structure. E Furnace intake/ Air intake and exhaust pipes for furnace. exhaust vent F Wall cracks Includes(but not limited to)cracks in wall,foundation,mortar,or air gaps around doors, windows,and pipes.See Protect the Structure. G Dryer vent Exhaust duct for clothes dryer. H Airflow restrictions Structural corners and locations with heavy vegetation restrict airflow.Exhaust gases can collect in such areas. IMPORTANT NOTE: Mechanical and gravity outdoor air intake openings for HVAC supply J Make up air system air systems shall be located not less than 10 feet(3048mm) horizontally from the generator enclosure.See Section 401 in the ICC Mechanical Code for any additional requirements. 14 Installation Guidelines for 60 Hz Air-Cooled Generators Site Selection and Preparation Fire Prevention The generator must be installed at a safe distance away Distance Requirements from combustible materials Engine, alternator, and See Figure 3-2. Minimum clearances must be exhaust system components become very hot during maintained around the generator enclosure. These operation. Fire risk increases if unit is not correctly clearances are primarily for fire prevention, but also to ventilated, is not correctly maintained, operates too close ensure sufficient room for removing front and end panels to combustible materials, or if fuel leaks exist. Also, for maintenance purposes. accumulations of flammable debris within or outside the generator enclosure may ignite. C O F A 1 A C C C 008782 Figure 3-2. Generator Distance Requirements ID Description Definition A Front and end Minimum clearance from the front and ends of generator must be 3 ft(0.91 m).This includes clearance shrubs, bushes, and trees. B Rear clearance Fuel and electrical connections are made here. 18 in (457 mm)minimum clearance per NFPA testing,labeling, and listing, unless state or local codes dictate otherwise. C Windows,vents, No operable windows,doors,vents,window wells,or openings in the wall are permitted near any and openings point of the generator. See Potential CO Entry Points for more information. D Existing wall The generator should not be placed closer than 18 in (457 mm)from existing walls. A removable barrier(non-permanent;without footings)installed as a visual surround. E Removable fence Removable fence panels for servicing cannot be placed less than 3 ft(0.91 m)in front of the generator. F Overhead clearance 5 ft(1.52 m)minimum distance from any structure,overhang,or projections from wall. DO NOT install under wooden decks or structures. Maintenance and Maneuvering space around generator for performing routine maintenance tasks such as battery G servicing replacement and engine service. Do not attempt to conceal generator with shrubs, bushes, or plants. Installation Guidelines for 60 Hz Air-Cooled Generators 15 Site Selection and Preparation Fire Codes, Standards, and Guidelines Generator installation-must comply strictly with ICC IFGC, NFPA 37, NFPA 54, NFPA 58, and NFPA 70 ® SwRI ID Na t3zoao}-0i O Compiant .nh aause Izt standards. These standards prescribe the minimum safe /�1 of Section au of LAPPA 37 LISTED BY. Southwest Research clearances around and above the generator enclosure. Institute Sen Antonio,Texas NFPA 37 NOTE 1130 CHAR MA*--•.•••""•."•m" ".....••••"•m^NOTE 2 130 CHAR MAXh•^'""^"••"•m'• NFPA 37 is the The National Fire Protection ��om, NOTE 3 130 CHAR MAXI••••••^m —" -•• NOTE 4(30 CHARMAX!• "•"• Association's standard for the installation and use of NOTE 5 130 CHAR MAXI•• ,---•--" m•m" NOTE 6 130 CHAR.MAXF•^••""••••^"•d• stationary combustion engines. Its requirements limit the NOTE 7 130 CHAR MAXI•••••-•-•-•-"•• spacing of an enclosed generator set from a structure or GENERAC POWER SYSTEMS, INCp g g WAuitESHA,N USA 53169 oL2F7 wall, and require generator to be located where it is 002158 readily accessible for maintenance, repair, and first Figure 3-3. Southwest Research Institute Marking responders. NFPA 37, Section 4.9.4, Engines Located Outdoors: http://www2.swri.orglwww2liistprodl Engines, and their weatherproof housings if provided, DocumentSelection.asp?ProductlD=973&lndustrylD=2 installed outdoors shall be located at least 5 ft (1.52 m) Based on this testing and the requirements of NFPA 37, from openings in walls and at least 5 ft (1.52 m) from Sec 4.1.4,the guidelines for installation of the generators structures having combustible walls. A minimum listed above are changed to 18 in (457 mm) from the separation shall not be required where the following back side of the generator to a stationary wall or building conditions exist: For adequate maintenance and airflow clearance, the 1. The adjacent wall of the structure has a fire resis- area above the generator should be at least 5 ft(1.52 m) tance rating of at least one hour. with a minimum of 3 ft (0.91 m) at the front and ends of 2. The weatherproof enclosure is constructed of non- the enclosure. This includes trees, shrubs, and bushes. combustible materials and it has been demon- Vegetation not in compliance with these clearance strated that a fire within the enclosure will not ignite parameters could obstruct air flow. In addition, exhaust combustible materials outside the enclosure. fumes from the generator could inhibit plant growth. See Annex A—Explanatory Material Figure 3-2 and the accompanying descriptions. ••- A4.1.4 (2) Means of demonstrating compliance are by Generator Maintenance means of full scale fire test or by calculation procedures Regular maintenance is crucial for minimizing exhaust Because of the limited spaces frequently available for emissions and reducing the risk of fire or equipment installation, it has become apparent that exception (2) failure. For example: would be beneficial for many residential and commercial • A dirty air filter or low engine oil level may cause installations. The manufacturer contracted with an engine to overheat. independent testing laboratory to run full scale fire tests. • Incorrect spark plug gaps may cause engine back- NOTE: The Southwest Research Institute (SwRI) is a firing and incomplete combustion. nationally recognized third party testing and listing IMPORTANT NOTE: See Maintenance section of agency. SwRI testing approves 18 in (457 mm) installa- generator owner's manual to view a table of tion minimum from the rear panel of the generator to an scheduled maintenance tasks and procedures. adjacent structure for fire protection. Perform all maintenance tasks as directed. The criteria was to determine the worst case fire scenario within the generator and to determine the ignitability of items outside the engine enclosure at various distances. The enclosure is constructed of non-combustible materials, and the results and conclusions from the Independent testing lab indicated that any fire within the generator enclosure would not pose any ignition risk to nearby combustibles or structures, with or without fire service personnel response. 16 Installation Guidelines for 60 Hz Air-Cooled Generators Site Selection and Preparation Fresh Air for Ventilation and Cooling Suitable Mounting Surface Install unit where air inlet and outlet openings will not See Figure 3-4. Prepare a rectangular area become obstructed by leaves, grass, snow, etc. If approximately 5 in (127 mm)deep (A)and approximately prevailing winds will cause blowing or drifting, consider 3 in (76.2 mm) longer and wider (B) than the generator using a windbreak at a safe distance to protect the unit on all sides Water Ingress Avoidance • Select a location on high ground where water lev- els will not rise and flood the generator. This unit should not operate in, or be subjected to, standing water. • Install unit where rain gutter downspouts, roof run- OB O Q off, landscape irrigation, water sprinklers, or sump pump discharge does not flood unit or spray enclo- sure, including any air inlet or outlet openings O • Excess moisture can cause excess corrosion and ; decrease life expectancy of the unit. 00866' Figure 3-4. Compacted Gravel or Concrete Pad Proximity to Utilities Select base type as desired or as required by local laws • Contact local utility providers and verify proposed or codes. The generator is typically placed on pea gravel, site selection meets all required utility placement crushed stone, or a concrete pad. Follow all applicable requirements before installation. This could affect codes if a concrete pad is required. warranty coverage. Verify surface where generator will be mounted is • Remember, laws and or codes may regulate dis- compacted, leveled, and will not erode over time. tance and location of unit to specific utilities. Generator must be level within 0.5 in (13 mm)all around. • It is recommended to pick a location where the generator is as close as possible to the transfer Placement on Roofs, Platforms, and switch and the fuel supply, while verifying the site Other Supporting Structures location conforms to the rest of the Site Selection section. Where required to place generator on a roof, platform, deck, or other supporting structure, generator must be Verify Wi-Fi Range placed in accordance with the requirements in NFPA 37, See Wi-Fi manual shipped with the unit if planning to use Section 4.1.3. Generator can be located 18 in (457 mm) the Wi-Fi feature. from structures having combustible walls and 5 ft (1.52 m) from any operable opening in the structure. Surface beneath the generator and beyond must be Transportation Recommendations noncombustible to a minimum distance of 12 in (30.5 Use a suitable cart or equipment to carry generator, cm) Contact local Building Inspection Department or fire including wooden pallet, to installation site. Place department to determine which noncombustible materials cardboard between cart and generator to prevent any are approved for installation. damage or scratches to generator. Do not lift, carry, or move generator by grasping the louvers. Doing so may bend or damage the sheet metal. Installation Guidelines for 60 Hz Air-Cooled Generators 17 Site Selection and Preparation This, page intentionally left blank. 18 Installation Guidelines for 60 Hz Air-Cooled Generators Generator Placement Section 4: Generator Placement Generator Placement Three 3/8 in (or M10) lag bolts (not supplied) are recom- See Figure 4-7. All air-cooled generators come with a mended for securing the generator to a concrete pad. composite pad. This composite pad elevates the genera- NOTE: The top of the generator carton has a template for and helps prevent water from pooling around base. which can be used to mark the concrete pad to pre-drill the mounting holes. Fascia Installation (If Applicable) 1. Locate the four threaded black rubber bumpers supplied with the loose parts. (See Parts Shipped Loose.) 2. See Figure 4-3. Remove bumpers from bag and screw them into threaded holes located inside the O end pieces of the fascia (two each) opposite one 000612 another(A). Figure 4-9. Composite Pad ---------------- B The composite pad allows the generator to be placed on two types of surfaces: 0 • on 5 in (127 mm) of compacted pea gravel or crushed stone i C5/ • on a concrete pad L---------------- See local codes to verify what type of site base is required. If a concrete pad is required, all federal, state, and local codes must be followed Place generator, with composite pad attached, and position correctly as per dimensional information given in Site Preparation. NOTE: Generator must be level within 0.5 in (13 mm). NOTE: See Figure 4-2. DO NOT remove composite pad for mounting generator to concrete.The composite pad is pre-drilled to accommodate mounting bolts. C O 000614 • c 0, Figure 4-3. Fascia Installation 3. Snap one of the end pieces into one of the front/ rear pieces of fascia. Repeat this action with the other two remaining pieces of fascia (B). NOTE: Do not assemble all four pieces together at this m point. ® 4. Place both assemblies at the generator base and d • • fit the rubber mounts into the lifting holes in the generator base (C). 001804 5. Once aligned, snap together the two remaining Figure 4-2. Mounting Hole Locations connection points Three mounting holes are available if codes require securing generator to concrete. Mounting holes are located inside the generator compartment—two in front and one in back. Installation Guidelines for 60 Hz Air-Cooled Generators 19 Generator Placement This page intentionally left blank. 20 Installation Guidelines for 60 Hz Air-Cooled Generators Fuel Conversion/Gas Connections Section 5: Fuel Conversion / Gas Connections Fuel Requirements and NOTE: All pipe sizing, construction, and layout must Recommendations comply with NFPA 54 for NG applications and NFPA 58 or ICC IFGC for LP gas applications. Verify fuel pressure NEVER drops below required specification once genera- itorOtor is installed. See the NFPA website at www.nfpa.org Explosion and fire Fuel and vapors are extremely for further information regarding NFPA requirements flammable and explosive. No leakage of fuel is permitted. Keep fire and spark away. Failure to do Always contact local fuel suppliers or fire marshal to ver- so will result in death or serious injury. (000192) ify codes and regulations for correct installation. Local codes will mandate correct routing of gaseous fuel line NOTE: NG is lighter than air and will collect in high piping around gardens,shrubs, and other landscaping. areas LP gas is heavier than air and will settle in low Piping strength and connections should be given special areas. consideration for installations in areas at risk for flooding, LP gas should only use a vapor withdrawal system. This tornadoes, hurricanes, earthquakes, and unstable ground. type of system uses vapors formed above liquid propane in the storage tank. IMPORTANT NOTE: Use an approved pipe sealant The unit will run on NG or LP gas, but has been factory- or joint compound on all threaded NPT fittings. configured to run on NG. NOTE: All installed gaseous fuel piping must be purged NOTE: Should the primary fuel need to be changed to and leak tested prior to initial startup in accordance with LP gas, the fuel system needs to be reconfigured See local codes, standards, and regulations. Fuel Conversion for instructions on converting the fuel system. Fuel Conversion Proceed as follows to convert from NG configuration to BTU Content LP gas. , Recommended fuels should have a BTU content of at See Figure 5-1 for fuel conversion knob (A) locations least 1,000 BTU/ft3 (37.26 MJ/m3) for NG; or at least The orange fuel conversion knob is located beneath the 2,500 BTU/ft3 (93.15 MJ/m3)for LP gas. fuel mixer on 9 kW units (B) and above the fuel mixer on NOTE: BTU fuel content information is available from 11 kW-22 kW units (C). fuel supplier. To select fuel type, turn fuel conversion knob towards marked fuel source arrow until it stops. Fuel conversion Fuel Pressure knob will rotate 180° and slide into mixer body when con- Required fuel pressure for NG is 3.5-7.0 in water column verting to LP gas. (0.87-1.74 kPa) at generator fuel inlet. Required fuel NOTE: The fuel selection (LP/NG) must be entered on pressure for LP gas is 10-12 in water column (2 49-2.99 the controller during initial startup using the Install Wiz- kPa)at generator fuel inlet and Menu Map navigation menu, or in EDIT menu under "Fuel Selection." NOTE: The primary regulator for LP gas supply is NOT INCLUDED with generator. 0 o � aG d A 001878 Figure 5-1. Fuel Conversion Knob Locations Installation Guidelines for 60 Hz Air-Cooled Generators 21 Fuel Conversion/Gas Connections Fuel Consumption Natural Gas Propane Generator 1/2 Load Full Load 1/2 Load Full Load 9 k 255/90 3.40/ 120 0.87/3.29/32 1.37/5.20/50 11 kW 3.03/ 107 4.50/ 159 1.22/4.62/44 1.97/7.45/72 16 kW 6.17/218 8.75/309 2.03/7.70/74 2.94/ 11.11 / 107 20 kW 5.78/204 8.52/301 2.37/8.99/87 3.56/ 13.48/ 130 22 kW 6.46/228 9.26/327 2.53/9.57/92 3.90/ 14.77/ 142 * Natural gas is in m3/h/ft3/h ** Propane is in gal/h (LP)/L/h (LP)/ft3/h (LPV) ***Values given are approximate These are approximate values. Use the appropriate spec sheet or fuel data decal for specific values Verify gas meter is capable of providing enough fuel flow to include household appliances and all other loads. NOTE: The fuel supply and pipe MUST be sized at 100% load BTU/h (Megajoule/h)rating. Always see fuel data label for correct BTU/h orMegajoule/h, and required fuel pressures. — Natural Gas: BTU/h =ft3/h x 1000 Megajoules/h = m3/h x 37.26 — Liquid Propane Gas (Vapor): BTU/h =ft3/h x 2500 Megajoules/h = m3/h x 93.15 Fuel Line Sizing Selecting the correct size fuel line is crucial to correct operation of the unit. IMPORTANT NOTE: Generator inlet size DOES NOT dictate the size of gas pipe to be used! For further information, see NFPA 54 for NG, or NFPA 58 or ICC IFGC for LP. Measure the distance from generator to fuel source. IMPORTANT NOTE: The generator should be plumb- ed directly from the fuel source, not off the end of an existing low pressure system. 22 Installation Guidelines for 60 Hz Air-Cooled Generators Fuel Conversion/Gas Connections Natural Gas Pipe Sizing To determine correct NG pipe size, find the kW rating of NOTE: See Table B 3 2 in NFPA 54 or Table A.2.2 in the generator in the left column, and trace to the right. The ICC IFGC, Equivalent Lengths of Pipe Fittings and number to the right is maximum length (measured in ft / Valves for the correct values to be added to overall fuel m)allowed for the pipe sizes on top. Pipe sizes are mea- piping length. Tables are based on schedule 40 black sured by trade size diameter to include any fittings, pipe. If installing any other piping system, follow pipe siz- valves (must be full flow), elbows, tees, or angles. ing charts for selected piping system. Table 5-1. NG Pipe Sizing ` For 5-7 in Water Column For 3.5-5 in Water Column (1.24-1.74 kPa) (0.87-1.24 kPa) Pipe Siz+a" >.0n/mm)'' Allowable Pipe Distances(ft/m) ,J%75 25 e , , y , .,..�.--, 2 -/ , 7 ! 125 38141 ;,moi n- -. 9 kW 10/3.1 60/18.3 200/61 750/228.6 - 20/6.1 60/18.3 175/53.3 - 11 kW - 30/9.1 100/3.5 450/1372 - - 30/9.1 125/38.1 200/61 16-20 kW - 10/3.1 35/10.7 140/42.3 300/91.4 - 10/3.1 60/18.3 125/38.1 22 kW - 10/3.1 30/91 115/35.1 250/76.2 - 10/3.1 60/18.3 125/38.1 LP Gas Pipe Sizing To determine correct LP gas pipe size, find the kW rating NOTE: Pipe sizes are from the outlet of the second of generator in the left column, and trace to the right The stage regulator to the fuel shdtoff valve. Table is based number to the right is maximum length (measured in ft/ on schedule 40 black pipe. If installing any other piping m) allowed for pipe sizes on top. Pipe sizes are mea- system, follow the pipe size charts for the selected piping sured by trade size diameter to include any fittings, system. valves (must be full flow), elbows, tees, or angles. See NOTE: Recommended minimum LP tank size is 250 gal Table B.3.2 in NFPA 54 or Table A.2.2 in the ICC IFGC, (946 Q. Contact LP provider to correctly size LP tank to Equivalent Lengths of Pipe Fittings and Valves for the generator. Vertical tanks, which are measured in pounds correct values to be added to overall fuel piping length. (or kilograms), are permitted if correctly sized for the gen- erator Do not connect generator to a 20 or 30 lbs LP tank. Table 5-2. LP Gas Pipe Sizing For 10-12 in Water Column A (2.49-2.99 kPa) Allowable Pipe Distances(ft/m) 25n," 1 25 t 32 9 kW 35/107 175/53.3 600/182.9 - 11 kW 15/46 80/244 350/1067 - 16-22 kW - 40/122 175/53.3 550/167.6 Installation Guidelines for 60 Hz Air-Cooled Generators 23 Fuel Conversion/Gas Connections Installing and Connecting Fuel Lines Explosion and fire. Fuel and vapors are extremely flammable and explosive. No leakage of fuel is permitted. Keep fire and spark away. Failure to do so will result in death or serious injury.- (000192) IMPORTANT NOTE: NG and LP gas are highly vola- tile substances. Strictly adhere to all safety proce- dures, codes, standards, and regulations. 000743 Fuel line connections should be made by a certified con- Figure 5-3. Fuel Shutoff Valve with Manometer Port tractor familiar with local codes. Always use AGA approved gas pipe and a quality pipe sealant or joint Fuel shutoff valves available through a local IASD: compound. • 1/2 in ball valve, part number OK8752 Verify capacity of NG meter or LP tank to provide suffi- • 3/4 in ball valve, part number OK8754 cient fuel for both the generator and other operating 1 in ball valve, part number OK8184 appliances. •' 1-1/4 in ball valve, part number OL2844 Fuel Shutoff Valve 1-1/2 in ball valve, part number OL2845 See Figure 5-2. The generator will require an external manual fuel shutoff valve (A) on the fuel line. Flexible Fuel Line -NOTE: Fuel shutoff valve must be installed at.a readily See Figure 5-2 When connecting flexible fuel line (B)to accessible location, and within 6 ft (1.8 m) of generator generator, use a listed assembly meeting the require-- fuel inlet. ments of ANSI Z21.75/ CSA 6.27—Connectors for Out- door Gas Appliances and Manufactured Homes or AGA- �--approved flexible fuel line in accordance with local regu- lations. 0c) , Flexible fuel line must not be connected directly to gener- ator fuel inlet. Always connect flexible fuel line to an approved gas.fitting. The purpose of flexible fuel line is to isolate vibration from A the generator to reduce possibility of a gas Peak at one of / the connection points. / NOTE: Follow all installation instructions and warnings ® provided with the flexible fuel-line Do not remove any C labels or tags. Flexible fuel line must be installed horizon- tally, and must be installed between fuel shutoff valve Figure 5-2. Sediment Trap, Fuel Shutoff Valve with and generator fuel inlet. Manometer Port, and Flexible Fuel Line- Sediment Trap 'Figure 5-3 illustrates a fuel shutoff valve with a manome- ter port for making fuel pressure checks. This optional See Figure 5-2. Some local codes require a sediment accessory fuel shutoff valve permits making pressure trap (C). The fuel regulator connection has an integrated checks for diagnostic purposes without going into the sediment trap. generator enclosure. The sediment trap must be cleaned periodically accord- ing to local codes. See owner's manual for more informa- tion. 24 Installation Guidelines for 60 Hz Air-Cooled Generators Fuel Conversion/Gas Connections Checking Fuel Line Connections Performing Fuel System Leak Test Checking Fuel Pressure ! Proceed as follows to check fuel pressure at regulator inExplosion and fire. Fuel and vapors are extremely the generator. "*., flammable and explosive. No leakage of fuel is permitted. Keep fire and spark away. Failure to do 1. Close fuel supply valve. so will result in death or serious injury. 2. See Figure 5-4. Remove top fuel pressure test port (000192) from regulator and install fuel pressure tester All products are factory-tested before shipping to verify (manometer). the performance and integrity of the fuel system. How- 3. Open fuel supply valve and verify fuel pressure is ever, it is important to perform a final fuel system leak test within specified values. before starting the generator. The entire fuel system 4. Record static fuel pressure: should be tested from supply to regulator. NOTE: Fuel pressure can also be tested at the manome- See Figure 5-5. Perform a final fuel system leak test ter port on fuel shutoff valve shown in Figure 5-2. after generator installation. The test will identify possible leaks at all connection points(A). NOTE: See Fuel Data Decal or spec sheet for correct It is best practice to perform a fuel system leak test fuel pressure specifications. If fuel pressure is not within during normally-scheduled maintenance. specifications, contact local fuel supplier. 5. Close fuel valve when completed, but keep man- ometer connected for future tests of generator A while starting, running, and under loads. A 0 ® 001807 0 00 Figure 5-4. Checking Pressure with Manometer o A 004038 Figure 5-5. Connection Points to Leak Check Inspect for leaks by spraying all connection points with a non-corrosive gas leak detection fluid. The solution should not be blown away or form bubbles. Installation Guidelines for 60 Hz Air-Cooled Generators 25 Fuel Conversion/Gas Connections Natural Gas Installation (Typical) ® A 0 0 D � D j I I E I i I I D �® C I B �� U 008965 NG BTU/h=ft3/h X 1000 Megajoules/h= m3/h X 37.26 A Fuel data decal B Minimum distance from rear obstruction—see Distance Requirements C Manual fuel shutoff valve (pressure port optional) Must be located no more than 6 ft(1.83 m)away from fuel inlet D Pipe fittings (field supplied) E Flexible fuel line F Check clearance with gas provider G Size gas meter for 100% generator load plus all appliance loads H For underground installations, verify piping system for code compliance I Reinforcing rod with clamps J To gas main Figure 5-6. Natural Gas Installation (typical) 26 Installation Guidelines for 60 Hz Air-Cooled Generators Fuel Conversion/Gas Connections LP Gas (Vapor) Installation (Typical) A 0® II D o � _ E JO G H L o � B I F I I 008966 LPG BTU/h =ft3/h X 2500 Megajoules/h=m3/h X 93.15 A Fuel data decal B Minimum distance from rear obstruction—see Distance Requirements C Manual fuel shutoff valve (pressure port optional) Must be located no more than 6 ft(1.83 m)away from fuel inlet. D Pipe fittings (field supplied) E Flexible fuel line F Verify minimum distance requirements for regulator vent according to local gas codes G Clamp H Secondary fuel pressure regulator J Manual shutoff valve K Primary fuel pressure regulator L Fuel tank—sized large enough to provide required MJ/BTU for generator and ALL connected appliance loads. Be sure to correct for weather evaporation. Figure 5-7. LP Gas(Vapor) Installation (typical) r Installation Guidelines for 60 Hz Air-Cooled Generators 27 Electrical Connections Section 6: Electrical Connections t . . .. Generator Connections See Figure 6-1.The electrical wiring enclosure is located behind an access panel on intake end of unit. Remove intake side panel as directed in Intake Side Panel Removal, and then remove access panel. Connect wires according to diagram and tables. 1. Remove main AC / control wiring knock-out plugs from back of generator. 2. Using appropriate wiring hole, install conduit and main AC and control wires between generator and transfer switch. 3. Close unused hole with a NEMA 3R rated plug (field-supplied). NOTE: All conductors are to be rated for minimum 300V. Control system interconnections may consist of N1, N2, and T1, and leads 23 and 194.All of the generator con- trol wiring circuits are Class 1 remote control or signaling circuits. Class 1 circuits are required to be installed in accordance with Part 1 of NEC Article 300 and with a NEC recognized Chapter 3 wiring method. The use of low voltage cables for the generator control circuit wiring is prohibited. See instruction manual of the specific engine generator for wiring connection details Recom- mended wire gauge sizes for this wiring depends on wire length, as recommended in Table 6-3. Exception: Conductors of AC and DC circuits, rated 1000 volts nominal or less, shall be permitted to occupy the same equipment, cable, or conduit. All conductors shall have an insulation rating equal to at least the maxi- mum circuit voltage applied to any conductor within the equipment, cable, or conduit See NEC 300.3(C)(1). 4. See Figure 6-1. Strip insulation from wire ends. Do not remove excessive insulation Route sense wires through supplied wire tie (Cl), and connect to sense wire terminal block (B). Push down on spring loaded connection point with a flat head screwdriver, insert wire, and release. 5. Using the same process, route control wires through second supplied wire tie (C2), and connect to control wire terminal block (A). 6. When all wires are securely connected to correct terminals, tighten wire ties and clip excess length NOTE: Only bare wire should be inserted into each ter- minal. Do not insert any wire insulation into terminals. NOTE: Damage caused by mis-wiring of the intercon- nect wires is not warrantable. Installation Guidelines for 60 Hz Air-Cooled Generators 29 Electrical Connections Control Wiring A B C1 C2 0 E1 Asa 8 DC GROUND YtI1ILtl ! gSEN,SE'° o 2�S,FN2tltH Y'S E2 3 23VAC LOA E 3TRANSFER 3 D SUPPLY -� O 005810 J H D F G Figure 6-9. Electrical Wiring Connections Table 6-1. Electrical Wiring Connection Points ID Description ID Description ID Description ID Description A Control wire terminal block C2 Wire tie for control wires E2 Power lug E2 H Neutral stud B Sense wire terminal block D Neutral lug F Ground stud J Neutral bar C1 Wire tie for sense wires E1 Power lug E1 G Ground lug — — Table 6-2.Customer Wiring Connections Table 6-3. Control Wire Recommended Length and Size (Copper Conductors Only) Terminal Numbering Decal Wire Numbers Maximum Wire Length Recommended Wire Size N1 &N2-240 VAC-Sensing for utility 1-115 ft(0 3-35 m) No.18 AWG YELLOW dropout and pickup P P P 115-185 ft(35-56 m) No. 16 AWG BLUE* T1 -Fused 120 VAC for battery charger 185-295 ft(56-89 m) No. 14 AWG BLACK** 0-DC(-)Common ground wire 295-460 ft(89-140 m) No. 12 AWG RED 194-DC(+)12 VDC for transfer controls WHITE 23-Transfer control signal wire *Must be connected to keep battery charged whether unit is running or not. **Required if generator is paired with optional Digital Power Management(DPM)smart technology. 30 Installation Guidelines for 60 Hz Air-Cooled Generators Electrical Connections Table 6-4. Ground and Neutral Connections Conductors of AC and DC circuits, rated 100.0 volts nom- (Copper o'Aluminum Conductors) inal or less, shall be permitted to occupy the same equip- ment, cable, or conduit. All conductors shall have an See national and/or local codes to verify correct wire sizes Insulation rating equal to at least the maximum circuit Recommended voltage applied to any conductor within the equipment, No. Description Wire Size Torque Spec cable, or conduit. See NEC 300.3(C)(1). 1 Power wire 2/0 to 8 AWG 120 in-lbs(13.56 Nm) terminals Service Entrance Decals 2 Large neutral 2/0 to 14 AWG 120 in-lbs(13 56 Nm) See Figure 2-10. Locate service entrance-related decals lug In the loose parts bag. 3 Large ground lug 2/0 to 14 AWG 120 in-lbs(13.56 Nm) - Place service disconnect decal next to main line 4-6 AWG 35 in-lbs(3.95 Nm) circuit breaker (generator disconnect) (if required 4 Neutral bus bar 8 AWG 25 in-lbs(2.82 Nm) by local code). 10-14 AWG 20 in-lbs(2.26 Nm) - Place service entrance warning decal in an appro- priate location according to instructions printed on Main AC Wiring decal. NOTE: Main AC wiring must be in accordance with local Common Alarm Relay (Option) jurisdiction and codes NOTE: Generator lugs are rated at 167 °F (75 °C), cop- Alarms relating to generator and engine performance appear on the controller and in Mobile LinkTapplication per or aluminum. (if used).The controller is equipped with a common alarm 1. Strip insulation off wire ends. Do not remove relay providing contacts for an optional customer-sup- excessive insulation. plied external alarm indicator. 2. See Figure 6-1. Loosen lugs at neutral (D), ground The common alarm relay is normally open until an alarm (G), and power wire (mains)terminals (E1, E2). occurs, triggering relay to close contacts. 3. Connect ground wire to ground lug and tighten to Terminals for common alarm relay are provided in the required specification. See Table 6-4. wiring harness near the controller plug (Wires 209 and 4. Connect neutral wire to neutral lug if applicable. 210). Tighten to required specification. See Table 6-4. Contact rating is for resistive load only: 5. Insert power wires (E1 and E2) into corresponding Contact rating 200 mA at 12 VDC lugs.Tighten to required specification. 6. Verify factory-installed ground array and neutral Battery Requirements connections are correctly tightened to 25 in-lbs (2.82 Nm). 12 volts, Group 26R Wet Cell 540CCA minimum, or NOTE: Neutral wire must remain connected to keep bat- Group 35 AGM 650CCA minimum. tery charged whether generator is running or not. NOTE: Do not use external battery chargers. NOTE: Neutral bonding—For installations requiring neu- tral to be bonded to ground, this is done on the customer connections terminals inside generator. See Figure 6-1. Connect a suitably sized system bond- ing jumper in accordance with NEC Table 250.102(C)(1) from neutral bar (J) to ground stud (F). Tighten ground stud nut to 35 in-lbs (3.95 Nm). This is required when generator is Installed as a separately derived system. Generator will also require a connection to a grounding electrode system in accordance with NEC Article 250.64 It is not required when generator is a backup source In a utility supplied electrical system with a 2-pole transfer switch. Installation must be made in accordance with NEC Articles 250.30 and 250.35(A) if generator will be installed as a separately derived system. NOTE: Tighten all wiring lugs, bus bars, and connection points to the required torque specifications. Installation Guidelines for 60 Hz Air-Cooled Generators 31 Electrical Connections Battery Installation '*,4 Explosion.Batteries emit explosive gases while charging. O Keep fire and spark away.Wear protective gear when O working with batteries.Failure to do so could result in death or serious injury (000137a) Risk of burns. Batteries contain sulfuric acid and 001832 can cause severe chemical burns. Wear protective Figure 6-2. Battery Cable Connections gear when working with batteries. Failure to do so could result in death or serious injury(000138a) Connect battery cables to battery posts as follows. 1. Connect red positive battery cable (A• from starter contactor)to positive battery post.Tighten to 70 in- It ." Ibs (8 Nm). Explosion. Batteries emit explosive gases. 2. Connect black negative battery cable (B: from Always connect positive battery cable first to frame ground) to negative battery post. Tighten to avoid spark. Failure to do so could result in 70 in-lbs (8 Nm). death or serious injury. (000133) 3. Install red battery post cover (shipped with loose parts). MNOTE: Apply dielectric grease to battery posts to pre- Risk of burn. Do not open or mutilate batteries. vent corrosion. Batteries contain electrolyte solution which can cause burns and blindness. If electrolyte contacts NOTE: In areas where temperatures fall below 0 °F skin or eyes,flush with water and seek immediate (-18 °C), a pad type battery warmer is recommended to medical attention. (000163a) aid in cold climate starting. The battery warmer is avail- • (Group 26R batteries only): Fill battery with the able as part of a cold weather kit from any IASD. correct electrolyte fluid if necessary. A battery warmer is not necessary for AGM-style batter- • Fully charge battery before installing it. ies. Complete the following steps before installing and con- necting battery: Battery Disposal 1. Verify generator is OFF. 2. Turn OFF utility power supply to transfer switch. _ 3. Remove 7.5A fuse from generator control panel. Environmental Hazard.Always recycle batteries at an official recycling center in accordance with all local Connecting Battery laws and regulations. Failure to do so could result in environmental damage, death or serious injury. (000228) Always recycle batteries in accordance with local laws Explosion. Batteries emit explosive gases. and regulations. Contact your local solid waste collection Always connect positive battery cable first to site or recycling facility to obtain information on local avoid spark. Failure to do so could result in death or serious injury. (000133) recycling processes. For more information on battery recycling, visit the Battery Council International website at: http://batterycouncii.org ACA UTION - Equipment damage. Do not make battery connections in reverse. Doing so will result in equipment damage. (000167a) See Figure 6-2. Battery cables (A, B) were factory con- nected at the generator. 32 Installation Guidelines for 60 Hz Air-Cooled Generators Control Panel Startup/Testing Section 7: Control Panel Startup/Testing Control Panel Interface NOTE: If home Wi-Fi network is not available, follow The control panel interface is located under the enclo- instructions on www.activategen.com. sure lid. Verify both left and right side locks are unlocked Proceed as follows after activating generator on-line: before attempting to lift enclosure lid. Open lid as 1. The display interface will launch Install Wizard directed in Opening the Lid. upon first power-up of the generator. Using the AUTO/MANUAL/OFF Buttons 2. Follow on-screen Instructions on the generator along with Quick Start Guide supplied with the unit to connect generator to home WI-Fi network. Button Description of Operation 3. Wait for on-line authentication of generator activa- AUTO Activates fully automatic system operation.Auto- tion through connected home WI-FI network matic operation allows unit to automatically start 4. Follow on-screen instructions to complete the and exercise generator according to exercise Install Wizard. timer settings (see Setting The Exercise NOTE: See Figure 7-2. If generator screen shows mes- Timer). sage shown below, press ESC and then ENTER to reset OFF Shuts down engine and also prevents automatic to Install Wizard. operation and exercise of unit. MANUAL Cranks and starts generator.Transfer to standby NOTACTIVATEDI power will not occur unless there is a utility fail- XXX(H) u re. (�a AUTO a MANWZ a®FF EWER D AUTO a MANUAL a OFF ESCAPE Oo o Q ENTER 009102 ESCAPE Figure 7-2. Not Activated Screen 000425 NOTE. Generator can only be placed in AUTO mode Figure 7-1. Generator Control Panel after completing activation process. IMPORTANT NOTE: Fuel selector knob must be set to Generator Setup the correct fuel for generator to function correctly. The controller illuminates when battery power is applied to the generator during the installation process. Genera- tor must be activated before it will automatically run in the event of a power outage. Activation To activate the generator, go to www.activategen.com and follow the instructions. Activation is a simple, one-time process. The generator will not prompt to activate again once the unit Is acti- vated, even if the generator battery, fuse, and battery charge circuit(T1) are disconnected. NOTE: The generator must be connected to the home WI-FI network for automatic authentication to be com- pleted successfully. See Wi-Fi manual for more informa- tion Installation Guidelines for 60 Hz Air-Cooled Generators 33 Control Panel Startup/Testing Display Reads Troubleshooting Language English + Use arrow keys to a Aero a MANUAL a OF!F scroll to desired Ian- Language can be changed later using O 0 Prase. the EDIT menu. Press ENTER to [�NTC�G� select. ESCAPE 002227 Enable Wi-Fi? - Yes + Use arrow keys to either enable or dis- c Aero 1&=j MANUAL a o—F able Wi-Fi (if equipped). U O O If YES,see Wi-Fi manual. ENTER If NO, continue. ESCAPE 004498 Activate me(ENT)or ESC to run in manual If ESCAPE is pressed instead of ENTER, generator will only run in a AUTO IZzQ MANUAL a oFF Press ENTER to begin manual mode (for test purposes) and Op 071Zactivation process. NOT ACTIVATED will be displayed. O Press ESC and then ENTER to reset ENTER Install Wizard ESCAPE 002228 To Activate go to wwwactivategen com If unit has not been activated,go to a ATO a MANUAL E 05 www.activategen.com. �p� O � If unit has been C a o vated, press ESC and ENTER then ENTER E�CAPE > 002229 34 Installation Guidelines for 60 Hz Air-Cooled Generators Control Panel Startup/Testing Display Reads-,-- _ Troubleshooting Select Hour(0-23) 6 + Activation Is complete a AUTO a MANUAL/Q®� when this screen is „ �0O displayed 1 O O Follow controller v prompts to complete 7 E TER installation. ESCAPE 002231 Cold Smart Start removed from controller via the controller fuse and T1 cir- The Cold Smart Start feature is factory-enabled, and can cuit and/or battery connections. be disabled in the EDIT menu. Generator will monitor NOTE: If Wi-Fl is enabled, exercise timer will a_utomati- ambient temperature and adjust its warm-up delay cally adjust for Daylight Saving Time. accordingly when Cold Smart Start is enabled. If ambient temperature is below a fixed temperature upon startup in NOTE: If using Wi-Fi.feature, exercise time well be set to AUTO mode (per chart below), generator will warm up for a random weekday during daylight hours. This setting 30 seconds, all engine to warm before load is can be'changed later. See Wi-Fi manual for details. applied. If ambient temperature Is at or above fixed tem- perature, generator will start up with normal warm-up Before Initial Startup delay of six seconds. See Cold Smart Start section in owner's manual. UJUGN Table 7-1.Cold Smart Start Set Points Engine'damage.Verify proper type and quantity of Generator Size 9 kW-20 kW 22 kW engine oil prior to starting engine. Failure to do so could result in engine damage. Fixed Temperature 50°F(10°C) 20°F(-7°C) (000135) Setting The Exercise Timer NOTE: The unit has,been 'run and tested at the factory prior to being shipped and does not require any type of This generator Is equipped with a configurable exercise break-in. timer.There'are two settings for the exercise timer: • Day/Time: Generator will start and exercise for NOTE: The unit comes filled with 5W-30 weight organic period defined, on day of week and at time of day oil from the factory. Check oil level and add appropriate specified. During this exercise period, unit runs for viscosity and amount of oil if necessary., five minutes on all models, and then shuts down. Install Wizard • Exercise frequency (how often exercise will take place): Can be set to Weekly, Biweekly, or See Figure 7-3. The Install Wizard immediately appears Monthly. If Monthly Is selected,'day of the month upon Initial startup. It allows user to input generator set- -must be selected from 1-28. Generator will exer- tings. clse on that day each month. Transfer of loads to The Install Wizard starts every time AC and DC power the generator output does not occur during exer- are removed and reapplied to generator. cise cycle unless utility power is lost. NOTE: If installer tests generator prior to Installation, press ENTER button to skip setting up exercise timer. NOTE: The exercise feature will operate only when gen- erator Is placed in AUTO mode, and will not work unless this procedure Is performed. If Wi-Fi is not enabled, cur- rent date/time must be reset every time power is Installation Guidelines for 60 Hz Air-Cooled Generators 35 Control Panel Startup/Testing Interconnect System Self Test Feature This controller goes through a system self test at power up, which checks for utility voltage on DC circuits. This check prevents damage if installer incorrectly connected AC utility power sense wires into the DC terminal block. The controller will display a warning message and lock out the generator if utility voltage is detected at the DC terminal block, preventing damage to the controller. Power to controller must be removed to clear this warn- ing. Utility voltage must be turned on and present at the N1 and N2 terminals inside the generator control panel for this test to be performed and pass. NOTE: All appropriate panels must be in place during any operation of generator. This includes operation by a servicing technician, while conducting troubleshooting procedures. Before starting, complete the following:. 1. Verify generator is OFF. 2. Set generator main circuit breaker to OFF (OPEN)' 3. Turn OFF all breakers to be powered by generator. 4. Verify auxiliary shutdown switch(es) are CLOSED M. 5. Check engine crankcase oil level and, if necessary, fill,to oil dipstick FULL mark with recommended oil. Do not overfill. 6. Inspect fuel supply. Gaseous fuel lines must have been correctly purged and leak tested-in accor- dance with applicable fuel-gas codes.All fuel shut- off valves in the fuel supply lines must be open. During initial start up only, generator may exceed normal number of start attempts and experience an "OVER- CRANK" fault. This is due'to accumulated air in the fuel system during installation. Reset control board by press- ing OFF mode button and ENTER button, and restart up to two more times if necessary. If unit fails to start, con- tact an IASD for assistance. 36 Installation Guidelines for 60 Hz Air-Cooled Generators iv n� o Note If language was Power Up Unit previously programmed c this goes directly C- to"Select Hour" CD FIRMWARE V XXX HARDWARE V XXX p AUTO D MANUAL DOFF UP ARROW=+ 0 2 Language v O O N + English - Install Wizard ENTER D + Espanol - 0 spanol -0 ESCAPE n + Francais - ° + Portuguese - a + - Defaults to English. DOWN ARROW= Select desired language by scrolling through list. ENTER m � o v Setup Wi-Fi? Yes--1- Follow setup WIFI Signal XX% Fuel Selection EN—�TER Cold Smart Start? N w + Yes or No - process Wi-Fi manual + NG or LP- F YES or NO a ENTER No ENTER N Use UP and DOWN Exercise Time Install Wizard f Time Zone Q Fuel Selection arrows to select fuel type, HH-MIM Day Biweekly Set Exercise.. XXXXXX + NG or LP- then press"ENTER". CD C Update From:WIFI WIFI Signal XX% lu a <Enter>to Begin ENTER if Use UP and DOWN arrows. Cold Smart Start? -`­to select YES or NO ESC ENTER F YES or NO 4 Press ENTER. Update From Server SYSTEM DATE/TIME Continue? o Select Hour(0-23) *Holding the Up or Down WIFI SUB MENUS ENTER o arrow button for 2 seconds - 14 + will speed dial through the selections Controller XXX �c Server X.XX.XXX U) ENTER l � 1 006668 � CDD w � r c n 0 0 ENTER 0 v 0 m Select Minute (0-59) ENTER Select Month (1-12) ENTER—0-- Select Date(1-3 1) ENTER—0- Select Year(0-99) v 0 - 0 + * - 2 + * - 13 + * - 13 + * I m TENTER cn SYSTEM DATE/TIME ­4—ESC USB Only–No WiFi ENTER Exercise Time Install Wizard <Enter>to Begin Set Exercise... 9 HH MM Day Biweekly �t � SETUP WIFI SUB MENUS ENTER Controller assigns - random date and time V I for biweekly exercise. ENTER a� Switched to OFF Firmware Update ENTER ENTER� Are You Sure v p Current.V X XX ? Hours of Protection Q' 0 (H) <-Insert USB-> USB. X.XX - Yes or No + 0 m m � C � ENTER o 1 a c Possible Message(s) Corrupted File m' Invalid File Select"Yes"then Press"Enter"to continue or Press"ESCAPE"to escape out of updating. v, File Not Found o Unsupported Device" During update process the Blue"Manual'light flashes,then the Green"Auto"light flashes Sequence a, does this twice.When update is complete the unit returns to Install Wizard menu. *Re-try using a higher quality N USB drive File names on the USB When the controller powers up the very first screen displays the version number for a few seconds. > cannot have more than 8 characters. When update is complete remove Thumb Drive,then follow the Install Wizard Menu. (7 0 0 m Q C co CD 0 0 006668