HomeMy WebLinkAboutGT Power Systems Corp - HRC Generator RESOLUTION 2020-568
�*4a ADOPTED DOC ID: 16426
THIS IS TO CERTIFY THAT THE FOLLOWING RESOLUTION NO. 2020-568 WAS
ADOPTED AT THE REGULAR MEETING OF THE SOUTHOLD TOWN BOARD ON
SEPTEMBER 8, 2020:
RESOLVED that the Town Board of the Town of Southold hereby authorizes and directs
Supervisor Scott A. Russell to execute an Agreement between the Town of Southold and GT
Power Systems Corp., for generator installation at the Human Resources Center pursuant to the
terms and conditions of the accepted contract#GEATS-061015 with the County of Suffolk,bid
opened March 25, 2015 and contracted through October 9, 2020, and extended to the Town of
Southold pursuant to §103(16) of the General Municipal Law, subject to the approval of the
Town Attorney.
Elizabeth A.Neville
Southold Town Clerk
RESULT: ADOPTED [UNANIMOUS]
MOVER: Sarah E. Nappa, Councilwoman
SECONDER:Robert Ghosio, Councilman
AYES: Nappa, Dinizio Jr, Doherty, Ghosio, Evans, Russell
AGREEMENT
THIS AGREEMENT,made on the a9 day of September, 2020,by and between the
Town of Southold, a municipal corporation of the State of New York having its principal
place of business at 53095 Main Road, Southold,New York,hereinafter called the
"Town" and G.T. Power Systems, Inc.,having its principal place of business at 56
Industrial Rd,PO Box 402,Wainscott,NY 11975, hereinafter called the"Contractor".
WITNESSETH:
WHEREAS, Contractor has submitted to the County of Suffolk a bid opened in
the office of the County Clerk on March 25, 2015, ("Bid")in response to the County's
generator construction and installation needs;
WHEREAS, specifically referenced and incorporated in said bid proposal was an
undertaking pursuant to the General Municipal Law where in the Contractor agreed that
any bid proposal offered could be accepted by other municipalities;
WHEREAS, after a public bidding period,the Contractor's bid was awarded and
a contract#GEATS-061015 was then entered into between the Contractor and the County
of Suffolk,a governmental agency;
WHEREAS,in accordance with §103(16)of the General Municipal Law, contract
#GEATS-061015 between the County of Suffolk and the Contractor, and the Extension
of Contract to Political Subdivisions provisions of the contract,the Town of Southold
wishes to `piggyback' on to such contract award, a copy of which is attached hereto as
Exhibits `B"and"C"; and
WHEREAS,the Town Board of the Town of Southold by Resolution No. 2020-
568 adopted on September 8,2020 authorized the Town Supervisor to enter into an
agreement with the Contractor to remove the existing generator and to replace and install
a new generator at the Human Resources Center as detailed in the offer letter of the
Contractor dated August 27, 2020 attached herewith as Exhibit"A";
NOW,THEREFORE;it is mutually covenanted and agreed by and between the
parties hereto as follows:
I. DEFINITIONS
Terms defined in the Bid Solicitation shall have the same meaning as if
defined herein. For the purposes of this agreement where Exhibits specify"County of
Suffolk"or"Suffolk County"the word"Southold" shall be substituted with the same
force and effect as contained therein.
II. SCOPE OF SERVICES
The Contractor shall perform the services in accordance with the
description of those services as set forth in the August 27,2020 offer letter, Contract, the
Contract Award Letter, for the County of Suffolk attached thereto as Exhibits"A", `B',
and"C", al1 construction to be completed by November 1, 2020.
j III. TERM OF AGREEMENT
The term of this Agreement shall be from the date of execution until the
completion of all construction.
I
IV. PRICE SCHEDULE/COMPENSATION
The contractor will charge the Town Thirty Four Thousand One Hundred
and Forty Seven Dollars and Fifty Cents ($34,147.50)for the removal of the existing
generator and the installation of new generator at the Human Resource Center.
V. PAYMENTS
A. The Town shall pay the Contractor upon the submission of a
voucher at the completion of the project. Such voucher shall be due and payable within
45 days after receipt of such voucher, but such sum shall not be due and payable by the
Town until the Town Board of the Town has audited and approved for payment the
voucher to be submitted by Contractor in connection therewith.
The Town Board shall process any voucher received from Contractor as
expeditiously as possible. In the event that the Town disputes or objects to any portion of
any voucher submitted by Contractor pursuant to this paragraph,the Town shall,within
30 days of the receipt of such voucher,notify Contractor in writing of such dispute or
objection. Contractor acknowledges that Contractor is familiar with the requirements of
section 118 of the Town Law which, in effect,prohibit payment of any of Contractor's
claims against the Town unless an itemized voucher therefore shall have been presented
to the Town Board or Town Comptroller and shall have been audited and allowed by the
Town Board or Town Comptroller.
The acceptance by the Contractor of payment shall be, and shall operate as a
release to the Town from all claims and all liabilities to the Contractor for all the things
done or furnished in connection with this work and for every act and neglect of the Town
and others relating to or arising out of,this Contract,up to the date of the voucher, except
Contractor's claims for interest upon the final payment, if this payment be improperly
delayed. No payment,however final or otherwise, shall operate to release the Contractor
or its sureties from any obligations under this Contract.
-2-
The Town shall be entitled to deduct from any payment owning to Contractor any
sums expended by the Town to cure any default or other Agreement non-compliance by
Contractor or to protect the Town from loss on account of claims filed or reasonably
anticipated to be filed.
VI. CONTRACTOR'S WARRANTIES AND REPRESENTATIONS,
Contractor makes the following warranties and representations:
i
A. Contractor represents that the Town has made no commitment
under this Agreement with respect to the volume of projects to be supplied during the
term of this Agreement.
B. Contractor warrants that Contractor shall comply with all federal,
state and local laws, ordinances, and regulations applicable to all of the services to be
performed by Contractor.
C. The Contractor represents that Contractor shall utilize its best
efforts to insure that Minority and Women Owned Businesses (MBE's and WBE's)have
the opportunity to participate as subcontractors under this Agreement. In the event the
Contractor subcontracts twenty-five percent(25%) or more of its work hereunder,
Contractor shall submit to the Town a WBE Utilization Plan,prior to execution of this
Agreement.
t
VII. INDEMNIFCATION INSURANCE/BONDS
A. Contractor agrees to defend,indemnify and save harmless the
Town of Southold against any and all liability, loss, damage,detriment, suit, claim,
demand, cost, charge, attorneys' fees and expenses of whatever kind or nature which the
Town may directly or indirectly incur, suffer or be required to pay by reason of or in
consequence of the Contractor carrying out or performing under the terms of this
Agreement, or failure to carry out any of the provisions, duties, services or requirements
of this Agreement,whether such losses and damages are suffered or sustained by the
Town directly or by its employees, licensees, agents, engineers, citizens or by other
persons or corporations, including any of Contractor's employees or agents who may seek
to hold the Town liable therefore. This obligation shall be ongoing, shall survive the
term of this Agreement and include,but not be limited to, claims concerning non-sudden
environmental impairments.
The Contractor shall join in the commencement of any action or
proceeding or in the defense of any action or proceeding which in the opinion of the
Town constitutes actual or threatened interference or interruption with the Town's rights
hereunder, including all appeals which,in the opinion of the Town,may be necessary.
-3-
B. Contractor shall procure and maintain the insurance described in
Exhibit"A" for a period commencing on the date of this Agreement and terminating no
earlier than one year following termination of services under this Agreement. All such
insurance coverage shall name the Town as an additional insured and shall provide that
the coverage shall not be changed or canceled until thirty(30) days written notice has
been given to the Town. All such insurance shall be issued by a company duly
authorized to transact business in the State of New York and acceptable to the Town and
shall include all riders and additional coverage necessary to insure that Contractor will be
financially able to meet its obligations under the foregoing indemnification.
VIII. FORCE MAJEURE
If either party is delayed or prevented from fulfilling any of its obligations
under this Agreement due to any act, event or condition,whether affecting the Town,the
Contractor, or the Destination Site, to the extent that it materially and adversely affects
the ability of either party to perforin any obligation hereunder(except for payment
obligations), and if such act, event or condition is beyond the reasonable control and is
not also the result of the willful or negligent action,inaction, or fault of the party relying
thereon as justification for not performing an obligation or complying with any condition
required of such party under the Agreement,the time for fulfilling that obligation shall be
extended day-by-day for the period of the uncontrollable circumstance;provided,
however,that the contesting in good faith or the failure in good faith to contest such
action or inaction shall not be construed as willful or negligent action or a lack of
reasonable diligence of either party. Subject to the foregoing, such acts or events shall
include the following:
(1) an act of God(but not including reasonable anticipated weather
conditions for the geographic area of the Town or Destination Site)hurricane, landslide,
lightning, earthquake, fire, explosion, flood, sabotage or similar occurrence, acts of a
public enemy, extortion,war,blockade or insurrection,riot or civil disturbance;
(2) the failure of any appropriate federal, state, county, town or local
public agency or private utility having jurisdiction in the areas in which the Contractor is
located to provide and maintain utilities, services,water and sewer lines and power
transmission lines which are required for the operation;
(3) governmental pre-emption of materials or services in connection
with a public emergency or any condemnation or other taking by eminent domain of any
portion of the Contractor's facilities; and
(4) the presence of hazardous waste upon,beneath or migrating from
the Contractor Facilities.
It is specifically understood that none of the following acts or conditions
shall constitute uncontrollable circumstances: (a) general economic conditions, interest
-4-
or inflation rates, or currency fluctuations; (b) the financial condition of the Town, the
Contractor, any of its affiliates or any subcontractor; (c)union work rules,requirements
or demands which have the effect of increasing the number of employees employed
otherwise increasing the cost to the Contractor of operating its haul operation or the
Destination Site; (d) equipment failure; (e) any impact of prevailing wage law, customs
practices on the Contractor's costs; (f) any act, event or circumstances occurring outside
of the United States; or(g) any change in law or in the permit conditions or status.
IX. SUBCONTRACTS
Contractor shall not enter into any subcontracts in connection with the
services to be performed by Contractor hereunder without the prior written approval by
the Town of such subcontracts. All such subcontracts shall make express reference to the
terms and conditions of this Agreement and shall obligate the subcontractor to comply
with all applicable federal, state and local laws, ordinances or regulations relating to the
services to be performed under the subcontract. In the event the subcontractor is required
to furnish any insurance or bonds for the benefit of Contractor,the Town shall also be
named as an additional insured or obligee.
X. PREVAILING WAGE RATES
Contractor agrees to comply with the provisions of the New York State
Labor Laws and the Federal Davis-Bacon wage determination relating to the payment of
prevailing wage rates to the extent applicable. In the event that at any time during
performance under this Agreement the Contractor is required to increase the wages paid
to any of its employees as a result of such requirement,all costs shall be borne
exclusively by Contractor.
XI. DEFAULT
In the event the Contractor fails to perform its obligations under the
Agreement, the Town may terminate the Agreement,procure the services from other
sources and hold the Contractor responsible for any costs incurred. The Town may also
deduct such costs from payments owing to the Contractor. The Town reserves the right
to terminate the Agreement for just cause.
XII. LIMITATION OF FUNDS
The Contractor agrees that this Agreement shall be deemed executory only
to the extent of the funds currently available for the purposes of this Agreement and that
the Town incurs no liability beyond those available by authorization of the Town Board
as of the date of this Agreement.
-5-
XIII. DISPUTES/ARBITRATION
Any disputes between the parties to this Agreement may be referred to
arbitration by mutual agreement of the parties. Absent such an agreement, any actions or
claims by either party hereto shall be commenced in Supreme Court, Suffolk County,
New York.
In the event the parties agree to arbitrate a dispute, such arbitration shall
be conducted in accordance with the rules of the American Arbitration Association. In
no event shall any demand for arbitration be made after the date when institution of legal
or equitable proceedings based on such claim or dispute would be barred by the
applicable statute of limitations. An award rendered by arbitrators following any such
! arbitration shall be final and judgment may be entered upon it in accordance with
i applicable law in any court having jurisdiction thereof.
1
XIV. MISCELLANEOUS
A. This Agreement shall be governed by the laws of the State of New
York.
B. Contractor shall not assign, convey or otherwise transfer its rights
or obligations under this Agreement without the prior written consent of the Town.
C. This Agreement, including all Exhibits and documents referred to ,
herein, along with the Specifications, Solicitation and the Bid, and all Appendices and
Exhibits thereto,represent the entire agreement between the Town and Contractor
relating to the services to be performed hereunder. This Agreement may be modified
only by written agreement of Contractor and the Town.
D. To the extent of any inconsistency among the documents
constituting the agreement of the parties,the priority among those documents shall be this
Agreement.
E. Without limiting any other right and/or remedy which the Town
may have at law or under this Agreement,if the Contractor is adjudged bankrupt or
makes an assignment for the benefit of creditors or a receiver is appointed for the
Contractor or any insolvency arrangement proceedings are instituted by or against the
Contractor, the Town may terminate this Agreement.
F. Contractor agrees that it will conduct itself consistent with its
status, said status being that of an independent contractor and, Contractor, its employees
or agents will neither hold themselves out nor claim to be an officer or employee of the
Town of Southold nor make claim to any right accruing thereto including,but not limited
to,Worker's Compensation, Unemployment Benefits, Social Security or retirement
membership or credit.
-6-
G. If any provision of this Agreement shall for any reason he held to
be invalid or unenforceable,the invalidity or unenforceability of such provision shall not
affect any of the remaining provisions of this Agreement and this Agreement shall be
enforced as if such invalid and unenforceable provision had not been contained herein.
H. Contractor agrees that it shall not discriminate and that it shall
cause there to be no discrimination against any employee who is employed in the work,
or against any applicant for such employment,because of race,religion, color, sex, age,
marital status,handicap or national origin in any manner prohibited by the laws of the
United States or of the State of New York. These requirements shall include, but not be
limited to,the following: employment;upgrading, demotion or transfer;recruitment or
recruitment advertising; layoff or termination; rates of pay or other forms of
compensation; and selection for training.
I
XV. NOTICES
All notices required to be given hereunder shall be made in writing by first
class mail addressed as follows:
If to the Town: Supervisor of the Town of Southold
Town Hall
53095 Main Road
P.O. Box 1179
Southold,New York 11971-0959
With a copy to: Town Engineer
Town of Southold
53095 Main Road
P.O. Box 1179
Southold, NY 11971-0959
If to the Contractor: G.T. Power Systems, Inc.
56 Industrial Rd.
P.O. Box 402
Wainscott,NY 11975
XVI. REQUIRED PROVISIONS OF LAW
Each and every provision of law and clause required by law to be inserted in this
Contract shall be deemed to have been inserted herein. If any such provision is not
inserted, through mistake or otherwise,then upon the application of either party, this
Contract shall be physically amended forthwith to make such insertion. In particular,the
Contractor shall, among other things, fully comply with:
(a) Labor Law section 220-e and Executive Law sections 291-299 and the
Civil Rights Law relating to prohibition against discrimination and
providing equal opportunity.
(b) Affirmative action as required by the Labor Law.
-7-
(c) Prevention of dust hazard required by Labor Law section 222-a.
(d) Preference in employment of persons required by Labor Law section 222.
(e) Eight-hour workday as required by Labor Law section 220(2).
(f) The parties hereto, in accordance with the provisions of section 220(3) of
the Labor Law,hereby agree that there shall be paid each employee
engaged in work under this Contract not less than the wage rate and
supplements set opposite the trade or occupation in which he/she is
engaged,which are the wage rates and supplements established as the
prevailing rate of wages for the work covered by this Contract.
i. Labor classifications not appearing on the schedule of wages can
be used only with the consent of the Owner and then the rate to be
paid will be given by the Owner after being advised by the
Department of Labor.
ii. The Contractor shall post in a prominent and accessible place on
the site of the work a legible statement of all wage rates and
supplements, as specified in the Contract, for the various classes of
mechanics,workingmen/women, or laborers employed on the
work.
XVI. AUTHORITY FOR EXECUTION ON BEHALF OF THE TOWN
The Supervisor has executed this Agreement pursuant to a Resolution adopted by
the Town Board of the Town of Southold, at a meeting thereof held on September
2020. Scott A. Russell, Supervisor,whose signature appears hereafter,is duly authorized
and empowered to execute this instrument and enter into such an Agreement on behalf of
the Town. This instrument shall be executed in duplicate. At least one copy shall be
permanently filed, after execution thereof, in the office of the Town Clerk, Elizabeth
Neville.
IN WITNESS WHEREOF,the parties hereto have executed this Agreement on
the day and year first above written.
TOVOFSOOLD
By: sell, Supe isor
G.T. POWER PYSTEMS, INC.
By; LAI
k4 �— 4t �
F�Grpird Yyf�.A.
-8-
STATE OF NEW YORK)
)ss..
COUNTY OF SUFFOLK)
f- 000
On this &4 day of in the year 2020 before me, the undersigned,
personally appeared SCOTT A. RUSSELL,personally known to me or proved to me on
the basis of satisfactory evidence to be the individual whose name is subscribed to the
within instrument and acknowledged to me that he executed the same in his capacity and
j that by his signature on the instrument,the individual or the person upon whose behalf of
which the individual acted, executed the instrument.
3 A .
Notary Public
LAUREN M. STANDISH
Notary Public-State of New York
STATE OF NEW YORK) No.01ST6164008
Qualified in Suffolk County
ss.: Commission Expires April 9, 2023
COUNTY OF SUFFOLK)
On this A day of September in the year 2020 before me,the undersigned,
personally (;Q,yp,r(,{ rv✓zi.,Authorized Agent of G.T.Power Systems, Inc.personally
known to me or proved to me on the basis of satisfactory evidence to be the individual
whose name is subscribed to the within instrument and acknowledged to me that he
executed the same in his capacity and that by his signature on the instrument,the
individual or the person upon whose behalf of which the individual acted, executed the
instrument. /
Notary Public
EDWARD M WALSH
NOTARY PUBLIC,STATE OF NEW YORK
Registration No.01 WA6157416
Quallfled In Suffolk County -
My Commaalon gxpiran Doc 11,2022
-9-
i
i
f
EXIIILIT "A"
EXHIBIT "A"
G,T, P 0 WhE R S YS TENS, IN C
Generator Salt>tiorns
sales-Service-Parts-Installation
24 hoar emergency service
August 27,2020
Town of Southold
Michael Collins
Via email: Michael.collins aftown.Southold.nya.ts
RE:Human Resources Center
Dear Michael,
Below is your cost on the following emergency standby generator system under Suffolk
County Contract GEATS-061015.
The generator will be in an aluminum sound enclosure with main line circuit breaker,
battery,battery rack and cables,'battery charger, engine hour meter,digital control panel,
critical grade muffler,two-year warranty, and seven-day exercise clock. This includes
freight,jobsite delivery and start up inspection.
MTU On Site 60kw,208v, 3ph diesel unit
Aluminum level 3 sound enclosure
72 hr/370 gal double wall base fuel tank $29,647.50 tax exempt
Crane service to remove old and set new $ 1,000.00 tax exempt
To disconnect and dispose of the existing gen set
Modify wiring for new gen set
Tie into existing automatic transfer switch
Test unit
Run and adjust to spec
Perform factory startup inspection $3,500.00 tax exempt
This"gtaote is based on current contract.
Any permits are responsibility of property owner
Fuel fill is responsibility of customer.
GT Power Systems is a full sales and service distributor offering 24 hour emergency
service to all our valued customers. Please review and call me with any questions you
may have.
Thank you,
Gerard Turza
PO Box 402, 56 Industrial Rd., Wainscott,New York 11975
Ph: 631-537-8890 Fax: 631-537-4143 Email: gtpivrsys@aol.com
WWW.GTPOWERSYSTEMSNY.COM
EXHIBIT "B"
COUNTY OF SUFFOLK
0
STEVEN BELLONE
SUFFOLK COUNTY EXECUTIVE
OFFICE OF CENTRAL PROCUREMENT
NOTICE OF CONTRACT
4 MONTH EXTENSION
ANNUAL REQUIREMENTS GENERATOR-EMERGENCY AND AUTOMATIC COMMODITY CODE: 28579
CONTRACT: TRANSFER SWITCHES
CONTRACT#: GEATS-061015 INITIATING DEPT: DPW
OPENING DATE: 03-25-2015 8199
PERIOD OF CONTRACT: 06-10-2019 THROUGH 10-09-2020 BID#: 15LPW/24687
VENDOR: GT POWER SYSTEMS CORP.
56 INDUSTRIAL ROAD P.O. BOX 402
WAINSCOTT NY 11975
VENDOR ID: VC0010657
CONTACT: GERARD TURZA
PHONE: 631-537-5212
FAX: , 631-537-4143
EMAIL: gtpwrsys@aol.com
ADDITIONAL VENDORS: CLICK HERE
DETAIL PAGE: CLICK HERE
ATTACHMENT: CLICK HERE
DELIVERY: FOB-DESTINATION
POLITICAL THIS CONTRACT IS AVAILABLE FOR USE BY OTHER MUNICIPALITIES
SUBDIVISIONS:
FOR FURTHER INFORMATION ROBERT PIERRO
CONTACT PURCHASING AGENT: 631-852-5216
08-21-2020
SUFFOLK COUNTY IS AN EQUAL OPPORTUNITY/AFFIRMATIVE ACTION EMPLOYER
(631)852-5196
335 YAPHANK AVENUE YAPHANK,N.Y.11980 FAX(631)852-5221
Return to Contract List Return to Search Page
For technical assistance or technical comments CLICK HERE
EXHIBIT "C"
GENERATOR-EMERGENCY AND AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
ARS
ENERGY/ALTER
VENDOR G T POWER NATE POWER
ITEM SIZE TYPE DESCRIPTION UNIT PRICING UNIT PRICING
1 30KW LIQUID PROPANE 120/240/30 $ 12,295.60
2 30KW LIQUID PROPANE 120/208/30 $ 12,295.60
3 30KW LIQUID PROPANE 277/480/30 $ 13,095.68
4 30KW LIQUID PROPANE 120/240/10 $ 12,295.60
5 30KW NATURAL GAS 120/240/30 $ 12,298.60
6 30KW NATURAL GAS 120/208/30 $ 12,298.60
7 30KW NATURAL GAS 277/480/30 $ 13,095.68
8 30KW NATURAL GAS 120/240/10 $ 12,298.60
DIESEL WBASE MOUNTED TANK—72
9 30KW HOURS 120/240/30 $ 19,767.60
DIESEL WBASE MOUNTED TANK—72
10 30KW HOURS 120/208/30 $ 19,767.60
DIESEL WBASE MOUNTED TANK—72
11 30KW HOURS 277/480/30 $ 19,767.60
DIESEL WBASE MOUNTED TANK—72
12 30KW HOURS 120/240/10 $ 19,767.60
13 30KW DIESEL W/O FUEL(GENERATOR ONLY) 120/240/30 $ 17,992.80
14 30KW DIESEL W/O FUEL(GENERATOR ONLY) 120/208/30 $ 17,992.80
15 30KW DIESEL W/O FUEL(GENERATOR ONLY) 277/480/30 $ 17,992.80
16 30KW DIESEL W/O FUEL(GENERATOR ONLY) 120/240/10 $ 17,992.80
17 60 KW LIQUID PROPANE 120/240/30 $ 20,500.00
18 60 KW LIQUID PROPANE 120/208/30 $ 20,500.00
19 60 KW LIQUID PROPANE 277/480/30 $ 20,500.00
20 60 KW LIQUID PROPANE 120/240/10 $ 20,500.00
21 60 KW NATURAL GAS 120/240/30 $ 20,500.00
22 60 KW NATURAL GAS 120/208/30 $ 20,500.00
23 60 KW NATURAL GAS 277/480/30 $ 20,500.00
24 60 KW NATURAL GAS 120/240/10 $ 20,500.00
DIESEL WBASE MOUNTED TANK—72
25 60 KW HOURS 120/240/30 $ 26,647.50
DIESEL WBASE MOUNTED TANK—72
26 60 KW HOURS 120/208/30 $ 26,647.50
DIESEL WBASE MOUNTED TANK—72
27 60 KW HOURS 277/480/30 $ 26,647.50
DIESEL WBASE MOUNTED TANK—72
28 60 KW HOURS 120/240/10 $ 26,647.50
29 61 KW DIESEL W/O FUEL(GENERATOR ONLY) 120/240/30 $ 22,222.74
30 62 KW DIESEL W/O FUEL(GENERATOR ONLY) 120/208/30 $ 22,222.74
31 63 KW DIESEL W/O FUEL(GENERATOR ONLY) 277/480/30 $ 22,222.74
32 64 KW DIESEL W/O FUEL(GENERATOR ONLY) 120/240/10 $ 22,222.74
33 100 KW LIQUID PROPANE 120/240/30 $ 28,000.00
34 100 KW LIQUID PROPANE 120/208/30 $ 28,000.00
35 100 KW LIQUID PROPANE 277/480/30 $ 28,000.00
36 100 KW LIQUID PROPANE 120/240/10 $ 28,000.00
37 100 KW NATURAL GAS 120/240/30 $ 28,000.00
38 100 KW NATURAL GAS 120/208/30 $ 28,000.00
39 100 KW NATURAL GAS 277/480/30 $ 28,000.00
40 100 KW NATURAL GAS 120/240/10 $ 28,000.00
DIESEL WBASE MOUNTED TANK—72
41 100 KW HOURS 120/240/30 $ 36,304.86
Page 3 of 51
GENERATOR-EMERGENCY AND AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
ARS
ENERGY/ALTER
VENDOR G T POWER NATE POWER
ITEM SIZE TYPE DESCRIPTION UNIT PRICING UNIT PRICING
DIESEL WBASE MOUNTED TANK—72
42 100 KW HOURS 120/208/30 $ 36,304.86
DIESEL WBASE MOUNTED TANK—72
43 100 KW HOURS 277/480/30 $ 36,304.86
DIESEL WBASE MOUNTED TANK—72
44 100 KW HOURS 120/240/10 $ 36,304.86
45 100 KW DIESEL W/O FUEL(GENERATOR ONLY) 120/240/30 $ 30,061.44
46 100 KW DIESEL W/O FUEL(GENERATOR ONLY) 120/208/30 $ 30,061.44
47 100 KW DIESEL W/O FUEL(GENERATOR ONLY) 277/480/30 $ 30,061.44
48 100 KW DIESEL W/O FUEL(GENERATOR ONLY) 120/240/10 $ 30,061.44
49 150KW LIQUID PROPANE 120/240/30 $ 33,933.00
50 150KW LIQUID PROPANE 120/208/30 $ 39,933.00
51 150KW LIQUID PROPANE 277/480/30 $ 39,933.00
52 150KW LIQUID PROPANE 120/240/10 $ 39,933.00
53 150KW NATURAL GAS 120/240/30 $ 39,933.00
54 150KW NATURAL GAS 120/208/30 $ 39,933.00
55 150KW NATURAL GAS 277/480/30 $ 39,933.00
56 150KW NATURAL GAS 120/240/10 $ 39,933.00
DIESEL WBASE MOUNTED TANK—72
57 150KW HOURS 120/240/30 $ 43,821.24
DIESEL WBASE MOUNTED TANK—72
58 150KW HOURS 120/208/30 $ 43,821.24
DIESEL WBASE MOUNTED TANK—72
59 150KW HOURS 277/480/30 $ 43,821.24
DIESEL WBASE MOUNTED TANK—72
60 150KW HOURS 120/240/10 $ 43,821.24
61 150KW DIESEL W/O FUEL(GENERATOR ONLY) 120/240/30 $ 37,430.94
62 150KW DIESEL W/O FUEL(GENERATOR ONLY) 120/208/30 $ 37,430.94
63 150KW DIESEL W/O FUEL(GENERATOR ONLY) 277/480/30 $ 37,430.94
64 150KW DIESEL W/O FUEL(GENERATOR ONLY) 120/240/10 $ 37,430.94
65 20OKW LIQUID PROPANE 120/240/30 $ 140,350.00
66 20OKW LIQUID PROPANE 120/208/30 $ 138,350.00
67 20OKW LIQUID PROPANE 277/480/30 $ 138,350.00
68 20OKW LIQUID PROPANE 120/240/10 $ 140,350.00
69 20OKW NATURAL GAS 120/240/30 $ 87,638.00
70 20OKW NATURAL GAS 120/208/30 $ 87,638.00
71 20OKW NATURAL GAS 277/480/30 $ 87,638.00
72 20OKW NATURAL GAS 120/240/10 $ 87,638.00
DIESEL WBASE MOUNTED TANK—72
73 20OKW HOURS 120/240/30 $ 56,229.54
DIESEL WBASE MOUNTED TANK—72
74 20OKW HOURS 120/208/30 $ 56,229.54
DIESEL WBASE MOUNTED TANK—72
75 20OKW HOURS 277/480/30 $ 56,229.54
DIESEL WBASE MOUNTED TANK—72
76 20OKW HOURS 120/240/10 $ 56,229.54
77 20OKW DIESEL W/O FUEL(GENERATOR ONLY) 120/240/30 $ 40,159.44
78 20OKW DIESEL W/O FUEL(GENERATOR ONLY) 120/208/30 $ 40,159.44
79 20OKW DIESEL W/O FUEL(GENERATOR ONLY) 277/480/30 $ 40,159.44
80 20OKW DIESEL W/O FUEL(GENERATOR ONLY) 120/240/10 $ 40,159.44
81 300 KW I LIQUID PROPANE 120/240/30 $ 220,000.00
Page 4 of 51
GENERATOR-EMERGENCY AND AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
ARS
ENERGY/ALTER
VENDOR G T POWER NATE POWER
ITEM SIZE TYPE DESCRIPTION UNIT PRICING UNIT PRICING
82 300 KW LIQUID PROPANE 120/208/30 $ 220,000.00
83 300 KW LIQUID PROPANE 277/480/30 $ 220,000.00
84 300 KW LIQUID PROPANE 120/240/10 $ 220,000.00
85 300 KW NATURAL GAS 120/240/30 $ 131,690.00
86 300 KW NATURAL GAS 120/208/30 $ 131,690.00
87 300 KW NATURAL GAS 277/480/30 $ 131,690.00
88 300 KW NATURAL GAS 120/240/10 $ 131,690.00
DIESEL WBASE MOUNTED TANK—72
89 300 KW HOURS 120/240/30 $ 74,354.94
DIESEL WBASE MOUNTED TANK—72
90 300 KW HOURS 120/208/30 $ 74,354.94
DIESEL WBASE MOUNTED TANK—72
91 300 KW HOURS 277/480/30 $ 74,354.94
DIESEL WBASE MOUNTED TANK—72
92 300 KW HOURS 120/240/10 $ 74,354.94
93 300 KW DIESEL W/O FUEL(GENERATOR ONLY) 120/240/30 $ 63,209.40
94 300 KW DIESEL W/O FUEL,(GENERATOR ONLY) 120/208/30 $ 63,209.40
95 300 KW DIESEL W/O FUEL(GENERATOR ONLY) 277/480/30 $ 63,209.40
96 300 KW DIESEL W/O FUEL(GENERATOR ONLY) 120/240/10 $ 63,209.40
97 500 KW LIQUID PROPANE 120/240/30 $ 452,300.00
98 500 KW LIQUID PROPANE 120/208/30 $ 452,300.00
99 500 KW LIQUID PROPANE 277/480/30 $ 452,300.00
100 500 KW LIQUID PROPANE 120/240/10 $ 452,300.00
101 500 KW NATURAL GAS 120/240/30 $ 240,334.00
102 500 KW NATURAL GAS 120/208/30 $ 240,334.00
103 500 KW NATURAL GAS 277/480/30 $ 240,334.00
104 500 KW NATURAL GAS 120/240/10 $ 240,334.00
DIESEL WBASE MOUNTED TANK—72
105 500 KW HOURS 120/240/30 $ 104,733.60
DIESEL WBASE MOUNTED TANK—72
106 500 KW HOURS 120/208/30 $ 104,733.60
DIESEL WBASE MOUNTED TANK—72
107 500 KW HOURS 277/480/30 $ 104,733.60
DIESEL WBASE MOUNTED TANK—72
108 500 KW HOURS 120/240/10 $ 104,733.60
109 500 KW DIESEL W/O FUEL(GENERATOR ONLY) 120/240/30 $ 87,695.52
110 500 KW DIESEL W/O FUEL(GENERATOR ONLY) 120/208/30 $ 87,695.52
111 500 KW DIESEL W/O FUEL(GENERATOR ONLY) 277/480/30 $ 87,695.52
112 500 KW DIESEL W/O FUEL(GENERATOR ONLY) 120/240/10 $ 87,695.52
113 600 KW LIQUID PROPANE 120/240/30 $ 530,500.00
114 600 KW LIQUID PROPANE 120/208/30 $ 530,500.00
115 600 KW LIQUID PROPANE 277/480/30 $ 530,500.00
116 600 KW LIQUID PROPANE 120/240/10 $ 530,500.00
117 600 KW NATURAL GAS 120/240/30 $ 245,810.00
118 600 KW NATURAL GAS 120/208/30 $ 245,810.00
119 600 KW NATURAL GAS 277/480/30 $ 245,810.00
120 600 KW NATURAL GAS 120/240/10 $ 245,810.00
DIESEL WBASE MOUNTED TANK—72
121 600 KW HOURS 120/240/30 $ 145,257.18
DIESEL WBASE MOUNTED TANK—72
122 600 KW HOURS 120/208/30 $ 145,257.18
Page 5 of 51
GENERATOR-EMERGENCY AND AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
ARS
ENERGY/ALTER
VENDOR G T POWER' NATE POWER
ITEM SIZE TYPE DESCRIPTION UNIT PRICING UNIT PRICING
DIESEL WBASE MOUNTED TANK—72
123 600 KW HOURS 277/480/30 $ 145,257.18
DIESEL WBASE MOUNTED TANK—72
124 600 KW HOURS 120/240/10 $ 145,257.18
125 600 KW DIESEL W/O FUEL(GENERATOR ONLY) 120/240/30 $ 103,910.46
126 600 KW DIESEL W/O FUEL(GENERATOR ONLY) 120/208/30 $ 103,910.46
127 600 KW DIESEL W/O FUEL(GENERATOR ONLY) 277/480/30 $ 103,910.46
128 600 KW DIESEL W/O FUEL(GENERATOR ONLY) 120/240/10 $ 103,910.46
ETHERNET IP ADDRESSABLE COMMUNICATION OF OPERATING AND
ALARM CONDITIONS TO SCADA SYSTEM FOR GENERATORS INCLUDES
THE FOLLOWING;VOLTS,AMPS,OIL PRESSURE,ENGINE
129 TEMPERATURE,OPERATING HOURS,FUWL LEVEL INCLUDED $ 1,800.00
130 AUTOMATIC TRANSFER SWITCHES-SEE PAGES 36 100 AMP $ 2,870.00
131 AUTOMATIC TRANSFER SWITCHES-SEE PAGES 36-150 AMP $ 2,870.00
132 AUTOMATIC TRANSFER SWITCHES-SEE PAGES 36 225 AMP $ 2,916.00
133 AUTOMATIC TRANSFER SWITCHES-SEE PAGES 36 300 AMP $ 3,122.00
134 AUTOMATIC TRANSFER SWITCHES-SEE PAGES 36 400 AMP $ 3,122.00
135 AUTOMATIC TRANSFER SWITCHES-SEE PAGES`36 600 AMP $ 5,163.00
136 AUTOMATIC TRANSFER SWITCHES-SEE PAGES 36 800 AMP $ 5,406.00
137 AUTOMATIC TRANSFER SWITCHES-SEE PAGES 36- 1000 AMP $ 7,310.00
138 AUTOMATIC TRANSFER SWITCHES-SEE PAGES 36 1200 AMP $ 8,888.00
139 AUTOMATIC TRANSFER SWITCHES-SEE PAGES 36 ADDRESSABLE $ 237.25
140 CABLES&CONNECTORS-SEE PAGES 34-35 250 MCM $ 371.00
141 CABLES&CONNECTORS-SEE PAGES 34-35 500 MCM $ 488.00
E-Z1016 SERIES
CAM-LOK
142 CABLES&CONNECTORS-SEE PAGES 34-35 CONNECTORS $ 52.00
REPAIR AND
143 LABOR-SEE PAGE 45 SERVICE $ 122.50 $ 140.00
EMERGENCY
144 LABOR-SEE PAGE 45 SERVICE CALLS $ 183.75 $ 210.00
SOFTWARE TO PROGRAM OR REPAIR UNIT YEARLY AT THE COUNTY'S
REQUEST THE VENDOR SHALL BE REQUIRED TO HOLD A TRAINING
FOR COUNTY EMPLOYEES ON TROUBLESHOOTING AND PM ON ALL
145 EQUIPMENT ON THE CONTRACT $ 1,000.00 $ 1,200.00
ACCESSORY
146 OPTIONAL FEATURES-SEE PAGES 4244 PACKAGE $ 268.00
CONTROLLER
147 OPTIONAL FEATURES-SEE PAGES 42-44 POWER SUPPLY $ 121.00
EXPANSION
148 OPTIONAL FEATURES-SEE PAGES 4244 MODULE $ 144.00
COMMUNICATION
149 OPTIONAL FEATURES-SEE PAGEi4244 INTERFACE $ 477.00
150 OPTIONAL FEATURES-SEE PAGES 4244 TRANSFER ALARM $ 328.00
151 OPTIONAL FEATURES-SEE PAGES 42-44 POWER METER $ 1,309.00
152 WITHSTAND AND CLOSING RATINGS INCLUDED
153 GENERATOR EXTENDED 3 YEAR WARRANTY 100%PARTS&LABOR SEE ATTACHED $ 2,000.00
Page 6 of 51
GENERATOR-EMERGENCY AND AUTOMATIC TRANSFER.SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
ARS
ENERGY/ALTER
VENDOR G T POWER NATE POWER
ITEM SIZE TYPE DESCRIPTION UNIT PRICING UNIT PRICING
154 REMOTE ANNUNCIATOR PANELS FOR GENERATORS $ 495.00
155 REMOTE ANNUNCIATOR-PANELS FOR AUTOMATIC TRANSFER $ 237.25
156 ADD POWER QUALITY METERS TO TRANSFER SWITCHES $' 290.00
157 ADD EITHER NEMA 4X OR 3R ENCLOSURE TO TRANSFER SWITCH SEE ATTACHED
158 BI FUEL CONVERSION KIT GENERATOR INSTALLED SEE ATTACHED
159 SUPPLY HIGHEST LEVEL OF SCHD ARTICLE 12 REGULATION SEE ATTACHED
LEVEL 3
160 HIGHEST LEVEL OF SOUND ATTENUATION INCLUDED
161 STAINLESS STEEL ENCLOUSURE FOR TRANSFER SWITCH SEE ATTACHED
Page 7 of 51
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
DIESEL ENGINE GENERATORS
GENERAL
1. RELATED DOCUMENTS
A. DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT,INCLUDING GENERAL
AND SUPPLEMENTARY CONDITIONS AND DIVISION 01 SPECIFICATION SECTIONS,
APPLY TO THIS SECTION.
2. SUMMARY
A. THIS SECTION INCLUDES PACKAGED ENGINE-GENERATOR SETS FOR STANDBY
POWER SUPPLY WITH THE FOLLOWING FEATURES:
• DIESEL ENGINE
• UNIT MOUNTED COOLING SYSTEM
• DGC 2020-LEVEL 1 EXPANDED
• LEVEL 3-MAXIMUM SOUND ATTENUATION(ALUMINUM)
• PERFORMANCE REQUIREMENTS FOR SENSITIVE LOADS
• LOAD BANK(TESTING ONLY)
B. RELATED SECTIONS INCLUDE THE FOLLOWING:
• SECTION 017900"DEMONSTRATION AND TRAINING"FOR SPECIFICATIONS
COVERING DEMONSTRATIONS AND TRAINING OF THE EQUIPMENT
• SECTION 260553 "IDENTIFICATION FOR ELECTRICAL SYSTEMS"FOR
SPECIFICATIONS COVERING ELECTRICAL SYSTEMS
• SECTION 260526"GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS"FOR
SPECIFICATIONS COVERING GROUNDING OF COMPONENTS
• SECTION 017823"OPERATION AND MAINTENANCE DATA"FOR MAINTENANCE AND
OPERATIONAL SPECIFICATIONS
• SECTION 260913 "ELECTRICAL POWER MONITORING AND CONTROL"FOR
SPECIFICATIONS COVERING DATA SYSTEM CONNECTIONS
• SECTION 260548"VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS"
FOR COMPLETE ENGINE-GENERATOR SET,BATTERIES,BATTERY RACKS,
ACCESSORIES,AND COMPONENTS SPECIFICATIONS.
3. DEFINITIONS
A. OPERATIONAL BANDWIDTH: THE TOTAL VARIATION FROM THE LOWEST TO HIGHEST
VALUE OF A PARAMETER OVER A RANGE OF CONDITIONS INDICATED,EXPRESSED AS
A PERCENTAGE OF THE NOMINAL VALUE OF THE PARAMETER.
B. STANDBY RATING: POWER OUTPUT RATING EQUAL TO THE POWER THE GENERATOR
SET DELIVERS CONTINUOUSLY UNDER NORMALLY VARYING LOAD FACTORS FOR
THE DURATION OF THE POWER OUTAGE.
4. ACTION SUBMITTALS
A. PRODUCT DATA:FOR EACH TYPE OF PACKAGED ENGINE GENERATOR INDICATED.
INCLUDE RATED CAPACITIES,OPERATING CHARACTERISTICS,AND FURNISHED
SPECIALTIES AND ACCESSORIES. IN ADDITION,INCLUDE THE FOLLOWING:
Page 8 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
• THERMAL DAMAGE CURVE FOR GENERATOR
• TIME-CURRENT CHARACTERISTIC OF CURVES FOR GENERATOR PROTECTIVE
DEVICE.
B. SHOP DRAWINGS:DETAILED EQUIPMENT ASSEMBLIES AND INDICATE DIMENSIONS,
WEIGHTS,LOADS,REQUIRED CLEARANCES,METHOD OF FIELD ASSEMBLY,
COMPONENTS,AND LOCATION AND SIZE OF EACH FIELD CONNECTION.
• DIMENSIONED OUTLINE PLAN AND ELEVATION DRAWING OF ENGINE-
GENERATOR SET AND OTHER COMPONENTS SPECIFIED.
• DESIGN CALCULATIONS:SIGNED AND SEALED BY A QUALIFIED ENGINEER.
CALCULATE REQUIREMENTS FOR SELECTING VIBRATION ISOLATORS AND
SEISMIC RESTRAINTS AND FOR DESIGNING VIBRATION ISOLATION BASES.
• VIBRATION ISOLATION BASE DETAILS: SIGNED AND SEALED BY A QUALIFIED
ENGINEER. DETAIL FABRICATION,INCLUDING ANCHORAGES AND ATTACHMENTS
TO STRUCTURE AND TO SUPPORTED EQUIPMENT. INCLUDE BASE WEIGHTS.
• WIRING DIAGRAMS:POWER,SIGNAL,AND CONTROL WIRING.
5. INFORMATIONAL SUBMITTALS
A. MANUFACTURER SEISMIC QUALIFICATION CERTIFICATION:SUBMIT CERTIFICATION
THAT COMPLETE ENGINE-GENERATOR SET,BATTERIES,BATTERY RACKS,
ACCESSORIES,AND COMPONENTS WILL WITHSTAND SEISMIC FORCES DEFINED IN
SECTION 260548"VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS."
INCLUDE THE FOLLOWING:
• BASIS FOR CERTIFICATION: INDICATE WHETHER WITHSTAND CERTIFICATION IS
BASED ON ACTUAL TEST OF THE ASSEMBLED COMPONENTS OR ON
CALCULATION.
➢ THE TERM"WITHSTAND"MEANS"THE UNIT WILL REMAIN IN PLACE
WITHOUT SEPARATION OF ANY PARTS FROM THE DEVICE WHEN
SUBJECTED TO THE SEISMIC FORCES SPECIFIED."
➢ THE TERM"WITHSTAND"MEANS"THE UNIT WILL REMAIN IN PLACE
WITHOUT SEPARATION OF ANY PARTS FROM THE DEVICE WHEN
SUBJECTED TO THE SEISMIC FORCES SPECIFIED AND THE UNIT WILL BE
FULLY OPERATIONAL AFTER THE SEISMIC EVENT"
• DIMENSIONED OUTLINE DRAWINGS OF EQUIPMENT UNIT:IDENTIFY CENTER OF
GRAVITY AND LOCATE AND DESCRIBE MOUNTING AND ANCHORAGE
PROVISIONS.
• DETAILED DESCRIPTION OF EQUIPMENT ANCHORAGE DEVICES ON WHICH THE
CERTIFICATION IS BASED AND THEIR INSTALLATION REQUIREMENTS.
B. QUALIFICATION DATA
• THIS GENERATOR SHALL BE MTU ONSITE ENERGY OR EQUAL AND WHO HAS BEEN
REGULARLY ENGAGED IN THE PRODUCTION OF ENGINE-GENERATOR SETS AND
ASSOCIATED CONTROLS FOR A MINIMUM OF TWENTY YEARS,THEREBY
IDENTIFYING ONE SOURCE OF SUPPLY AND RESPONSIBILITY. EQUAL MEANS
HAVING THE SAME SYSTEM CONFIGURATION,OPERATION,FOOTPRINT OF THE
ENGINE-GENERATOR SET WITH THE SAME SIZING SOLUTION. ALTERNATE
OFFERINGS MUST BE SUBMITTED FOR APPROVAL 14 DAYS PRIOR TO BID.
• THE MANUFACTURER SHALL PROVIDE FACTORY-TRAINED SERVICE AND PARTS
SUPPORT THROUGH A FACTORY AUTHORIZED DEALER/SUPPLIER THAT IS
REGULARLY DOING BUSINESS IN THE AREA OF INSTALLATION.
Page 9 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
• THE MANUFACTURER SHALL HAVE PRINTED LITERATURE AND BROCHURES
DESCRIBING THE STANDARD SYSTEM SPECIFIED,NOT A ONE OF A KIND
FABRICATION.
• AS PART OF QUALIFICATION PROCESS;AN AUTHORIZED DEALER/SUPPLIER,
HEREIN KNOWN AS THE DEALER SHALL REPRESENT THE MANUFACTURER. TO
QUALIFY AS THE DEALER/SUPPLIER,IT MUST BE A"FULL PRODUCT LINE SALES
AND SERVICE DEALER OF MTU ONSITE ENERGY"AND SHALL HAVE 24-HOUR
SERVICE AVAILABILITY. THE DEALER/SUPPLIER MUST HAVE CERTIFIED
GENERATOR SERVICE TECHNICIANS,INVENTORY OF PARTS TO SUPPORT AFTER
SALES SERVICE AND CAN PROVE 5 YEARS OF EXPERIENCE IN THE ENGINE-
GENERATOR FIELD.
C. SOURCE QUALITY-CONTROL TEST REPORTS
• CERTIFIED SUMMARY OF PROTOTYPE-UNIT TEST REPORT.
• CERTIFIED TEST REPORTS: FOR COMPONENTS AND ACCESSORIES THAT ARE
EQUIVALENT,BUT NOT IDENTICAL,TO THOSE TESTED ON PROTOTYPE UNIT.
• CERTIFIED SUMMARY OF PERFORMANCE TESTS: CERTIFY COMPLIANCE WITH
SPECIFIED REQUIREMENT TO MEET PERFORMANCE CRITERIA FOR SENSITIVE
LOADS.
• REPORT OF FACTORY-TEST ON UNITS TO BE SHIPPED FOR THIS PROJECT,SHOWING
EVIDENCE OF COMPLIANCE WITH SPECIFIED REQUIREMENTS.
• REPORT OF SOUND GENERATION.
• REPORT OF EXHAUST EMISSIONS SHOWING COMPLIANCE WITH APPLICABLE
REGULATIONS.
• CERTIFIED TORSIONAL VIBRATION COMPATIBILITY: COMPLY WITH NFPA 110.
• OPERATION AND MAINTENANCE DATA: FOR PACKAGED ENGINE-GENERATOR
SETS TO INCLUDE EMERGENCY,OPERATION,AND MAINTENANCE MANUALS. IN
ADDITION TO ITEMS SPECIFIED IN DIVISION 1 SECTION"CLOSEOUT PROCEDURES"
INCLUDE THE FOLLOWING:
➢ LIST OF TOOLS AND REPLACEMENT ITEMS RECOMMENDED TO BE STORED AT
THE PROJECT FOR READY ACCESS. INCLUDING PART AND DRAWING
NUMBERS AND SOURCE OF SUPPLY.
D. FIELD QUALITY-CONTROL TEST REPORTS
E. WARRANTY: SPECIAL WARRANTY SPECIFIED IN THIS SECTION
6. CLOSEOUT SUBMITTALS
A. OPERATION AND MAINTENANCE DATA: FOR PACKAGED ENGINE-GENERATOR SETS
TO INCLUDE:EMERGENCY,OPERATION,AND MAINTENANCE MANUALS. IN ADDITION
TO ITEMS SPECIFIED IN DIVISION I SECTION"CLOSEOUT PROCEDURES"INCLUDE THE
FOLLOWING:
• LIST OF TOOLS AND REPLACEMENT ITEMS RECOMMENDED TO BE STORED AT THE
PROJECT FOR READY ACCESS;INCLUDING PART AND DRAWING NUMBERS,
CURRENT PRICES,AND SOURCE OF SUPPLY.
7. MAINTENANCE MATERIAL SUBMITTALS
8. QUALITY ASSURANCE
Page 10 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
A. INSTALLER QUALIFICATIONS: MANUFACTURER'S AUTHORIZED REPRESENTATIVE
WHO IS TRAINED AND APPROVED FOR INSTALLATION OF UNITS REQUIRED FOR THIS
PROJECT.
• MAINTENANCE PROXIMITY: NOT MORE THAN 2(TWO)HOURS NORMAL TRAVEL
TIME FROM INSTALLER'S PLACE OF BUSINESS TO PROJECT SITE.
• ENGINEERING RESPONSIBILITY: PREPARATION OF DATA FOR VIBRATION
ISOLATORS AND SEISMIC RESTRAINTS OF ENGINE SKID MOUNTS,INCLUDING
SHOP DRAWINGS,BASED ON THE TESTING AND ENGINEERING ANALYSIS OF
MANUFACTURER'S STANDARD UNITS IN ASSEMBLIES SIMILAR TO THOSE
INDICATED FOR THIS PROJECT.
B. MANUFACTURER QUALIFICATIONS:A QUALIFIED MANUFACTURER,MAINTAIN
WITHIN 75 MILES OF PROJECT SITE,A SERVICE CENTER CAPABLE OF PROVIDING
TRAINING,PARTS,AND EMERGENCY MAINTENANCE REPAIRS.
C. TESTING AGENCY QUALIFICATIONS: AN INDEPENDENT AGENCY,WITH THE
EXPERIENCE AND CAPABILITY TO CONDUCT THE TESTING INDICATED,THAT IS A
MEMBER COMPANY OF THE INTERNATIONAL ELECTRICAL TESTING ASSOCIATION OR
IS A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTL),AND THAT IS
ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION.
• TESTING AGENCY'S FIELD SUPERVISOR: PERSON CURRENTLY CERTIFIED BY THE
INTERNATIONAL ELECTRICAL TESTING ASSOCIATION(NETA)OR THE NATIONAL
INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES TO SUPERVISE
ON-SITE TESTING SPECIFIED IN PART 3.
D. SOURCE LIMITATIONS: OBTAIN PACKAGED ENGINE-GENERATOR SETS AND
AUXILIARY COMPONENTS THROUGH ONE SOURCE FROM A SINGLE MANUFACTURER.
E. PRODUCT OPTIONS: DRAWINGS INDICATE SIZE,PROFILES,AND DIMENSIONAL
REQUIREMENTS OF PACKAGED GENERATOR SETS AND ARE BASED ON THE SPECIFIC
SYSTEM INDICATED. REFER TO DIVISION I SECTION"PRODUCT REQUIREMENTS."
F. ELECTRICAL COMPONENTS,DEVICES,AND ACCESSORIES: LISTED AND LABELED AS
DEFINED IN NFPA 70,ARTICLE 100,BY A TESTING AGENCY ACCEPTABLE TO
AUTHORITIES HAVING JURISDICTION,AND MARKED FOR INTENDED USE.
G. COMPLY WITH ASME B15.1.
H. COMPLY WITH NFPA 37.
I. COMPLY WITH NFPA 30.
J. COMPLY WITH NFPA 70.
K. COMPLY WITH NFPA 99.
L. COMPLY WITH NFPA 110 REQUIREMENTS FOR LEVEL 1 EMERGENCY POWER SUPPLY
SYSTEM.
M. ENGINE EXHAUST EMISSIONS: COMPLY WITH APPLICABLE STATE AND LOCAL
GOVERNMENT REQUIREMENTS.
N. NOISE EMISSION: COMPLY WITH STATE AND LOCAL GOVERNMENT REQUIREMENTS
FOR MAXIMUM NOISE LEVEL AT NEARBY PROPERTY DUE TO SOUND EMITTED BY
Page 11 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
GENERATOR SET INCLUDING ENGINE,ENGINE EXHAUST,ENGINE COOLING-AIR
INTAKE AND DISCHARGE,AND OTHER COMPONENTS OF INSTALLATION.
O. ENVIRONMENTAL CONDITIONS: ENGINE-GENERATOR SYSTEM SHALL WITHSTAND
THE FOLLOWING ENVIRONMENTAL CONDITIONS WITHOUT MECHANICAL OR
ELECTRICAL DAMAGE OR DEGRADATION OF PERFORMANCE CAPABILITY:
• MINIMUM TEMPERATURE:0°F/-18°C
• MAXIMUM TEMPERATURE: 100'F/38'C
• RELATIVE HUMIDITY: 0-95 PERCENT
• ALTITUDE: 1000 FEET/305 METERS
9. WARRANTY
A. SPECIAL WARRANTY: MANUFACTURER'S STANDARD FORM IN WHICH
MANUFACTURER AGREES TO REPAIR OR REPLACE COMPONENTS OF PACKAGED
ENGINE-GENERATOR SETS AND ASSOCIATED AUXILIARY COMPONENTS THAT FAIL IN
MATERIALS OR WORKMANSHIP WITHIN SPECIFIED WARRANTY PERIOD.
• WARRANTY PERIOD- 5 YEAR COMPREHENSIVE WARRANTY SUPPORTED BY
FACTORY FROM DATE OF SUBSTANTIAL COMPLETION. LOCAL DEALER
WARRANTY WILL NOT BE ACCEPTABLE. SUPPLYING DEALER/DISTRIBUTOR MUST
MAINTAIN A FACILITY WITHIN 75 MILES OF PROJECT WITH MINIMUM OF 6
FACTORY TRAINED TECHNICIANS EACH WITH A STOCKED SERVICE VEHICLE.
THEY SHALL HAVE AN INVENTORY OF FACTORY REPLACEMENT PARTS ALONG
WITH SPECIAL TOOLS AND TESTING EQUIPMENT. OWNER HAS RIGHT TO INSPECT
FACILITY FOR COMPLIANCE.
• PROVIDING DEALER/DISTRIBUTOR MUST BE ABLE TO WARRANTY COMPLETE
GENERATOR PACKAGE.
• MUST BE AUTHORIZED DIESEL ENGINE SERVICE FACILITY FOR PRODUCT BEING
SUPPLIED.
• PROVIDE 24 HOUR EMERGENCY SERVICE, 365 DAYS A YEAR, WITH 2 HOUR
RESPONSE TIME FOR EMERGENCY SERVICE AND 24 HOUR FOR NON-EMERGENCY
SERVICE.
PRODUCTS
1. MANUFACTURERS
A. BASIS-OF-DESIGN PRODUCT: SUBJECT TO COMPLIANCE WITH REQUIREMENTS,
PROVIDE MTU ONSITE ENERGY MODEL DS00125D6S-A OR A COMPARABLE PRODUCT
BY ONE OF THE FOLLOWING:
• MTU ONSITE ENERGY OR EQUAL
ANY CHANGES TO THE GENERATOR SET INSTALLATION REQUIREMENTS DUE TO
MANUFACTURERS'PRODUCTS DIFFERING FROM THE BASIS-OF-DESIGN PRODUCT ARE
THE RESPONSIBILITY OF THE CONTRACTOR.
2. ENGINE-GENERATOR SET
A KW/ KVA, 120/208V,3 PHASE, 12 WIRE,60HZ PACKAGED ENGINE GENERATOR
SET SHALL BE A COORDINATED ASSEMBLY OF COMPATIBLE COMPONENTS.
Page 12 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
B. FACTORY-ASSEMBLED AND-TESTED,ENGINE-GENERATOR SET.
C. MOUNTING FRAME: MAINTAIN ALIGNMENT OF MOUNTED COMPONENTS WITHOUT
DEPENDING ON CONCRETE FOUNDATION;AND HAVE LIFTING ATTACHMENTS.
D. CAPACITIES AND CHARACTERISTICS:
• POWER OUTPUT RATINGS: NOMINAL RATINGS AS INDICATED,WITH CAPACITY AS
REQUIRED TO OPERATE AS A UNIT AS EVIDENCE BY RECORDS OF PROTOTYPE
TESTING.
• OUTPUT CONNECTIONS: 208 VOLT 3 PHASE 12W 60HZ
• NAMEPLATES: FOR EACH MAJOR SYSTEM COMPONENT TO IDENTIFY
MANUFACTURER'S NAME AND ADDRESS,AND MODEL AND SERIAL NUMBER OF
COMPONENT.
E. GENERATOR-SET PERFORMANCE WITH SHUNT EXCITATION:
• STEADY-STATE VOLTAGE OPERATIONAL BANDWIDTH: 1 PERCENT OF RATED
OUTPUT VOLTAGE FROM NO LOAD TO FULL LOAD.
• TRANSIENT VOLTAGE PERFORMANCE: NOT MORE THAN 20 PERCENT VARIATION
FOR 50 PERCENT STEP-LOAD INCREASE OR DECREASE. VOLTAGE SHALL
RECOVER AND REMAIN WITHIN THE STEADY-STATE OPERATING BAND WITHIN
THREE TO FOUR SECONDS.
• STEADY-STATE FREQUENCY OPERATIONAL BANDWIDTH: 0.25 PERCENT OF
RATED FREQUENCY FROM NO LOAD TO FULL LOAD.
• STEADY-STATE FREQUENCY.STABILITY: WHEN SYSTEM IS OPERATING AT ANY
CONSTANT LOAD WITHIN THE RATED LOAD,THERE SHALL BE NO RANDOM SPEED
VARIATIONS OUTSIDE THE STEADY-STATE OPERATIONAL BAND AND NO
HUNTING OR SURGING OF SPEED.
• TRANSIENT FREQUENCY PERFORMANCE: LESS THAN 5 PERCENT VARIATION FOR
50 PERCENT STEP-LOAD INCREASE OR DECREASE. FREQUENCY SHALL RECOVER
AND REMAIN WITHIN THE STEADY-STATE OPERATING BAND WITHIN FIVE
SECONDS.
• START TIME: COMPLY WITH NFPA 110,TYPE 10,SYSTEM REQUIREMENTS.
3. ENGINE JOHN DEERE
A. BASIC ENGINE:CAST-IRON,OIL PAN,DRY EXHAUST MANIFOLD AND VIBRATION
DAMPER
B. RATED ENGINE SPEED: 1800 RPM
C. STARTER:ONE ELECTRIC STARTER 12V DC OR 24V DC
D. FUEL SYSTEM:HIGH PRESSURE FUEL PUMP,ELECTRONICALLY CONTROLLED
INJECTION,FUEL FILTER AND WATER SEPARATOR
E. GENERATOR:ENGINE MOUNTED BELT DRIVE
F. LUBE OIL SYSTEM:FORCED FEED LUBRICATION,LUBE OIL FILTER,LUBE OIL HEAT
EXCHANGER,FILLER NECK AND DIP STICK
G. COMBUSTION AIR SYSTEM:DRY TYPE AIR FILTER
H. COOLING SYSTEM:COOLANT CIRCULATION PUMP AND PUSHER FAN
Page 13 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
I. GOVERNOR:ELECTRONIC CONTROL THROUGH ECU,WITH SPEED SENSING
J. ENGINE FUEL SYSTEM:
• MAIN FUEL PUMP:•MOUNTED ON ENGINE. PUMP ENSURES ADEQUATE PRIMARY
FUEL FLOW UNDER STARTING AND LOAD CONDITIONS.
• RELIEF-BYPASS VALVE: AUTOMATICALLY REGULATES PRESSURE IN FUEL LINE
AND RETURNS EXCESS FUEL TO SOURCE.
• LIFT PUMP:PROVIDES ADEQUATE PRESSURE TO THE MAIN FUEL PUMP MOUNTED
ON THE ENGINE.
• SINGLE CANISTER FUEL WATER SEPARATOR: SINGLE FILTER ELEMENT FUEL
WATER SEPARATOR RATED TO REMOVE A MINIMUM OF 30 MICRONS AND
SMALLER WHILE PASSING FULL FLOW.
K. COOLANT JACKET HEATER: AN ELECTRIC WATER HEATER WITH INTEGRAL
THERMOSTATIC CONTROL,PROPERLY SIZED TO MAINTAIN ENGINE JACKET WATER
AT 90 DEGREES AND SUITABLE FOR OPERATION IN AN AMBIENT TEMPERATURE OF-
20°F(-29°C). COMPLY WITH NFPA 110 REQUIREMENTS FOR LEVEL 1 EQUIPMENT FOR
HEATER CAPACITY.
L. COOLING SYSTEM: CLOSED LOOP,LIQUID COOLED,WITH RADIATOR FACTORY
MOUNTED ON ENGINE-GENERATOR SET MOUNTING FRAME AND INTEGRAL ENGINE-
DRIVEN COOLANT PUMP.
• SOLUTION OF 50 PERCENT ETHYLENE-GLYCOL-BASED ANTIFREEZE AND 50
PERCENT WATER,WITH ANTICORROSION ADDITIVES AS RECOMMENDED BY
ENGINE MANUFACTURER.
• SIZE OF RADIATOR: ADEQUATE TO CONTAIN EXPANSION OF TOTAL SYSTEM
COOLANT FROM COLD START TO 110 PERCENT OF LOAD CONDITION.
• EXPANSION TANK: CONSTRUCTED WITHSTAND MAXIMUM CLOSED-LOOP
COOLANT SYSTEM PRESSURE FOR ENGINE USED.
• TEMPERATURE CONTROL: SELF-CONTAINED,THERMOSTATIC-CONTROL VALVE
MODULATES COOLANT FLOW AUTOMATICALLY TO MAINTAIN OPTIMUM
CONSTANT COOLANT TEMPERATURE AS RECOMMENDED BY ENGINE
MANUFACTURER.
• COOLANT HOSE: FLEXIBLE ASSEMBLY WITH INSIDE SURFACE OF NONPOROUS
RUBBER.
➢ RATING:50-PSIG(345-KPA)MAXIMUM WORKING PRESSURE WITH COOLANT AT
A TEMPERATURE OF 1807(82-C),AND NON-COLLAPSIBLE UNDER VACUUM.
➢ END FITTINGS: FLANGES OR STEEL PIPE NIPPLES WITH CLAMPS TO SUIT
PIPING AND EQUIPMENT CONNECTIONS.
M. INTERNAL SILENCER:THE INTERNAL SILENCER SHALL ATTENUATE EXHAUST NOISE
TO A CRITICAL LEVEL.
• AN EXHAUST SILENCER AND FLEXIBLE STAINLESS STEEL FITTING SHALL BE
FURNISHED FACTORY INSTALLED INSIDE THE ENCLOSURE. PIPE SIZE SHALL BE
SUFFICIENTLY LARGE TO HANDLE THE ENGINE EXHAUST GAS FLOW AT FULL
RATED LOAD WITHOUT CAUSING BACK PRESSURE IN EXCESS OF THAT ALLOWED
BY THE ENGINE MANUFACTURER. EXHAUST SYSTEM SHALL INCLUDE ALL
ELBOWS AND FITTINGS TO FORM A COMPLETE EXHAUST PIPING SYSTEM. RAIN
COLLAR AND ROOF PENETRATION PROTECTION SHALL BE INCLUDED. EXHAUST
PIPE SHALL BE EQUIPPED WITH RAIN CAP TO PREVENT PRECIPITATION FROM
COLLECTING IN THE EXHAUST SYSTEM.
Page 14 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
N. AIR-INTAKE FILTER: STANDARD-DUTY,ENGINE-MOUNTED AIR CLEANER WITH
REPLACEABLE DRY-FILTER ELEMENT AND"BLOCKED FILTER"INDICATOR.
O. STARTING SYSTEM: 12 OR 24 VOLT ELECTRIC,WITH NEGATIVE GROUND.
• COMPONENTS: SIZED SO THEY WILL NOT BE DAMAGED DURING A FULL ENGINE-
CRANKING CYCLE WITH AMBIENT TEMPERATURE AT MAXIMUM SPECIFIED IN
PART 1 "PROJECT CONDITIONS"ARTICLE.
• CRANKING MOTOR: HEAVY-DUTY UNIT THAT AUTOMATICALLY ENGAGES AND
RELEASES FROM ENGINE FLYWHEEL WITHOUT BINDING.
• CRANKING CYCLE: AS REQUIRED BY NFPA 110 FOR SYSTEM LEVEL SPECIFIED.
• BATTERY: ADEQUATE CAPACITY WITHIN AMBIENT TEMPERATURE RANGE
SPECIFIED IN PART I "PROJECT CONDITIONS"ARTICLE TO PROVIDE SPECIFIED
CRANKING CYCLE AT LEAST THREE(3)WITHOUT RECHARGING.
• BATTERY CABLE: SIZED AS RECOMMENDED BY ENGINE MANUFACTURER FOR
CABLE LENGTH INDICATED. INCLUDE REQUIRED INTERCONNECTING
CONDUCTORS AND CONNECTION ACCESSORIES.
• BATTERY COMPARTMENT: BATTERY RACK FLOOR MOUNTED CONSTRUCTED OF
STEEL,GLOSS BLACK FINISH.INCLUDE ACCESSORIES REQUIRED TO SUPPORT AND
FASTEN BATTERIES IN PLACE.
• BATTERY CHARGER: 12VDC,CURRENT-LIMITING,AUTOMATIC-EQUALIZING AND
FLOAT-CHARGING TYPE. THE FOLLOWING FEATURES SHALL BE INCLUDED:
➢ OPERATION: EQUALIZING-CHARGING RATE OF 6 AMPS SHALL BE INITIATED
AUTOMATICALLY AFTER BATTERY HAS LOST CHARGE UNTIL AND
ADJUSTABLE EQUALIZING VOLTAGE IS ACHIEVED AT BATTERY TERMINALS.
UNIT SHALL THEN BE AUTOMATICALLY SWITCHED TO A LOWER FLOAT-
CHARGING MODE AND SHALL CONTINUE TO OPERATE IN THAT MODE UNTIL
BATTERY IS DISCHARGED AGAIN.
4. FUEL STORAGE
A. DAY TANK: NONE
B. BASE-MOUNTED FUEL OIL TANK: FACTORY INSTALLED AND PIPED,COMPLYING
WITH UL 142 FUEL OIL TANK. FEATURES INCLUDE THE FOLLOWING:
• TANK LEVEL INDICATOR.
• CAPACITY: FUEL FOR 48 HOURS CONTINUOUS OPERATION AT 100 PERCENT
RATED POWER OUTPUT.
• FEATURES:
➢ EMERGENCY TANK AND BASIN VENTS.
➢ MECHANICAL LEVEL GAUGE.
➢ FUEL SUPPLY AND RETURN LINES,CONNECTED TO GENERATOR SET WITH
FLEXIBLE FUEL LINES,AS RECOMMENDED BY THE ENGINE MANUFACTURER,
AND IN COMPLIANCE WITH UL 2200 AND NFPA REQUIREMENTS.
➢ LEAK DETECTION PROVISIONS,WIRED TO THE GENERATOR SET CONTROL FOR
LOCAL AND REMOTE ALARM INDICATION.
➢ HIGH AND LOW LEVEL FLOAT SWITCHES TO INDICATE FUEL LEVEL.WIRE
SWITCHES TO GENERATOR CONTROL FOR LOCAL AND REMOTE INDICATION
OF FUEL LEVEL.
➢ BASIN DRAIN.
➢ INTEGRAL LIFTING PROVISIONS.
➢ VANDAL-RESISTANT FILL CAP.
Page 15 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
• CONTAINMENT PROVISIONS: COMPLY WITH REQUIREMENTS OF SUFFOLK
COUNTY BOARD OF HEALTH APPROVED UL 142 FOR DOUBLE WALL TANK.
5. CONTROLS AND MONITORING
A. AUTOMATIC STARTING SYSTEM SEQUENCE OF OPERATION: WHEN MODE-SELECTOR
SWITCH ON THE CONTROL AND MONITORING PANEL IS IN THE AUTOMATIC POSITION,
REMOTE-CONTROL CONTACTS IN ONE OR MORE SEPARATE AUTOMATIC TRANSFER
SWITCHES INITIATE STARTING AND STOPPING OF GENERATOR SET. WHEN MODE-
SELECTOR SWITCH IS SWITCHED TO THE ON POSITION,THE GENERATOR SET STARTS.
THE OFF POSITION OF SAME SWITCH INITIATES GENERATOR-SET SHUTDOWN. WHEN
GENERATOR SET IS RUNNING,SPECIFIED SYSTEM OR EQUIPMENT FAILURES OR
DERANGEMENTS AUTOMATICALLY SHUT DOWN GENERATOR SET AND INITIATE
ALARMS. OPERATION OF A REMOTE EMERGENCY-STOP SWITCH ALSO SHUTS DOWN
GENERATOR SET.
B. MANUAL STARTING SYSTEM SEQUENCE OF OPERATION: SWITCHING ON-OFF SWITCH
ON THE GENERATOR CONTROL PANEL TO THE ON POSITION STARTS THE GENERATOR
SET. THE OFF POSITION OF SAME SWITCH INITIATES GENERATOR-SET SHUTDOWN.
WHEN GENERATOR SET IS RUNNING,SPECIFIED SYSTEM OR EQUIPMENT FAILURES OR
DERANGEMENTS AUTOMATICALLY SHUT DOWN GENERATOR SET AND INITIATE
ALARMS. OPERATION OF A REMOTE EMERGENCY-STOP SWITCH ALSO SHUTS DOWN
GENERATOR SET.
C. CONFIGURATION: OPERATING AND SAFETY INDICATIONS,PROTECTIVE DEVICES,
BASIC SYSTEM CONTROLS,ENGINE GAGES,INSTRUMENT TRANSFORMERS,
GENERATOR DISCONNECT SWITCH OR CIRCUIT BREAKER,AND OTHER INDICATED
COMPONENTS SHALL BE GROUPED IN A COMBINATION CONTROL AND POWER PANEL.
RIGIDLY MOUNTED TO THE GENERATOR SET.
D. DIGITAL GENERATOR CONTROLLER
• GENERATOR MOUNTED CONTROL PANEL: PROVIDE A GENERATOR MOUNTED
CONTROL PANEL MTU DGC 2020 LEVEL 1
• COMMUNICATION:USB,RS485 USING MODBUS(SLAVE),AND INTERNAL
INDUSTRIAL GRADE MODEM WITH DIAL OUT AND DIAL IN CAPABILITY,SAE J1939
ENGINE ECU CAPABILITY AND SEPARATE RS485 FOR PROVIDING
COMMUNICATIONS TO A REMOTE DISPLAY PANEL FOR NFPA 110 INDICATION.
• GENERATOR CONTROL PANEL PROTECTION FEATURES: KWH/KVARH METER,
ENGINE(OVER SPEED,BATTERY OVER/UNDER VOLTAGE,AUXILIARY EXCITATION
AND SPEED/FREQUENCY MISMATCH),GENERATOR(OVER/UNDER VOLTAGE,
OVER/UNDER FREQUENCY,UNBALANCED VOLTAGE,DEAD BUS DETECTION,
OVERLOAD,REVERSE/REDUCED POWER)
• AGENCY APPROVALS:
➢ CONFORMS TO UL 508,INDUSTRIAL CONTROL EQUIPMENT—UL RECOGNIZED
COMPONENT
➢ CONFORMS TO CSA STD.C22.2 NO. 14,INDUSTRIAL CONTROL EQUIPMENT—
CSA CERTIFIED
➢ COMPLIES WITH NFPA 110, STANDARD FOR EMERGENCY AND STANDBY
POWER SYSTEMS
• CE COMPLIANCE:
➢ THIS PRODUCT COMPLIES WITH THE REQUIREMENTS OF THE FOLLOWING EC
DIRECTIVES:
➢ LOW VOLTAGE DIRECTIVE(LVD)-73/23/EEC AS AMENDED BY 93/68/EEC
Page 16 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
➢ ELECTROMAGNETIC COMPATIBILITY(EMC)-89/336/EEC AS AMENDED BY
92/31/EEC AND 93/68/EEC
➢ EN 50178:1997-ELECTRONIC EQUIPMENT FOR USE,IN POWER INSTALLATIONS
➢ EN 61000-6-4:2001 -ELECTROMAGNETIC COMPATIBILITY(EMC),GENERIC
STANDARDS,EMISSION STANDARD FOR INDUSTRIAL ENVIRONMENTS
➢ EN 61000-6-2:2001 -ELECTROMAGNETIC COMPATIBILITY(EMC),GENERIC
STANDARDS,IMMUNITY FOR INDUSTRIAL ENVIRONMENTS
• ENVIRONMENTAL:
➢ TEMPERATURE:OPERATING:-40°TO 158°F(40°TO 70°C),STORAGE:40°TO
185°F
➢ (-40°TO 85°C)
➢ HUMIDITY:IEC 68-2-38
➢ SALT FOG:ASTM B 17-73,IEC 68-2-11 (TESTED WHILE OPERATIONAL)
➢ INGRESS PROTECTION:IEC IP54 FOR FRONT PANEL
➢ SHOCK: 15 G IN 3 PERPENDICULAR PLANES
➢ VIBRATION:
0 5 TO 29 TO 5 HZ: 1.5 G PEAK FOR 5 MIN.
0 29 TO 52 TO 29 HZ:0.036"DECS-A FOR 2.5 MIN
o 52 TO 500 TO 52 HZ:5 G PEAK FOR 7.5 MIN
• ENGINE CONTROL:
➢ CRANKING CONTROL:CYCLE OR CONTINUOUS(QUANTITY AND DURATION
FULLY PROGRAMMABLE)
➢ ENGINE COOL DOWN
➢ SUCCESSFUL START COUNTER:COUNTS AND RECORDS SUCCESSFUL ENGINE
STARTS
➢ TIMERS INCLUDING,BUT NOT LIMITED TO:
o ENGINE COOL DOWN TIMER
o ENGINE MAINTENANCE TIMER
o PRE-ALARM TIME DELAYS FOR WEAK/LOW BATTERY VOLTAGE
o ALARM TIME DELAY FOR OVER SPEED
o ALARM TIME DELAY FOR SENDER FAILURE.
o ARMING TIME DELAYS AFTER CRANK DISCONNECT:
■ LOW OIL PRESSURE
■ HIGH COOLANT TEMPERATURE
• ALARMS:
➢ LOW OIL PRESSURE
➢ HIGH COOLANT TEMPERATURE
➢ LOW COOLANT LEVEL
➢ LOW FUEL LEVEL
➢ OVER SPEED
➢ OVER CRANK
➢ ENGINE SENDER UNIT FAILURE
➢ FUEL LEAK/FUEL SENDER FAILURE
➢ EMERGENCY STOP
➢ BATTERY CHARGER FAILURE
➢ CRITICAL LOW FUEL SHUTDOWN
• PRE-ALARMS:
➢ LOW OIL PRESSURE
➢ HIGH COOLANT TEMPERATURE
➢ LOW COOLANT TEMPERATURE
➢ BATTERY OVERVOLTAGE
➢ WEAK BATTERY
Page 17 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
➢ BATTERY CHARGER FAILURE
➢ ENGINE SENDER UNIT FAILURE
➢ ENGINE KW OVERLOAD(3 LEVELS)
➢ MAINTENANCE INTERVAL TIMER
➢ LOW COOLANT LEVEL
➢ LOW FUEL LEVEL
➢ FUEL LEAK DETECT
➢ HIGH FUEL LEVEL
• GENERATOR PROTECTION ANSI FUNCTIONS:
➢ UNDER VOLTAGE(27)
➢ OVERVOLTAGE(59)
➢ ANSI CODES REVERSE POWER(32)
➢ OVER FREQUENCY(8 10)
➢ LOSS OF EXCITATION(40Q)
➢ UNDER FREQUENCY(81U)
E. INDICATING AND PROTECTIVE DEVICES AND CONTROLS: AS REQUIRED BY NFPA 110
FOR LEVEL 1 SYSTEM,AND THE FOLLOWING ACCESSORIES:
F. SUPPORTING ITEMS: INCLUDE SENSORS,TRANSDUCERS,TERMINALS,RELAYS,AND
OTHER DEVICES AND INCLUDE WIRING REQUIRED TO SUPPORT SPECIFIED ITEMS.
LOCATE SENSORS AND OTHER SUPPORTING ITEMS ON ENGINE OR GENERATOR,
UNLESS OTHERWISE INDICATED.
G. CONNECTION TO DATA LINK: A SEPARATE TERMINAL BLOCK,FACTOR WIRED TO
FORM C DRY CONTACTS,FOR EACH ALARM AND STATUS INDICATION IS RESERVED
FOR CONNECTIONS FOR DATA-LINK TRANSMISSION OF INDICATIONS TO REMOTE
DATA TERMINALS. DATA SYSTEM CONNECTIONS TO TERMINALS ARE COVERED IN
SECTION 260913"ELECTRICAL POWER MONITORING AND CONTROL."
H. COMMON REMOTE AUDIBLE ALARM: COMPLY WITH NFPA 110 REQUIREMENTS FOR
LEVEL 1 SYSTEMS. INCLUDE NECESSARY CONTACTS AND TERMINALS IN CONTROL
AND MONITORING PANEL.
• OVERCRANK SHUTDOWN.
• COOLANT LOW-TEMPERATURE ALARM.
• CONTROL SWITCH NOT IN AUTO POSITION.
• BATTERY-CHARGER MALFUNCTION ALARM.
• BATTERY LOW-VOLTAGE ALARM.
I. COMMON REMOTE AUDIBLE ALARM: SIGNAL THE OCCURRENCE OF ANY EVENT
LISTED BELOW WITHOUT DIFFERENTIATING BETWEEN EVENT TYPES. CONNECT SO
THAT AFTER AN ALARM IS SILENCED,CLEARING OF INITIATING CONDITION WILL
REACTIVATE ALARM UNTIL SILENCING SWITCH IS RESET.
• ENGINE HIGH-TEMPERATURE SHUTDOWN.
• LUBE-OIL,LOW-PRESSURE SHUTDOWN.
• OVERSPEED SHUTDOWN.
• REMOTE EMERGENCY-STOP SHUTDOWN.
• ENGINE HIGH-TEMPERATURE PRE-ALARM.
• LUBE-OIL,LOW-PRESSURE PRE-ALARM.
• FUEL TANK,LOW-FUEL LEVEL.
• LOW COOLANT LEVEL.
J. REMOTE ALARM ANNUNCIATOR: 16 LLIGHT REMOTE ANNUNCIATOR
Page 18 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
K. REMOTE EMERGENCY-STOP SWITCH:
6. GENERATOR OVERCURRENT AND FAULT PROTECTION
A. GENERATOR CIRCUIT BREAKER: ADJUSTABLE THERMAL-MAGNETIC TRIP TYPE;80
PERCENT RATED;COMPLYING WITH NEMA AB 1 AND UL 489
• MANUFACTURERS:
➢ GENERAL ELECTRIC
➢ CUTLER HAMMER
➢ SQUARE D
B. PRODUCT DESCRIPTION:ENCLOSED,MOLDED-CASE CIRCUIT BREAKER CONFORMING
TO NEMA AB 1 AND FS-W-C
C. ACCESSORIES:CONFORM TO NEMA AB 1
• SHUNT TRIP DEVICE:24 VOLTS,DC.
• UNDERVOLTAGE TRIP DEVICE.
• AUXILIARY SWITCH: 120 VOLTS,AC.
• ALARM SWITCH: 120 VOLTS,AC.
• HANDLE LOCK:PROVISIONS FOR PADLOCKING.
• ENCLOSURE:NEMA ICS 6,TYPE[ 1 ,4,3R STAINLESS STEEL OR BETTER],
MOUNTED ON THE ENGINE-GENERATOR SET.
D. SERIES RATING:SERIES RATED BREAKERS SHALL NOT BE USED
E. GENERATOR PROTECTION: MICROPROCESSOR-BASED DEVICE SHALL CONTINUOUSLY
MONITOR THE TOTAL KVA LEVEL OF THE GENERATOR OUTPUT,ANNUNCIATING
CONDITIONS THAT MAY RESULT IN GENERATOR DAMAGE.
• PROTECTIVE DEVICES SHALL PERFORM THE FOLLOWING FUNCTIONS:
➢ INITIATES A GENERATOR OVERLOAD PRE-ALARM WHEN GENERATOR HAS
OPERATED AT AN OVERLOAD EQUIVALENT TO 105 PERCENT OF FULL-RATED
LOAD FOR 5 SECONDS. INDICATION FOR THIS ALARM IS INTEGRATED WITH
OTHER GENERATOR SET MALFUNCTION PRE-ALARMS.
➢ INDICATES A GENERATOR OVERLOAD ALARM WHEN GENERATOR HAS
OPERATED AT AN OVERLOAD EQUIVALENT TO 105 PERCENT OF FULL-RATED
LOAD FOR 300 SECONDS. INDICATION FOR THIS ALARM IS INTEGRATED WITH
OTHER GENERATOR SET MALFUNCTION ALARMS.
F. GROUND-FAULT INDICATION: NONE
7. GENERATOR,EXCITER,AND VOLTAGE REGULATOR
A. COMPLY WITH NEMA MG 1.
B. DRIVE: GENERATOR SHAFT SHALL BE DIRECTLY CONNECTED TO THE ENGINE SHAFT.
EXCITER SHALL BE ROTATED INTEGRALLY WITH GENERATOR ROTOR.
C. ELECTRICAL INSULATION: CLASS H OR CLASS F
D. STATOR-WINDING LEADS: BROUGHT OUT TO TERMINAL BOX TO PERMIT FUTURE
RECONNECTION FOR OTHER VOLTAGES IF REQUIRED
Page 19 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
E. CONSTRUCTION SHALL PREVENT MECHANICAL,ELECTRICAL,AND THERMAL
DAMAGE DUE TO VIBRATION,OVERSPEED UP TO 125 PERCENT OF RATING,AND HEAT
DURING OPERATION AT 110 PERCENT OF RATED CAPACITY.
F. ENCLOSURE: DRIP PROOF
G. INSTRUMENT TRANSFORMERS: MOUNTED WITHIN GENERATOR ENCLOSURE
H. VOLTAGE REGULATOR: ANALOG VOLTAGE CONTROLLER REGULATES VOLTAGE ON
50 OR 60 HERTZ BRUSHLESS GENERATORS.THE CONTROLLERS INCLUDE FREQUENCY
COMPENSATION,OVER-EXCITATION SHUTDOWN,SOLID-STATE BUILDUP CIRCUITRY,
AND EMI FILTERING. ADJUSTMENT POTENTIOMETERS ARE LOCATED ON THE
TERMINALS AND COMPONENTS SIDE OF THE CONTROLLER.IF REMOTE ADJUSTMENT
OF THE GENERATOR OUTPUT IS DESIRED,THE VOLTAGE ADJUST RHEOSTAT JUMPER
MUST BE REPLACED WITH A USER-SUPPLIED RHEOSTAT.A 1000 OHM,Y"-WATT
RHEOSTAT WILL PROVIDE ADEQUATE VOLTAGE ADJUSTMENT RANGE FOR MOST
APPLICATIONS.
8. OUTDOOR GENERATOR-SET ENCLOSURE
A. DESCRIPTION: ENCLOSURE IS DESIGNED TO BE WIND RESISTANT UP TO 150 MPH.
ASCE 7-05 EXPOSURE C,3-SECOND WIND GUSTS.
B. DESCRIPTION: ALUMINUM ENCLOSURE WITH THE FOLLOWING FEATURES:
• CONSTRUCTION: FORMED AND/OR WELDED ALUMINUM.
• HINGED DOORS FOR ACCESS WITH LOCKABLE LATCHES
• LOUVERED AND/OR BAFFLED AIR INLET. GRATED AIR OUTLET
• INTERIOR LINED WITH ACOUSTICAL FOAM FOR SOUND ATTENUATION
• EXHAUST SCOOPS AND IN SOME CASES INTAKE SCOOPS ARE INSTALLED FOR
ADDITIONAL SOUND ATTENUATION
• CHOICE OF STANDARD COLORS. CUSTOM COLORS AVAILABLE UPON REQUEST
• ADDITIONAL ENCLOSURE FEATURES:
➢ EXHAUST SCOOP
o ALUMINUM HOUSING EXTENSION INTENDED TO REDIRECT EXHAUST
AIR VERTICAL INSTEAD OF HORIZONTAL TO INCREASE SOUND
ATTENUATION.
➢ SOUND ATTENUATION 70 DBA @ 23 FEET
o APPLICATION OF FOAM MATERIAL TO REDUCE NOISE EMISSIONS.
9. VIBRATION ISOLATION DEVICES
A. NEOPRENE PAD
• %INCH THICK ELASTOMERIC PAD IN SQUARE SHAPE TO BE PLACED UNDER THE
BASE FRAME AT EACH OF THE PRE-DRILLED ISOLATOR MOUNTING HOLES.
• HELPS TO PREVENT SLIDING OF THE UNIT AS WELL AS REDUCING THE
TRANSMISSION OF SOUND AND VIBRATION INTO THE FLOOR.
I0.FINISHES
A. INDOOR AND OUTDOOR ENCLOSURES AND COMPONENTS: MANUFACTURER'S
STANDARD FINISH OVER CORROSION-RESISTANT PRETREATMENT AND COMPATIBLE
PRIMER.
Page 20 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
I LSOURCE QUALITY CONTROL
A. PROTOTYPE TESTING: FACTORY TEST ENGINE-GENERATOR SET USING SAME ENGINE
MODEL,CONSTRUCTED OF IDENTICAL OR EQUIVALENT COMPONENTS AND EQUIPPED
WITH IDENTICAL OR EQUIVALENT ACCESSORIES.
• TESTS: COMPLY WITH NFPA 110,LEVEL 1 ENERGY CONVERTERS AND WITH IEEE
115.
B. PROJECT-SPECIFIC EQUIPMENT TESTS: BEFORE SHIPMENT,FACTORY TEST ENGINE-
GENERATOR SET AND OTHER SYSTEM COMPONENTS AND ACCESSORIES
MANUFACTURED SPECIFICALLY FOR THIS PROJECT. PERFORM TESTS AT RATED
LOAD AND POWER FACTOR. INCLUDE THE FOLLOWING TESTS:
• TEST COMPONENTS AND ACCESSORIES FURNISHED WITH INSTALLED UNIT THAT
ARE NOT IDENTICAL TO THOSE ON TESTED PROTOTYPE TO DEMONSTRATE
COMPATIBILITY AND RELIABILITY.
• FULL LOAD RUN
• MAXIMUM POWER
• VOLTAGE REGULATION
• TRANSIENT AND STEADY STATE GOVERNING
• SINGLE-STEP LOAD PICKUP
• SAFETY SHUTDOWN
• PROVIDE 14 DAYS'ADVANCE NOTICE OF TESTS AND OPPORTUNITY FOR
OBSERVATION OF TESTS BY OWNER'S REPRESENTATIVE.
• REPORT FACTORY TEST RESULTS WITHIN 10 DAYS OF COMPLETION OF TEST.
EXECUTION
1. EXAMINATION
A. EXAMINE AREAS,EQUIPMENT BASES,AND CONDITIONS,WITH INSTALLER PRESENT,
FOR COMPLIANCE WITH REQUIREMENTS FOR INSTALLATION AND OTHER
CONDITIONS AFFECTING PACKAGED ENGINE-GENERATOR SET PERFORMANCE.
B. EXAMINE ROUGHING-IN OF PIPING SYSTEMS AND ELECTRICAL CONNECTIONS.
VERIFY ACTUAL LOCATIONS OF CONNECTIONS BEFORE PACKAGED ENGINE-
GENERATOR INSTALLATION.
C. PROCEED WITH INSTALLATION ONLY AFTER UNSATISFACTORY CONDITIONS HAVE
BEEN CORRECTED.
2. INSTALLATION
A. COMPLY WITH PACKAGED ENGINE-GENERATOR MANUFACTURERS' WRITTEN
INSTALLATION AND ALIGNMENT INSTRUCTIONS AND WITH NFPA 110.
B. INSTALL PACKAGED ENGINE GENERATOR TO PROVIDE ACCESS,WITHOUT REMOVING
CONNECTIONS OR ACCESSORIES,FOR PERIODIC MAINTENANCE.
C. ELECTRICAL WIRING: INSTALL ELECTRICAL DEVICES FURNISHED BY EQUIPMENT
MANUFACTURERS BUT NOT SPECIFIED TO BE FACTORY MOUNTED.
Page 21 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
3. CONNECTIONS
A. COORDINATE PIPING INSTALLATIONS AND SPECIALTY ARRANGEMENTS WITH
SCHEMATICS ON DRAWINGS AND WITH REQUIREMENTS SPECIFIED IN PIPING
SYSTEMS. IF DRAWINGS ARE EXPLICIT ENOUGH,THESE REQUIREMENTS MAY BE
REDUCED OR OMITTED.
B. PIPING INSTALLATION REQUIREMENTS ARE SPECIFIED IN DIVISION 23 SECTIONS.
DRAWINGS INDICATE GENERAL ARRANGEMENT OF PIPING AND SPECIALTIES.
C. CONNECT FUEL;COOLING-SYSTEM,AND EXHAUST-SYSTEM PIPING ADJACENT TO
PACKAGED ENGINE GENERATOR TO ALLOW SERVICE AND MAINTENANCE.
D. CONNECT FUEL PIPING TO ENGINES WITH A GATE VALVE AND UNION AND FLEXIBLE
CONNECTOR.
• DIESEL STORAGE TANKS,TANK ACCESSORIES,PIPING,VALVES,AND SPECIALTIES
FOR FUEL SYSTEMS ARE SPECIFIED IN DIVISION 23 SECTION"FACILITY FUEL-OIL
PIPING."
• NATURAL-GAS PIPING,VALVES,AND SPECIALTIES FOR GAS DISTRIBUTION ARE
SPECIFIED IN DIVISION 23 SECTION"FACILITY NATURAL-GAS PIPING."
• LP-GAS PIPING,VALVES,AND SPECIALTIES FOR GAS PIPING ARE SPECIFIED IN
DIVISION 23 SECTION"FACILITY LIQUEFIED-PETROLEUM GAS PIPING."
E. GROUND EQUIPMENT ACCORDING TO DIVISION 26 SECTION"GROUNDING AND
BONDING FOR ELECTRICAL SYSTEMS."
F. CONNECT WIRING ACCORDING TO DIVISION 26 SECTION"LOW-VOLTAGE ELECTRICAL
POWER CONDUCTORS AND CABLES."
4. IDENTIFICATION
A. IDENTIFY SYSTEM COMPONENTS ACCORDING TO DIVISION 23 SECTION
"IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT"AND DIVISION 26 SECTION
"IDENTIFICATION FOR ELECTRICAL SYSTEMS."
5. FIELD QUALITY CONTROL
A. MANUFACTURER'S FIELD SERVICE: ENGAGE A FACTORY-AUTHORIZED SERVICE
REPRESENTATIVE TO INSPECT,TEST,AND ADJUST COMPONENTS,ASSEMBLIES,AND
EQUIPMENT INSTALLATIONS,INCLUDING CONNECTIONS. REPORT RESULTS IN
WRITING.
B. PERFORM TESTS AND INSPECTIONS AND PREPARE TEST REPORTS.
• MANUFACTURER'S FIELD SERVICE: ENGAGE A FACTORY-AUTHORIZED SERVICE
REPRESENTATIVE TO INSPECT COMPONENTS,ASSEMBLIES,AND EQUIPMENT
INSTALLATIONS,INCLUDING CONNECTIONS,AND TO ASSIST IN TESTING.
C. TESTS AND INSPECTIONS:
• COORDINATE TESTS FOR TRANSFER SWITCHES AND RUN THEM CONCURRENTLY
• LEAK TEST: AFTER INSTALLATION,CHARGE SYSTEM AND TEST FOR LEAKS.
REPAIR LEAKS AND RETEST UNTIL NO LEAKS EXIST
Page 22 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
• OPERATIONAL TEST: AFTER ELECTRICAL CIRCUITRY HAS BEEN ENERGIZED,
START UNITS TO CONFIRM PROPER MOTOR ROTATION AND UNIT OPERATION.
• TEST AND ADJUST CONTROLS AND SAFETIES. REPLACE DAMAGED AND
MALFUNCTIONING CONTROLS AND EQUIPMENT.
• REMOVE AND REPLACE MALFUNCTIONING UNITS AND RETEST AS SPECIFIED
ABOVE.
• RETEST: CORRECT DEFICIENCIES IDENTIFIED BY TESTS AND OBSERVATIONS AND
RETEST UNTIL SPECIFIED REQUIREMENTS ARE MET.
6. DEMONSTRATION
A. ENGAGE A FACTORY-AUTHORIZED SERVICE REPRESENTATIVE TO TRAIN OWNER'S
MAINTENANCE PERSONNEL TO ADJUST,OPERATE,AND MAINTAIN PACKAGED
ENGINE GENERATORS
Page 23 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
NATURAL GAS/PROPANE ENGINE GENERATORS
GENERAL
1. RELATED DOCUMENTS
A. DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT,INCLUDING GENERAL
AND SUPPLEMENTARY CONDITIONS AND DIVISION 01 SPECIFICATION SECTIONS,
APPLY TO THIS SECTION.
2. SUMMARY
A. THIS SECTION INCLUDES PACKAGED ENGINE-GENERATOR SETS FOR STANDBY
POWER SUPPLY WITH THE FOLLOWING FEATURES:
• NATURAL GAS ENGINE
• UNIT MOUNTED COOLING SYSTEM
• DGC 2020-EXPANDED
• ULTRAQUIET-ALUMINUM ENCLOSURE
• PERFORMANCE REQUIREMENTS FOR SENSITIVE LOADS
• LOAD BANK(S)
B. RELATED SECTIONS INCLUDE THE FOLLOWING:
• SECTION 017900"DEMONSTRATION AND TRAINING"FOR SPECIFICATIONS
COVERING DEMONSTRATIONS AND TRAINING OF THE EQUIPMENT.
• SECTION 260553 "IDENTIFICATION FOR ELECTRICAL SYSTEMS"FOR
SPECIFICATIONS COVERING ELECTRICAL SYSTEMS.
• SECTION 231113"FACILITY FUEL-OIL PIPING"FOR SPECIFICATIONS COVERING
DIESEL STORAGE TANKS,TANK ACCESSORIES,PIPING,VALVES,AND SPECIALTIES
FOR FUEL SYSTEMS.
• SECTION 260526"GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS"FOR
SPECIFICATIONS COVERING GROUNDING OF COMPONENTS.
• SECTION 230553 "IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT"FOR
SPECIFICATIONS COVERING HVAC PIPING.
• SECTION 017823 "OPERATION AND MAINTENANCE DATA"FOR MAINTENANCE AND
OPERATIONAL SPECIFICATIONS.
• SECTION 260913"ELECTRICAL POWER MONITORING AND CONTROL"FOR
SPECIFICATIONS COVERING DATA SYSTEM CONNECTIONS.
• SECTION 262413 "SWITCHBOARDS"FOR SWITCHBOARD SPECIFICATIONS.
• SECTION 262300"LOW-VOLTAGE SWITCHGEAR"FOR SWITCHGEAR
SPECIFICATIONS.
• SECTION 260548"VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS"
FOR COMPLETE ENGINE-GENERATOR SET,BATTERIES,BATTERY RACKS,
ACCESSORIES,AND COMPONENTS SPECIFICATIONS.
Page 24 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
• SECTION 260519"LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES"
FOR SPECIFICATIONS COVERING WIRING.
3. DEFINITIONS
A. OPERATIONAL BANDWIDTH: THE TOTAL VARIATION FROM THE LOWEST TO HIGHEST
VALUE OF A PARAMETER OVER A RANGE OF CONDITIONS INDICATED,EXPRESSED AS
A PERCENTAGE OF THE NOMINAL VALUE OF THE PARAMETER.
B. LP: LIQUID PETROLEUM
C. NG: NATURAL GAS
D. STANDBY RATING: POWER OUTPUT RATING EQUAL TO THE POWER THE GENERATOR
SET DELIVERS CONTINUOUSLY UNDER NORMALLY VARYING LOAD FACTORS FOR
THE DURATION OF THE POWER OUTAGE.
4. ACTION SUBMITTALS
A. PRODUCT DATA:FOR EACH TYPE OF PACKAGED ENGINE GENERATOR INDICATED.
INCLUDE RATED CAPACITIES,,OPERATING CHARACTERISTICS,AND FURNISHED
SPECIALTIES AND ACCESSORIES. IN ADDITION,INCLUDE THE FOLLOWING:
• THERMAL DAMAGE CURVE FOR GENERATOR
• TIME-CURRENT CHARACTERISTIC OF CURVES FOR GENERATOR PROTECTIVE
DEVICE
B. SHOP DRAWINGS:DETAILED EQUIPMENT ASSEMBLIES AND INDICATE DIMENSIONS,
WEIGHTS,LOADS,REQUIRED CLEARANCES,METHOD OF FIELD ASSEMBLY,
COMPONENTS,AND LOCATION AND SIZE OF EACH FIELD CONNECTION.
• DIMENSIONED OUTLINE PLAN AND ELEVATION DRAWING OF ENGINE-
GENERATOR SET AND OTHER COMPONENTS SPECIFIED.
• DESIGN CALCULATIONS:SIGNED AND SEALED BY A QUALIFIED ENGINEER.
CALCULATE REQUIREMENTS FOR SELECTING VIBRATION ISOLATORS AND
SEISMIC RESTRAINTS AND FOR DESIGNING VIBRATION ISOLATION BASES.
• VIBRATION ISOLATION BASE DETAILS:SIGNED AND SEALED BY A QUALIFIED
ENGINEER. DETAIL FABRICATION,INCLUDING ANCHORAGES AND ATTACHMENTS
TO STRUCTURE AND TO SUPPORTED EQUIPMENT. INCLUDE BASE WEIGHTS.
• WIRING DIAGRAMS:POWER,SIGNAL,AND CONTROL WIRING.
5. INFORMATIONAL SUBMITTALS
A. MANUFACTURER SEISMIC QUALIFICATION CERTIFICATION:SUBMIT CERTIFICATION
THAT COMPLETE ENGINE-GENERATOR SET,BATTERIES,BATTERY RACKS,
ACCESSORIES,AND COMPONENTS WILL WITHSTAND SEISMIC FORCES DEFINED IN
SECTION 260548"VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS."
INCLUDE THE FOLLOWING:
• BASIS FOR CERTIFICATION: INDICATE WHETHER WITHSTAND CERTIFICATION IS
BASED ON ACTUAL TEST OF THE ASSEMBLED COMPONENTS OR ON
CALCULATION.
Page 25 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
➢ THE TERM"WITHSTAND"MEANS"THE UNIT WILL REMAIN IN PLACE WITHOUT
SEPARATION OF ANY PARTS FROM THE DEVICE WHEN SUBJECTED TO THE
SEISMIC FORCES SPECIFIED"
➢ THE TERM"WITHSTAND"MEANS"THE UNIT WILL REMAIN IN PLACE WITHOUT
SEPARATION OF ANY PARTS FROM THE DEVICE WHEN SUBJECTED TO THE
SEISMIC FORCES SPECIFIED AND THE UNIT WILL BE FULLY OPERATIONAL
AFTER THE SEISMIC EVENT."
• DIMENSIONED OUTLINE DRAWINGS OF EQUIPMENT UNIT:IDENTIFY CENTER OF
GRAVITY AND LOCATE AND DESCRIBE MOUNTING AND ANCHORAGE
PROVISIONS.
• DETAILED DESCRIPTION OF EQUIPMENT ANCHORAGE DEVICES ON WHICH THE
CERTIFICATION IS BASED AND THEIR INSTALLATION REQUIREMENTS.
B. QUALIFICATION DATA
• THIS GENERATOR SHALL BE MTU ONSITE ENERGY OR EQUAL AND WHO HAS BEEN
REGULARLY ENGAGED IN THE PRODUCTION OF ENGINE-GENERATOR SETS AND
ASSOCIATED CONTROLS FOR A MINIMUM OF TWENTY YEARS,THEREBY
IDENTIFYING ONE SOURCE OF SUPPLY AND RESPONSIBILITY. EQUAL MEANS
HAVING THE SAME SYSTEM CONFIGURATION,OPERATION,FOOTPRINT OF THE
ENGINE-GENERATOR SET WITH THE SAME SIZING SOLUTION. ALTERNATE
OFFERINGS MUST BE SUBMITTED FOR APPROVAL 14 DAYS PRIOR TO BID.
• THE MANUFACTURER SHALL PROVIDE FACTORY-TRAINED SERVICE AND PARTS
SUPPORT THROUGH A FACTORY AUTHORIZED DEALER/SUPPLIER THAT IS
REGULARLY DOING BUSINESS IN THE AREA OF INSTALLATION.
• THE MANUFACTURER SHALL HAVE PRINTED LITERATURE AND BROCHURES
DESCRIBING THE STANDARD SYSTEM SPECIFIED,NOT A ONE OF A KIND
FABRICATION.
• AS PART OF QUALIFICATION PROCESS;AN AUTHORIZED DEALER/SUPPLIER,
HEREIN KNOWN AS THE DEALER SHALL REPRESENT THE MANUFACTURER. TO
QUALIFY AS THE DEALER/SUPPLIER,IT MUST BE A"FULL PRODUCT LINE SALES
AND SERVICE DEALER OF MTU ONSITE ENERGY"AND SHALL HAVE 24-HOUR
SERVICE AVAILABILITY. THE DEALER/SUPPLIER MUST HAVE CERTIFIED
GENERATOR SERVICE TECHNICIANS,INVENTORY OF PARTS TO SUPPORT AFTER
SALES SERVICE AND CAN PROVE 5 YEARS OF EXPERIENCE IN THE ENGINE-
GENERATOR FIELD.
C. SOURCE QUALITY-CONTROL TEST REPORTS
• CERTIFIED SUMMARY OF PROTOTYPE-UNIT TEST REPORT.
• CERTIFIED TEST REPORTS: FOR COMPONENTS AND ACCESSORIES THAT ARE
EQUIVALENT,BUT NOT IDENTICAL,TO THOSE TESTED ON PROTOTYPE UNIT.
• CERTIFIED SUMMARY OF PERFORMANCE TESTS: CERTIFY COMPLIANCE WITH
SPECIFIED REQUIREMENT TO MEET PERFORMANCE CRITERIA FOR SENSITIVE
LOADS.
• REPORT OF FACTORY TEST ON UNITS TO BE SHIPPED FOR THIS PROJECT,SHOWING
EVIDENCE OF COMPLIANCE WITH SPECIFIED REQUIREMENTS.
• REPORT OF SOUND GENERATION.
• REPORT OF EXHAUST EMISSIONS SHOWING COMPLIANCE WITH APPLICABLE
REGULATIONS.
• CERTIFIED TORSIONAL VIBRATION COMPATIBILITY: COMPLY WITH NFPA 110.
• OPERATION AND MAINTENANCE DATA: FOR PACKAGED ENGINE-GENERATOR
SETS TO INCLUDE EMERGENCY,OPERATION,AND MAINTENANCE MANUALS. IN
ADDITION TO ITEMS SPECIFIED IN DIVISION 1 SECTION"CLOSEOUT PROCEDURES"
INCLUDE THE FOLLOWING:
Page 26 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
➢ LIST OF TOOLS AND REPLACEMENT ITEMS RECOMMENDED TO BE STORED AT
THE PROJECT FOR READY ACCESS. INCLUDING PART AND DRAWING
NUMBERS,AND SOURCE OF SUPPLY.
D. FIELD QUALITY-CONTROL TEST REPORTS
E. WARRANTY: SPECIAL WARRANTY SPECIFIED IN THIS SECTION
6. CLOSEOUT SUBMITTALS
A. OPERATION AND MAINTENANCE DATA: FOR PACKAGED ENGINE-GENERATOR SETS
TO INCLUDE EMERGENCY,OPERATION,AND MAINTENANCE MANUALS. IN ADDITION
TO ITEMS SPECIFIED IN DIVISION I SECTION"CLOSEOUT PROCEDURES"INCLUDE THE
FOLLOWING:
• LIST OF TOOLS AND REPLACEMENT ITEMS RECOMMENDED TO BE STORED AT THE
PROJECT FOR READY ACCESS. INCLUDING PART AND DRAWING NUMBERS,AND
SOURCE OF SUPPLY.
7. MAINTENANCE MATERIAL SUBMITTALS
A. FURNISH EXTRA MATERIALS DESCRIBED BELOW THAT MATCH PRODUCTS
INSTALLED AND THAT ARE PACKAGED WITH PROTECTIVE COVERING FOR STORAGE
AND IDENTIFIED WITH LABELS DESCRIBING CONTENTS.
• FUSES: ONE FOR EVERY TEN OF EACH TYPE AND RATING,BUT NO LESS THAN ONE
OF EACH
• INDICATOR LAMPS: TWO FOR EVERY SIX OF TEACH TYPE USED,BUT NO FEWER
THAN TWO OF EACH
• FILTERS: ONE SET EACH OF LUBRICATING OIL,FUEL,AND COMBUSTION-AIR
FILTERS
• BELTS: ONE SET OF EACH GENERATOR AND FAN BELT
8. QUALITY ASSURANCE
A. INSTALLER QUALIFICATIONS: MANUFACTURER'S AUTHORIZED REPRESENTATIVE
WHO IS TRAINED AND APPROVED FOR INSTALLATION OF UNITS REQUIRED FOR THIS
PROJECT.
• MAINTENANCE PROXIMITY: NOT MORE THAN 2(TWO)HOURS NORMAL TRAVEL
TIME FROM INSTALLER'S'PLACE OF BUSINESS TO PROJECT SITE.
• ENGINEERING RESPONSIBILITY: PREPARATION OF DATA FOR VIBRATION
ISOLATORS AND SEISMIC RESTRAINTS OF ENGINE SKID MOUNTS,INCLUDING
SHOP DRAWINGS,BASED ON THE TESTING AND ENGINEERING ANALYSIS OF
MANUFACTURER'S STANDARD UNITS IN ASSEMBLIES SIMILAR TO THOSE
INDICATED FOR THIS PROJECT.
B. MANUFACTURER QUALIFICATIONS: A QUALIFIED MANUFACTURER. MAINTAIN
WITHIN 75 MILES OF PROJECT SITE,A SERVICE CENTER CAPABLE OF PROVIDING
TRAINING,PARTS,AND EMERGENCY MAINTENANCE REPAIRS.
C. TESTING AGENCY QUALIFICATIONS: AN INDEPENDENT AGENCY,WITH THE
EXPERIENCE AND CAPABILITY TO CONDUCT THE TESTING INDICATED,THAT IS A
MEMBER COMPANY OF THE INTERNATIONAL ELECTRICAL TESTING ASSOCIATION OR
Page 27 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
IS A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTL),AND THAT IS
ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION.
• TESTING AGENCY'S FIELD SUPERVISOR: PERSON CURRENTLY CERTIFIED BY THE
INTERNATIONAL ELECTRICAL TESTING ASSOCIATION(META)OR THE NATIONAL
INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES TO SUPERVISE
ON-SITE TESTING SPECIFIED IN PART 3.
D. SOURCE LIMITATIONS: OBTAIN PACKAGED ENGINE-GENERATOR SETS AND
AUXILIARY COMPONENTS THROUGH ONE SOURCE FROM A SINGLE MANUFACTURER.
E. PRODUCT OPTIONS: DRAWINGS INDICATE SIZE,PROFILES,AND DIMENSIONAL
REQUIREMENTS OF PACKAGED GENERATOR SETS AND ARE BASED ON THE SPECIFIC
SYSTEM INDICATED. REFER TO DIVISION I SECTION"PRODUCT REQUIREMENTS."
F. ELECTRICAL COMPONENTS,DEVICES,AND ACCESSORIES: LISTED AND LABELED AS
DEFINED IN NFPA 70,ARTICLE 100,BY A TESTING AGENCY ACCEPTABLE TO
AUTHORITIES HAVING JURISDICTION,AND MARKED FOR INTENDED USE.
G. COMPLY WITH ASME B15.1
H. COMPLY WITH NFPA 37
I. COMPLY WITH NFPA 30
J. COMPLY WITH NFPA 70
K. COMPLY WITH NFPA 99
L. COMPLY WITH NFPA 110 REQUIREMENTS FOR LEVEL 1 EMERGENCY POWER SUPPLY
SYSTEM
M. ENGINE EXHAUST EMISSIONS: COMPLY WITH APPLICABLE STATE AND LOCAL
GOVERNMENT REQUIREMENTS.
N. NOISE EMISSION: COMPLY WITH APPLICABLE STATE AND LOCAL GOVERNMENT
REQUIREMENTS FOR MAXIMUM NOISE LEVEL AT ADJACENT PROPERTY BOUNDARIES
DUE TO SOUND EMITTED BY GENERATOR SET INCLUDING ENGINE, ENGINE EXHAUST,
ENGINE COOLING-AIR INTAKE AND DISCHARGE,AND OTHER COMPONENTS OF
INSTALLATION.
9. PROJECT CONDITIONS
A. ENVIRONMENTAL CONDITIONS: ENGINE-GENERATOR SYSTEM SHALL WITHSTAND
THE FOLLOWING ENVIRONMENTAL CONDITIONS WITHOUT MECHANICAL OR
ELECTRICAL DAMAGE OR DEGRADATION OF PERFORMANCE CAPABILITY:
• MINIMUM TEMPERATURE:0°F/-18°C
• MAXIMUM TEMPERATURE: 1007/38'C
• RELATIVE HUMIDITY: 0-95 PERCENT
• ALTITUDE: 1000 FEET/305 METERS
10. WARRANTY
A. SPECIAL WARRANTY: MANUFACTURER'S STANDARD FORM IN WHICH
MANUFACTURER AGREES TO REPAIR OR REPLACE COMPONENTS OF PACKAGED
Page 28 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
ENGINE-GENERATOR SETS AND ASSOCIATED AUXILIARY COMPONENTS THAT FAIL IN
MATERIALS OR WORKMANSHIP WITHIN SPECIFIED WARRANTY PERIOD.
• WARRANTY PERIOD-5 YEAR COMPREHENSIVE WARRANTY SUPPORTED BY
FACTORY FROM DATE OF SUBSTANTIAL COMPLETION.LOCAL DEALER
WARRANTY WILL NOT BE ACCEPTABLE.SUPPLYING DEALER/DISTRIBUTOR MUST
MAINTAIN A FACILITY WITHIN 75 MILES OF PROJECT WITH MINIMUM OF 6
FACTORY TRAINED TECHNICIANS EACH WITH A STOCKED SERVICE VEHICLE.
THEY SHALL HAVE AN INVENTORY OF FACTORY REPLACEMENT PARTS ALONG
WITH SPECIAL TOOLS AND TESTING EQUIPMENT.(OWNER)HAS RIGHT TO INSPECT
FACILITY FOR COMPLIANCE.
• PROVIDING DEALER/DISTRIBUTOR MUST BE ABLE TO WARRANTY COMPLETE
GENERATOR PACKAGE.
• MUST BE AUTHORIZED DIESEL ENGINE SERVICE FACILITY FOR PRODUCT BEING
SUPPLIED.
• PROVIDE 24 HOUR EMERGENCY SERVICE, 365 DAYS A YEAR, WITH 2 HOUR
RESPONSE TIME FOR EMERGENCY SERVICE AND 24 HOUR FOR NON-EMERGENCY
SERVICE.
PRODUCTS
1. MANUFACTURERS
A. BASIS-OF-DESIGN PRODUCT: SUBJECT TO COMPLIANCE WITH REQUIREMENTS,
PROVIDE MTU ONSITE ENERGY MODEL 60-GC6NLT1 OR A COMPARABLE PRODUCT BY
ONE OF THE FOLLOWING:
• MTU ONSITE ENERGY OR EQUAL
ANY CHANGES TO THE GENERATOR SET INSTALLATION REQUIREMENTS DUE TO
MANUFACTURERS'PRODUCTS DIFFERING FROM THE BASIS-OF-DESIGN PRODUCT ARE
THE RESPONSIBILITY OF THE CONTRACTOR.
2. ENGINE-GENERATOR SET
A. KW/ KVA,208 VOLT 3 PHASE 12W 60HZ PACKAGED ENGINE GENERATOR SET
SHALL BE A COORDINATED ASSEMBLY OF COMPATIBLE COMPONENTS.
B. FACTORY-ASSEMBLED AND-TESTED,ENGINE-GENERATOR SET.
C. MOUNTING FRAME: MAINTAIN ALIGNMENT OF MOUNTED COMPONENTS WITHOUT
DEPENDING ON CONCRETE FOUNDATION;AND HAVE LIFTING ATTACHMENTS.
D.CAPACITIES AND CHARACTERISTICS:
• POWER OUTPUT RATINGS: NOMINAL RATINGS AS INDICATED,WITH CAPACITY AS
REQUIRED TO OPERATE AS A UNIT AS EVIDENCE BY RECORDS OF PROTOTYPE
TESTING.
• OUTPUT CONNECTIONS: 208 VOLT 3 PHASE 12W 60HZ
Page 29 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
• NAMEPLATES: FOR EACH MAJOR SYSTEM COMPONENT TO IDENTIFY
MANUFACTURER'S NAME AND ADDRESS,AND MODEL AND SERIAL NUMBER OF
COMPONENT.
E. GENERATOR-SET PERFORMANCE WITH SHUNT EXCITATION:
• STEADY-STATE VOLTAGE OPERATIONAL BANDWIDTH: 1 PERCENT OF RATED
OUTPUT VOLTAGE FROM NO LOAD TO FULL LOAD.
• TRANSIENT VOLTAGE PERFORMANCE: NOT MORE THAN 20 PERCENT VARIATION
FOR 50 PERCENT STEP-LOAD INCREASE OR DECREASE. VOLTAGE SHALL
RECOVER AND REMAIN WITHIN THE STEADY-STATE OPERATING BAND WITHIN
THREE TO FOUR SECONDS.
• STEADY-STATE FREQUENCY OPERATIONAL BANDWIDTH: 0.25 PERCENT OF
RATED FREQUENCY FROM NO LOAD TO FULL LOAD.
• STEADY-STATE FREQUENCY STABILITY: WHEN SYSTEM IS OPERATING AT ANY
CONSTANT LOAD WITHIN THE RATED LOAD,THERE SHALL BE NO RANDOM SPEED
VARIATIONS OUTSIDE THE STEADY-STATE OPERATIONAL BAND AND NO
HUNTING OR SURGING OF SPEED.
• TRANSIENT FREQUENCY PERFORMANCE: LESS THAN 5 PERCENT VARIATION FOR
50 PERCENT STEP-LOAD INCREASE OR DECREASE. FREQUENCY SHALL RECOVER
AND REMAIN WITHIN THE STEADY-STATE OPERATING BAND WITHIN FIVE
SECONDS.
• START TIME: COMPLY WITH NFPA 110,TYPE 10,SYSTEM REQUIREMENTS.
3. ENGINE GM OR FORD
A. BASIC ENGINE: CAST-IRON,OIL PAN,DRY EXHAUST MANIFOLD AND VIBRATION
DAMPER
B. RATED ENGINE SPEED: 1800 RPM
C. STARTER: ONE ELECTRIC STARTER 12V DC
D. FUEL SYSTEM: CONTROLLED BY A MICROPROCESSOR BASED ENGINE CONTROL
MODULE(ECM)AND A HIGH SPEED ELECTRONIC FUEL PRESSURE REGULATOR(EPR).
THE ECM AND EPR WORK WITH AN 02 SENSOR FOR FEEDBACK CONTROL. SYSTEMS
UTILIZING THREE WAY CATALYST ALSO EMPLOY A POST CATALYST 02 SENSOR. THE
SYSTEM OPERATES ON THE BASIS OF A STOICHIOMETRIC AIR FUEL RATIO.
E. GENERATOR: ENGINE MOUNTED BELT DRIVE
F. LUBE OIL SYSTEM: FORCED FEED LUBRICATION,LUBE OIL FILTER,FILLER NECK AND
DIP STICK
G. COMBUSTION AIR SYSTEM: DRY TYPE AIR FILTER
H. COOLING SYSTEM: COOLANT CIRCULATION PUMP AND PUSHER FAN
I. GOVERNOR:ELECTRONIC CONTROL THROUGH ECU,WITH SPEED SENSING
J. ENGINE FUEL SYSTEM:
• ELECTRONIC PRESSURE REGULATOR:REGULATES THE FUEL MIXTURE BASED ON
INTAKE AIR TEMPERATURE,LOAD,ETC.
• ECU:COUPLED INTO THE GENERATOR SET CONTROL PANEL INTERFACE TO
ALLOW DIRECT CONTROL FROM THE PANEL.
Page 30 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
• SYSTEM CONTROL:CLOSED LOOP FUEL SYSTEM USING READINGS FROM 02
SENOR(S)TO MAINTAIN PROPER FUEL MIXTURE THROUGH CONTROL OF THE
ELECTRONIC PRESSURE REGULATOR.
K. COOLANT JACKET HEATER: AN ELECTRIC WATER HEATER WITH INTEGRAL
THERMOSTATIC CONTROL,PROPERLY SIZED TO MAINTAIN ENGINE JACKET WATER
AT 90 DEGREES AND SUITABLE FOR OPERATION IN AN AMBIENT TEMPERATURE OF-
20°F(-29°C). COMPLY WITH NFPA 110 REQUIREMENTS FOR LEVEL 1 EQUIPMENT FOR
HEATER CAPACITY.
L. COOLING SYSTEM: CLOSED LOOP,LIQUID COOLED,WITH RADIATOR FACTORY
MOUNTED ON ENGINE-GENERATOR SET MOUNTING FRAME AND INTEGRAL ENGINE-
DRIVEN COOLANT PUMP.
• SOLUTION OF 50 PERCENT ETHYLENE-GLYCOL-BASED ANTIFREEZE AND 50
PERCENT WATER,WITH ANTICORROSION ADDITIVES AS RECOMMENDED BY
ENGINE MANUFACTURER.
• SIZE OF RADIATOR: ADEQUATE TO CONTAIN EXPANSION OF TOTAL SYSTEM
COOLANT FROM COLD START TO 110 PERCENT OF LOAD CONDITION.
• EXPANSION TANK: CONSTRUCTED WITHSTAND MAXIMUM CLOSED-LOOP
COOLANT SYSTEM PRESSURE FOR ENGINE USED.
• TEMPERATURE CONTROL: SELF-CONTAINED,THERMOSTATIC-CONTROL VALVE
MODULATES COOLANT FLOW AUTOMATICALLY TO MAINTAIN OPTIMUM
CONSTANT COOLANT TEMPERATURE AS RECOMMENDED BY ENGINE
MANUFACTURER.
• COOLANT HOSE: FLEXIBLE ASSEMBLY WITH INSIDE SURFACE OF NONPOROUS
RUBBER.
➢ RATING:50-PSIG(345-KPA)MAXIMUM WORKING PRESSURE WITH COOLANT AT
A TEMPERATURE OF 180°F(82°C),AND NON-COLLAPSIBLE UNDER VACUUM.
➢ END FITTINGS. FLANGES OR STEEL PIPE NIPPLES WITH CLAMPS TO SUIT
PIPING AND EQUIPMENT CONNECTIONS.
M. CRITICAL GRADE SILENCER:THE SILENCER SHALL ATTENUATE EXHAUST NOISE TO A
CRITICAL LEVEL.
• AN EXHAUST SILENCER AND FLEXIBLE STAINLESS STEEL EXHAUST FITTING
SHALL BE FURNISHED FOR INSTALLATION BY A MECHANICAL CONTRACTOR PER
MANUFACTURER'S RECOMMENDATIONS.PIPE SIZE SHALL BE SUFFICIENTLY
LARGE TO HANDLE THE ENGINE EXHAUST GAS FLOW AT FULL RATED LOAD
WITHOUT CAUSING BACK PRESSURE IN EXCESS OF THAT ALLOWED BY THE
ENGINE MANUFACTURER.
N. AIR-INTAKE FILTER: STANDARD-DUTY,ENGINE-MOUNTED AIR CLEANER WITH
REPLACEABLE DRY-FILTER ELEMENT AND"BLOCKED FILTER"-INDICATOR.
O. STARTING SYSTEM: 12 OR 24 VOLT ELECTRIC,WITH NEGATIVE GROUND
• COMPONENTS: SIZED SO THEY WILL NOT BE DAMAGED DURING A FULL ENGINE-
CRANKING CYCLE WITH AMBIENT TEMPERATURE AT MAXIMUM SPECIFIED IN
PART 1 "PROJECT CONDITIONS"ARTICLE.
• CRANKING MOTOR: HEAVY-DUTY UNIT THAT AUTOMATICALLY ENGAGES AND
RELEASES FROM ENGINE FLYWHEEL WITHOUT BINDING.
• CRANKING CYCLE: AS REQUIRED BY NFPA 110 FOR SYSTEM LEVEL SPECIFIED
Page 31 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
• BATTERY: ADEQUATE CAPACITY WITHIN AMBIENT TEMPERATURE RANGE
SPECIFIED IN PART 1 "PROJECT CONDITIONS"ARTICLE TO PROVIDE SPECIFIED
CRANKING CYCLE AT LEAST THREE TIMES]WITHOUT RECHARGING.
• BATTERY CABLE: SIZED AS RECOMMENDED BY ENGINE MANUFACTURER FOR
THE CABLE LENGTH INDICATED. INCLUDE REQUIRED INTERCONNECTING
CONDUCTORS AND CONNECTION ACCESSORIES.
• BATTERY COMPARTMENT: PLASTIC BATTERY BOX WHICH INCLUDES COVER.
INCLUDE ACCESSORIES REQUIRED TO SUPPORT AND FASTEN BATTERIES IN
PLACE.
• BATTERY CHARGER: 12VDC,CURRENT-LIMITING,AUTOMATIC-EQUALIZING AND
FLOAT-CHARGING TYPE. THE FOLLOWING FEATURES SHALL BE INCLUDED:
➢ OPERATION: EQUALIZING-CHARGING RATE OF 6 AMPS SHALL BE INITIATED
AUTOMATICALLY AFTER BATTERY HAS LOST CHARGE UNTIL AND
ADJUSTABLE EQUALIZING VOLTAGE IS ACHIEVED AT BATTERY TERMINALS.
UNIT SHALL THEN BE AUTOMATICALLY SWITCHED TO A LOWER FLOAT-
CHARGING MODE AND SHALL CONTINUE TO OPERATE IN THAT MODE UNTIL
BATTERY IS DISCHARGED AGAIN.
P. IGNITION: VARIES FROM DISTRIBUTOR TO ELECTRONIC.
4. FUEL STORAGE
A. NO ADDITIONAL STORAGE OPTIONS FOR GASEOUS UNITS
5. CONTROLS AND MONITORING
A. AUTOMATIC STARTING SYSTEM SEQUENCE OF OPERATION: WHEN MODE-SELECTOR
SWITCH ON THE CONTROL AND MONITORING PANEL IS IN THE AUTOMATIC POSITION,
REMOTE-CONTROL CONTACTS IN ONE OR MORE SEPARATE AUTOMATIC TRANSFER
SWITCHES INITIATE STARTING AND STOPPING OF GENERATOR SET. WHEN MODE-
SELECTOR SWITCH IS SWITCHED TO THE ON POSITION,THE GENERATOR SET STARTS.
THE OFF POSITION OF SAME SWITCH INITIATES GENERATOR-SET SHUTDOWN. WHEN
GENERATOR SET IS RUNNING,SPECIFIED SYSTEM OR EQUIPMENT FAILURES OR
DERANGEMENTS AUTOMATICALLY SHUT DOWN GENERATOR SET AND INITIATE
ALARMS. OPERATION OF A REMOTE EMERGENCY-STOP SWITCH ALSO SHUTS DOWN
GENERATOR SET.
B. MANUAL STARTING SYSTEM SEQUENCE OF OPERATION: SWITCHING ON-OFF SWITCH
ON THE GENERATOR CONTROL PANEL TO THE ON POSITION STARTS THE GENERATOR
SET. THE OFF POSITION OF SAME SWITCH INITIATES GENERATOR-SET SHUTDOWN.
WHEN GENERATOR SET IS RUNNING,SPECIFIED SYSTEM OR EQUIPMENT FAILURES OR
DERANGEMENTS AUTOMATICALLY SHUT DOWN GENERATOR SET AND INITIATE
ALARMS. OPERATION OF A REMOTE EMERGENCY-STOP SWITCH ALSO SHUTS DOWN
GENERATOR SET.
C. CONFIGURATION: OPERATING AND SAFETY INDICATIONS,PROTECTIVE DEVICES,
BASIC SYSTEM CONTROLS,ENGINE GAGES,INSTRUMENT TRANSFORMERS,
GENERATOR DISCONNECT SWITCH OR CIRCUIT BREAKER,AND OTHER INDICATED
COMPONENTS SHALL BE GROUPED IN A COMBINATION CONTROL AND POWER PANEL.
RIGIDLY MOUNTED TO THE GENERATOR SET.
D. DIGITAL GENERATOR CONTROLLER
• GENERATOR MOUNTED CONTROL PANEL: PROVIDE A GENERATOR MOUNTED
CONTROL PANEL MTU DGC 2020 LEVEL 1
Page 32 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
• COMMUNICATION:USB,RS485 USING MODBUS(SLAVE),AND INTERNAL
INDUSTRIAL GRADE MODEM WITH DIAL OUT AND DIAL IN CAPABILITY,SAE J1939
ENGINE ECU CAPABILITY AND SEPARATE RS485 FOR PROVIDING
COMMUNICATIONS TO A REMOTE DISPLAY PANEL FOR NFPA 110 INDICATION.
• GENERATOR CONTROL PANEL PROTECTION FEATURES: KWH/KVARH METER,
ENGINE(OVER SPEED,BATTERY OVER/UNDER VOLTAGE,AUXILIARY EXCITATION
AND SPEED/FREQUENCY MISMATCH),GENERATOR(OVER/UNDER VOLTAGE,
OVER/UNDER FREQUENCY,UNBALANCED VOLTAGE,DEAD BUS DETECTION,
OVERLOAD,REVERSE/REDUCED POWER)
• AGENCY APPROVALS:
➢ CONFORMS TO UL 508,INDUSTRIAL CONTROL EQUIPMENT—UL RECOGNIZED
COMPONENT
➢ CONFORMS TO CSA STD.C22.2 NO. 14,INDUSTRIAL CONTROL EQUIPMENT—
CSA CERTIFIED
➢ COMPLIES WITH NFPA 110, STANDARD FOR EMERGENCY AND STANDBY
POWER SYSTEMS
• CE COMPLIANCE:
➢ THIS PRODUCT COMPLIES WITH THE REQUIREMENTS OF THE FOLLOWING EC
DIRECTIVES:
➢ LOW VOLTAGE DIRECTIVE(LVD)-73/23/EEC AS AMENDED BY 93/68/EEC
➢ ELECTROMAGNETIC COMPATIBILITY(EMC)-89/336/EEC AS AMENDED BY
92/31/EEC AND 93/68/EEC
➢ EN 50178:1997-ELECTRONIC EQUIPMENT FOR USE IN POWER INSTALLATIONS
➢ EN 61000-64:2001 -ELECTROMAGNETIC COMPATIBILITY(EMC),GENERIC
STANDARDS,EMISSION STANDARD FOR INDUSTRIAL ENVIRONMENTS
➢ EN 61000-6-2:2001 -ELECTROMAGNETIC COMPATIBILITY(EMC),GENERIC
STANDARDS,IMMUNITY FOR INDUSTRIAL ENVIRONMENTS
• ENVIRONMENTAL:
➢ TEMPERATURE:OPERATING:-40°TO 158°F(-40°TO 70°C),STORAGE:-40°TO
185°F (40°TO 85°C)
➢ HUMIDITY:IEC 68-2-38
➢ SALT FOG:ASTM B 17-73,IEC 68-2-11 (TESTED WHILE OPERATIONAL)
➢ INGRESS PROTECTION:IEC IP54 FOR FRONT PANEL
➢ SHOCK: 15 G IN 3 PERPENDICULAR PLANES
➢ VIBRATION:
0 5 TO 29 TO 5 HZ: 1.5 G PEAK FOR 5 MIN.
o 29 TO 52 TO 29 HZ:0.036"DECS-A FOR 2.5 MIN.
0 52 TO 500 TO 52 HZ:5 G PEAK FOR 7.5 MIN.
• ENGINE CONTROL:
➢ CRANKING CONTROL:CYCLE OR CONTINUOUS(QUANTITY AND DURATION
FULLY PROGRAMMABLE)
➢ ENGINE COOL DOWN
➢ SUCCESSFUL START COUNTER:COUNTS AND RECORDS SUCCESSFUL ENGINE
STARTS
➢ TIMERS INCLUDING,BUT NOT LIMITED TO:
o ENGINE COOL DOWN TIMER
o ENGINE MAINTENANCE TIMER
o PRE-ALARM TIME DELAYS FOR WEAK/LOW BATTERY VOLTAGE
o ALARM TIME DELAY FOR OVER SPEED
Page 33 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
o ALARM TIME DELAY FOR SENDER FAILURE.
o ARMING TIME DELAYS AFTER CRANK DISCONNECT:
■ LOW OIL PRESSURE
■ HIGH COOLANT TEMPERATURE
• ALARMS:
➢ LOW OIL PRESSURE
➢ HIGH COOLANT TEMPERATURE
➢ LOW COOLANT LEVEL
➢ LOW FUEL LEVEL
➢ OVER SPEED
➢ OVER CRANK
➢ ENGINE SENDER UNIT FAILURE
➢ EMERGENCY STOP
➢ BATTERY CHARGER FAILURE
• PRE-ALARMS:
➢ LOW OIL PRESSURE
➢ HIGH COOLANT TEMPERATURE
➢ LOW COOLANT TEMPERATURE
➢ BATTERY OVERVOLTAGE
➢ WEAK BATTERY
➢ BATTERY CHARGER FAILURE
➢ ENGINE SENDER UNIT FAILURE
➢ ENGINE KW OVERLOAD(3 LEVELS)
➢ MAINTENANCE INTERVAL TIMER
➢ LOW COOLANT LEVEL
• GENERATOR PROTECTION ANSI FUNCTIONS:
➢ UNDER VOLTAGE(27)
➢ OVERVOLTAGE(59)
➢ ANSI CODES REVERSE POWER(32)
➢ OVER FREQUENCY(810)
➢ LOSS OF EXCITATION(40Q)
➢ UNDER FREQUENCY(81U)
E. INDICATING AND PROTECTIVE DEVICES AND CONTROLS: AS REQUIRED BY NFPA 110
FOR LEVEL 1 SYSTEM,AND THE FOLLOWING ACCESSORIES:
F. SUPPORTING ITEMS: INCLUDE SENSORS,TRANSDUCERS,TERMINALS,RELAYS,AND
OTHER DEVICES AND INCLUDE WIRING REQUIRED TO SUPPORT SPECIFIED ITEMS.
LOCATE SENSORS AND OTHER SUPPORTING ITEMS ON ENGINE OR GENERATOR,
UNLESS OTHERWISE INDICATED.
G. CONNECTION TO DATA LINK: A SEPARATE TERMINAL BLOCK,FACTOR WIRED TO
FORM C DRY CONTACTS,FOR EACH ALARM AND STATUS INDICATION IS RESERVED
FOR CONNECTIONS FOR DATA-LINK TRANSMISSION OF INDICATIONS TO REMOTE
DATA TERMINALS. DATA SYSTEM CONNECTIONS TO TERMINALS ARE COVERED IN
SECTION 260913 "ELECTRICAL POWER MONITORING AND CONTROL."
H. COMMON REMOTE AUDIBLE ALARM: COMPLY WITH NFPA 110 REQUIREMENTS FOR
LEVEL 1 SYSTEMS. INCLUDE NECESSARY CONTACTS AND TERMINALS IN CONTROL
AND MONITORING PANEL.
Page 34 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
• OVERCRANK SHUTDOWN.
• COOLANT LOW-TEMPERATURE ALARM.
• CONTROL SWITCH NOT IN AUTO POSITION.
• BATTERY-CHARGER MALFUNCTION ALARM.
• BATTERY LOW-VOLTAGE ALARM.
I. COMMON REMOTE AUDIBLE ALARM: SIGNAL THE OCCURRENCE OF ANY EVENT
LISTED BELOW WITHOUT DIFFERENTIATING BETWEEN EVENT TYPES. CONNECT SO
THAT AFTER AN ALARM IS SILENCED,CLEARING OF INITIATING CONDITION WILL
REACTIVATE ALARM UNTIL SILENCING SWITCH IS RESET.
• ENGINE HIGH-TEMPERATURE SHUTDOWN.
• LUBE-OIL,LOW-PRESSURE SHUTDOWN.
• OVERSPEED SHUTDOWN.
• REMOTE EMERGENCY-STOP SHUTDOWN.
• ENGINE HIGH-TEMPERATURE PRE-ALARM.
• LUBE-OIL,LOW-PRESSURE PRE-ALARM.
• FUEL TANK,LOW-FUEL LEVEL.
• LOW COOLANT LEVEL.
J. REMOTE ALARM ANNUNCIATOR: NONE
K. REMOTE EMERGENCY-STOP SWITCH: NONE
L. DIFFERENTIAL CURRENT TRANSFORMER: NONE
M. PARALLELING CURRENT TRANSFORMER: NONE
N. VOLTAGE REGULATOR SENSING POTENTIAL TRANSFORMER: NONE
6. GENERATOR OVERCURRENT AND FAULT PROTECTION
A. GENERATOR CIRCUIT BREAKER: ADJUSTABLE THERMAL-MAGNETIC TRIP TYPE;80
PERCENT RATED;COMPLYING WITH NEMA AB 1 AND UL 489
• MANUFACTURERS:
➢ GENERAL ELECTRIC
➢ CUTLER HAMMER
➢ SQUARE D
B. PRODUCT DESCRIPTION:ENCLOSED,MOLDED-CASE CIRCUIT BREAKER CONFORMING
TO NEMA AB 1 AND FS-W-C
C. ACCESSORIES:CONFORM TO NEMA AB 1.
• SHUNT TRIP DEVICE:24 VOLTS,DC.
• UNDERVOLTAGE TRIP DEVICE.
• AUXILIARY SWITCH: 120 VOLTS,AC.
• ALARM SWITCH: 120 VOLTS,AC.
• HANDLE LOCK:PROVISIONS FOR PADLOCKING.
• ENCLOSURE:NEMA ICS 6,TYPE[1 ,4,3R STAINLESS STEEL OR BETTER],
MOUNTED ON THE ENGINE-GENERATOR SET.
D. GENERATOR PROTECTION: MICROPROCESSOR-BASED DEVICE SHALL CONTINUOUSLY
Page 35 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
MONITOR THE TOTAL KVA LEVEL OF THE GENERATOR OUTPUT,ANNUNCIATING
CONDITIONS THAT MAY RESULT IN GENERATOR DAMAGE.
PROTECTIVE DEVICES SHALL PERFORM THE FOLLOWING FUNCTIONS:
• INITIATES A GENERATOR OVERLOAD PRE-ALARM WHEN GENERATOR HAS
OPERATED AT AN OVERLOAD EQUIVALENT TO 105 PERCENT OF FULL-RATED
LOAD FOR 5 SECONDS. INDICATION FOR THIS ALARM IS INTEGRATED WITH
OTHER GENERATOR SET MALFUNCTION PRE-ALARMS.
• INDICATES A GENERATOR OVERLOAD ALARM WHEN GENERATOR HAS OPERATED
AT AN OVERLOAD EQUIVALENT TO 105 PERCENT OF FULL-RATED LOAD FOR 300
SECONDS. INDICATION FOR THIS ALARM IS INTEGRATED WITH OTHER
GENERATOR SET MALFUNCTION ALARMS.
E. GROUND-FAULT INDICATION: NONE
7. GENERATOR,EXCITER,AND VOLTAGE REGULATOR
A. COMPLY WITH NEMA MG 1
B. DRIVE: GENERATOR SHAFT SHALL BE DIRECTLY CONNECTED TO THE ENGINE SHAFT.
EXCITER SHALL BE ROTATED INTEGRALLY WITH GENERATOR ROTOR.
C. ELECTRICAL INSULATION: CLASS H OR CLASS F
D. STATOR-WINDING LEADS: BROUGHT OUT TO TERMINAL BOX TO PERMIT FUTURE
RECONNECTION FOR OTHER VOLTAGES IF REQUIRED.
E. CONSTRUCTION SHALL PREVENT MECHANICAL,ELECTRICAL,AND THERMAL
DAMAGE DUE TO VIBRATION,OVERSPEED UP TO 125 PERCENT OF RATING,AND HEAT
DURING OPERATION AT 110 PERCENT OF RATED CAPACITY.
F. ENCLOSURE: DRIP PROOF
G. INSTRUMENT TRANSFORMERS: MOUNTED WITHIN GENERATOR ENCLOSURE
H. VOLTAGE REGULATOR: ANALOG VOLTAGE CONTROLLER REGULATES VOLTAGE ON
50 OR 60 HERTZ BRUSHLESS GENERATORS.THE CONTROLLERS INCLUDE FREQUENCY
COMPENSATION,OVER-EXCITATION SHUTDOWN,SOLID-STATE BUILDUP CIRCUITRY,
AND EMI FILTERING. ADJUSTMENT POTENTIOMETERS ARE LOCATED ON THE
TERMINALS AND COMPONENTS SIDE OF THE CONTROLLER.IF REMOTE ADJUSTMENT
OF THE GENERATOR OUTPUT IS DESIRED,THE VOLTAGE ADJUST RHEOSTAT JUMPER
MUST BE REPLACED WITH A USER-SUPPLIED RHEOSTAT.A 1000 OHM,'h-WATT
RHEOSTAT WILL PROVIDE ADEQUATE VOLTAGE ADJUSTMENT RANGE FOR MOST
APPLICATIONS.
8. OUTDOOR GENERATOR-SET ENCLOSURE
A. DESCRIPTION: NO WIND RATING SPECIFIED.
B. DESCRIPTION: ALUMINUM ENCLOSURE WITH THE FOLLOWING FEATURES:
• CONSTRUCTION: FORMED AND/OR WELDED ALUMINUM.
• HINGED DOORS FOR ACCESS WITH LOCKABLE LATCHES.
• LOUVERED AND/OR BAFFLED AIR INLET. GRATED AIR OUTLET.
Page 36 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
• INTERIOR LINED WITH ACOUSTICAL FOAM FOR SOUND ATTENUATION.
• INTEGRATED INTAKE AND EXHAUST SCOOPS ARE INSTALLED FOR ADDITIONAL
SOUND ATTENUATION.
• CHOICE OF STANDARD COLORS. CUSTOM COLORS AVAILABLE UPON REQUEST.
• ADDITIONAL ENCLOSURE FEATURES:
➢ EXHAUST SCOOP
o ALUMINUM HOUSING EXTENSION INTENDED TO REDIRECT EXHAUST
AIR VERTICAL INSTEAD OF HORIZONTAL TO INCREASE SOUND
ATTENUATION.
➢ SOUND ATTENUATION
o APPLICATION OF FOAM MATERIAL TO REDUCE NOISE EMISSIONS,
LEVEL 3,DBA TO MEET 70DBA @ 23FT
9. VIBRATION ISOLATION DEVICES
A. NEOPRENE PAD
• '/INCH THICK ELASTOMERIC PAD IN SQUARE SHAPE TO BE PLACED UNDER THE
BASE FRAME AT EACH OF THE PRE-DRILLED ISOLATOR MOUNTING HOLES.
• HELPS TO PREVENT SLIDING OF THE UNIT AS WELL AS REDUCING THE
TRANSMISSION OF SOUND AND VIBRATION INTO THE FLOOR.
10. FINISHES
A. INDOOR AND OUTDOOR ENCLOSURES AND COMPONENTS: MANUFACTURER'S
STANDARD FINISH OVER CORROSION-RESISTANT PRETREATMENT AND COMPATIBLE
PRIMER.
11. SOURCE QUALITY CONTROL
A. PROTOTYPE TESTING: FACTORY TEST ENGINE-GENERATOR SET USING SAME ENGINE
MODEL,CONSTRUCTED OF IDENTICAL OR EQUIVALENT COMPONENTS AND EQUIPPED
WITH IDENTICAL OR EQUIVALENT ACCESSORIES.
• TESTS: COMPLY WITH NFPA 110,LEVEL 1 ENERGY CONVERTERS AND WITH IEEE
115
B. PROJECT-SPECIFIC EQUIPMENT TESTS: BEFORE SHIPMENT,FACTORY TEST ENGINE-
GENERATOR SET AND OTHER SYSTEM COMPONENTS AND ACCESSORIES
MANUFACTURED SPECIFICALLY FOR THIS PROJECT. PERFORM TESTS AT RATED
LOAD AND POWER FACTOR. INCLUDE THE FOLLOWING TESTS:
• TEST COMPONENTS AND ACCESSORIES FURNISHED WITH INSTALLED UNIT THAT
ARE NOT IDENTICAL TO THOSE ON TESTED PROTOTYPE TO DEMONSTRATE
COMPATIBILITY AND RELIABILITY.
• FULL LOAD RUN
• MAXIMUM POWER
• VOLTAGE REGULATION
• TRANSIENT AND STEADY-STATE GOVERNING
• SINGLE-STEP LOAD PICKUP
• SAFETY SHUTDOWN
• PROVIDE 14 DAYS'ADVANCE NOTICE OF TESTS AND OPPORTUNITY FOR
OBSERVATION OF TESTS BY OWNER'S REPRESENTATIVE
• REPORT FACTORY TEST RESULTS WITHIN 10 DAYS OF COMPLETION OF TEST
Page 37 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
EXECUTION
1. EXAMINATION
A. EXAMINE AREAS,EQUIPMENT BASES,AND CONDITIONS,WITH INSTALLER PRESENT,
FOR COMPLIANCE WITH REQUIREMENTS FOR INSTALLATION AND OTHER
CONDITIONS AFFECTING PACKAGED ENGINE-GENERATOR SET PERFORMANCE.
B. EXAMINE ROUGHING-IN OF PIPING SYSTEMS AND ELECTRICAL CONNECTIONS.
VERIFY ACTUAL LOCATIONS OF CONNECTIONS BEFORE PACKAGED ENGINE-
GENERATOR INSTALLATION.
C. PROCEED WITH INSTALLATION ONLY AFTER UNSATISFACTORY CONDITIONS HAVE
BEEN CORRECTED.
2. INSTALLATION
A. COMPLY WITH PACKAGED ENGINE-GENERATOR MANUFACTURERS' WRITTEN
INSTALLATION AND ALIGNMENT INSTRUCTIONS AND WITH NFPA 110.
B. INSTALL PACKAGED ENGINE GENERATOR TO PROVIDE ACCESS,WITHOUT REMOVING
CONNECTIONS OR ACCESSORIES,FOR PERIODIC MAINTENANCE.
C. INSTALL PACKAGED ENGINE-GENERATOR WITH VMC GROUP OSHPD PRE-APPROVED
VIBRATION SPRING ISOLATORS HAVING A MINIMUM DEFLECTION OF 1.07 INCHES ON
A 10 INCH HIGH CONCRETE BASE. SECURE SETS TO ANCHOR BOLTS INSTALLED IN
CONCRETE BASES. CONCRETE BASE CONSTRUCTION IS SPECIFIED IN SECTION 260548
"VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS."
D. ELECTRICAL WIRING: INSTALL ELECTRICAL DEVICES FURNISHED BY EQUIPMENT
MANUFACTURERS BUT NOT SPECIFIED TO BE FACTORY MOUNTED.
3. CONNECTIONS
A. COORDINATE PIPING INSTALLATIONS AND SPECIALTY ARRANGEMENTS WITH
SCHEMATICS ON DRAWINGS AND WITH REQUIREMENTS SPECIFIED IN PIPING
SYSTEMS. IF DRAWINGS ARE EXPLICIT ENOUGH,THESE REQUIREMENTS MAY BE
REDUCED OR OMITTED.
B. PIPING INSTALLATION REQUIREMENTS ARE SPECIFIED IN DIVISION 23 SECTIONS.
DRAWINGS INDICATE GENERAL ARRANGEMENT OF PIPING AND SPECIALTIES.
C. CONNECT FUEL,COOLING-SYSTEM,AND EXHAUST-SYSTEM PIPING ADJACENT TO
PACKAGED ENGINE GENERATOR TO ALLOW SERVICE AND MAINTENANCE.
D. CONNECT FUEL PIPING TO ENGINES WITH A GATE VALVE AND UNION AND FLEXIBLE
CONNECTOR.
• DIESEL STORAGE TANKS,TANK ACCESSORIES,PIPING,VALVES,AND SPECIALTIES
FOR FUEL SYSTEMS ARE SPECIFIED IN DIVISION 23 SECTION"FACILITY FUEL-OIL
PIPING."
• NATURAL-GAS PIPING,VALVES,AND SPECIALTIES FOR GAS DISTRIBUTION ARE
SPECIFIED IN DIVISION 23 SECTION"FACILITY NATURAL-GAS PIPING."
Page 38 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
• LP-GAS PIPING,VALVES,AND SPECIALTIES FOR GAS PIPING ARE SPECIFIED IN
DIVISION 23 SECTION"FACILITY LIQUEFIED-PETROLEUM GAS PIPING."
E. GROUND EQUIPMENT ACCORDING TO DIVISION 26 SECTION"GROUNDING AND
BONDING FOR ELECTRICAL SYSTEMS."
F. CONNECT WIRING ACCORDING TO DIVISION 26 SECTION"LOW-VOLTAGE ELECTRICAL
POWER CONDUCTORS AND CABLES."
4. IDENTIFICATION
A. IDENTIFY SYSTEM COMPONENTS ACCORDING TO DIVISION 23 SECTION
"IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT"AND DIVISION 26 SECTION
"IDENTIFICATION FOR ELECTRICAL SYSTEMS."
5. FIELD QUALITY CONTROL
A. TESTING AGENCY:OWNER WILL ENGAGE A QUALIFIED TESTING AGENCY TO
PERFORM TESTS AND INSPECTIONS AND PREPARE TEST REPORTS.
B. MANUFACTURER'S FIELD SERVICE: ENGAGE A FACTORY-AUTHORIZED SERVICE
REPRESENTATIVE TO INSPECT,TEST,AND ADJUST COMPONENTS,ASSEMBLIES,AND
EQUIPMENT INSTALLATIONS,INCLUDING CONNECTIONS. REPORT RESULTS IN
WRITING.
C. PERFORM TESTS AND INSPECTIONS AND PREPARE TEST REPORTS.
• MANUFACTURER'S FIELD SERVICE: ENGAGE A FACTORY-AUTHORIZED SERVICE
REPRESENTATIVE TO INSPECT COMPONENTS,ASSEMBLIES,AND EQUIPMENT
INSTALLATIONS,INCLUDING CONNECTIONS,AND TO ASSIST IN TESTING.
➢ MEASURE CHARGING VOLTAGE AND VOLTAGES BETWEEN AVAILABLE
BATTERY TERMINALS FOR FULL-CHARGING AND FLOAT-CHARGING
CONDITIONS. CHECK ELECTROLYTE LEVEL AND SPECIFIC GRAVITY UNDER
BOTH CONDITIONS.
➢ TEST FOR CONTACT INTEGRITY OF ALL CONNECTORS. PERFORM AN
INTEGRITY LOAD TEST AND A CAPACITY LOAD TEST FOR THE BATTERY.
➢ VERIFY ACCEPTANCE OF CHARGE FOR EACH ELEMENT OF THE BATTERY
AFTER DISCHARGE.
➢ VERIFY THAT MEASUREMENTS ARE WITHIN MANUFACTURER'S
SPECIFICATIONS.
• BATTERY-CHARGER TESTS: VERIFY SPECIFIED RATES OF CHARGE FOR BOTH
EQUALIZING AND FLOAT-CHARGING CONDITIONS.
• NOISE LEVEL TESTS: PROVIDE CALCULATED NOISE MEASUREMENT OF THE
COMPLETE GENERATOR PACKAGE.
• OPERATIONAL TEST: AFTER ELECTRICAL CIRCUITRY HAS BEEN ENERGIZED,
START UNITS TO CONFIRM PROPER MOTOR ROTATION AND UNIT OPERATION.
• TEST AND ADJUST CONTROLS AND SAFETIES. REPLACE DAMAGED AND
MALFUNCTIONING CONTROLS AND EQUIPMENT.
• REMOVE AND REPLACE MALFUNCTIONING UNITS AND RETEST AS SPECIFIED
ABOVE.
• RETEST: CORRECT DEFICIENCIES IDENTIFIED BY TESTS AND OBSERVATIONS AND
RETEST UNTIL SPECIFIED REQUIREMENTS ARE MET.
Page 39 of 52
J '
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
6. DEMONSTRATION
A. ENGAGE A FACTORY-AUTHORIZED SERVICE REPRESENTATIVE TO TRAIN OWNER'S
MAINTENANCE PERSONNEL TO ADJUST,OPERATE,AND MAINTAIN PACKAGED
ENGINE GENERATORS.
1
Page 40 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
250 MCM CABLE
2000V,90°C(40°C),OIL AND SUNLIGHT RESISTANT
COLOR:
ALL COLORS AVAILABLE
APPLICATIONS:
TYPE W PORTABLE POWER CABLE IS SUITABLE FOR USE IN INDUSTRIAL AND LIGHT-TO-MEDIUM
MINING APPLICATIONS,HEAVY-DUTY SERVICE,TEMPORARY POWER SUPPLY CABLES,MOTOR,
BATTERY AND GENERATOR LEADS.ALSO SUITABLE FOR MOBILE AND PORTABLE ELECTRICAL
EQUIPMENT.
COMPLIANCES:
• UL LISTED-TYPE W PER UL 1650
• CONDUCTORS ARE MANUFACTURED IN ACCORDANCE WITH ASTM AND B-172
• MADE IN ACCORDANCE WITH ICEA S-75-381
• NEMA WC-58-PORTABLE AND POWER FEEDER CABLES FOR USE IN MINES AND SIMILAR
LOCATIONS
• MSHA ACCEPTED,P-136-135,LR65300
• UL LISTED AS TYPE RHH OR RHW-2
• CSA OR C(UL)CERTIFIED AS APPLICABLE
• ROHS COMPLIANT
• MEETS FT-5 FLAME TEST
CONDUCTOR:
FULLY ANNEALED STRANDED BARE COPPER PER ASTM B-172.
INSULATION:
EP RUBBER INSULATION
JACKET:
CPE RUBBER JACKETS ARE REINFORCED BY A BRAID OR SERVE OF SYNTHETIC MATERIAL.
SPECIFICATIONS:
SIZE: 250 MCM
NUMBER OF CONDUCTORS: 1
CONDUCTOR STRAND: 627
NOMINAL INSULATION THICKNESS: 0.095 INCHES/2.41 MM
OUTSIDE,DIAMETER: 1.045 INCHES/26.54 MM
CURRENT AMPS: 455
NET WEIGHT: 1.155 LBS PER FT
Page 41 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
500 MCM CABLE
2000V,90°C(40°C),OIL AND SUNLIGHT RESISTANT
COLOR:
ALL COLORS AVAILABLE
APPLICATIONS:
TYPE W PORTABLE POWER CABLE IS SUITABLE FOR USE IN INDUSTRIAL AND LIGHT-TO-MEDIUM
MINING APPLICATIONS,HEAVY-DUTY SERVICE,TEMPORARY POWER SUPPLY CABLES,MOTOR,
BATTERY AND GENERATOR LEADS.ALSO SUITABLE FOR MOBILE AND PORTABLE ELECTRICAL
EQUIPMENT.
COMPLIANCES:
• UL LISTED-TYPE W PER UL 1650
• CONDUCTORS ARE MANUFACTURED IN ACCORDANCE WITH ASTM AND B-172
• MADE IN ACCORDANCE WITH ICEA S-75-381
• NEMA WC-58-PORTABLE AND POWER FEEDER CABLES FOR USE IN MINES AND SIMILAR
LOCATIONS
• MSHA ACCEPTED,P-136-135,LR65300
• UL LISTED AS TYPE RHH OR RHW-2
• CSA OR C(UL)CERTIFIED AS APPLICABLE
• ROHS COMPLIANT
• MEETS FT-5 FLAME TEST
CONDUCTOR:
FULLY ANNEALED STRANDED BARE COPPER PER ASTM B-172
INSULATION:
EP RUBBER INSULATION
JACKET:
CPE RUBBER JACKETS ARE REINFORCED BY A BRAID OR SERVE OF SYNTHETIC MATERIAL
SPECIFICATIONS:
SIZE: 500 MCM
NUMBER OF CONDUCTORS: 1
CONDUCTOR STRAND: 1235
NOMINAL INSULATION THICKNESS: 0.095 INCHES/2.41 MM
OUTSIDE DIAMETER: 1.310 INCHES/33.28 MM
CURRENT AMPS: 700
NET WEIGHT: 2.048 LBS PER FT
Page 42 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
AUTOMATIC TRANSFER SWITCH(ATS)SPECIFICATIONS
GENERAL
1. SCOPE
A. FURNISH DELAYED TRANSITION TRANSFER SWITCH WITH NUMBER OF POLES,
AMPERAGE, VOLTAGE, AND WITHSTAND CURRENT RATINGS AS SHOWN ON THE
-PLANS. EACH DTTS SHALL CONSIST OF A POWER TRANSFER SWITCH UNIT AND A
CONTROL PANEL INTERCONNECTED TO PROVIDE COMPLETE AUTOMATIC
OPERATION. ALL TRANSFER SWITCHES SHALL BE THE PRODUCT OF THE SAME
MANUFACTURER.
B. THE SWITCH SHALL TRANSFER THE LOAD IN DELAYED TRANSITION(BREAK-BEFORE-
MAKE) MODE. TRANSFER IS ACCOMPLISHED WITH A USER—DEFINED INTERRUPTION
PERIOD IN BOTH DIRECTIONS,(SEE 3.03 TIME DELAYS FOR ADJUSTMENT RANGE).
C. THE LOAD DISCONNECT TIME DELAY SHALL BE CONFIGURED TO BE ACTIVE FOR ALL
TRANSFERS OR TO BE BYPASSED IN THE EVENT THAT THE VOLTAGE OF ALL THREE
PHASES OF THE SOURCE THE LOAD IS CONNECTED TO DROP BELOW 70%OF NOMINAL
2. CODES AND STANDARDS
THE AUTOMATIC TRANSFER SWITCHES AND CONTROLS SHALL CONFORM TO THE
REQUIREMENTS OF:
A. UL 1008-STANDARD FOR TRANSFER SWITCH EQUIPMENT
B. CSA C22.2 NO.178—1978
C. IEC 60947-6-1 LOW-VOLTAGE SWITCHGEAR AND CONTROL GEAR;MULTIFUNCTION
EQUIPMENT;AUTOMATIC TRANSFER SWITCHING EQUIPMENT
D. NFPA 70-NATIONAL ELECTRICAL CODE
E. NFPA 99-ESSENTIAL ELECTRICAL SYSTEMS FOR HEALTH CARE FACILITIES
F. NFPA 110-EMERGENCY AND STANDBY POWER SYSTEMS
G. IEEE STANDARD 446-IEEE RECOMMENDED PRACTICE FOR EMERGENCY AND
STANDBY POWER SYSTEMS FOR COMMERCIAL AND INDUSTRIAL APPLICATIONS
H. NEMA STANDARD ICS10-1993(FORMERLY ICS2-447)-AC AUTOMATIC TRANSFER
SWITCHES
I. INTERNATIONAL STANDARDS ORGANIZATION ISO 9001:2008
J. IEC 60947-6-1
3. ACCEPTABLE MANUFACTURERS
A. TRANSFER SWITCH SHALL BE:
a. EMERSON NETWORK POWER—ASCO 300 SERIES
b. SUBSTITUTIONS: PROPOSED SUBSTITUTIONS SHALL INCLUDE COMPLETE
SUBMITTAL DATA, AS SPECIFIED HEREIN, CLEARLY DENOTING ANY AND ALL
DEVIATIONS AND/OR EXCEPTIONS TO THE EQUIPMENT SPECIFIED. THE
COMPLETE PROPOSAL MUST BE SUBMITTED TO THE ENGINEER OR ARCHITECT
FOR APPROVAL/DISAPPROVAL NOT LESS THAN 10 DAYS PRIOR TO THE
SCHEDULED BID DATE. IF APPROVED,THE CONTRACTOR IS RESPONSIBLE FOR
THE CHARGES FOR ALL NECESSARY REVISIONS.
Page 43 of 52
I
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
PRODUCTS
1. MECHANICALLY HELD TRANSFER SWITCH
A. THE TRANSFER SWITCH SHALL BE ELECTRICALLY OPERATED AND MECHANICALLY
HELD. THE ELECTRICAL OPERATOR SHALL BE A MOMENTARILY ENERGIZED, SINGLE-
SOLENOID MECHANISM. MAIN OPERATORS WHICH INCLUDE OVERCURRENT
DISCONNECT DEVICES,LINEAR MOTORS OR GEARS SHALL NOT BE ACCEPTABLE. THE
SWITCH SHALL BE MECHANICALLY INTERLOCKED TO ENSURE ONLY TWO POSSIBLE
POSITIONS,NORMAL OR EMERGENCY.
B. THE SWITCH SHALL BE POSITIVELY LOCKED AND UNAFFECTED BY MOMENTARY
OUTAGES, SO THAT CONTACT PRESSURE IS MAINTAINED AT A CONSTANT VALUE
AND CONTACT TEMPERATURE RISE IS MINIMIZED FOR MAXIMUM RELIABILITY AND
OPERATING LIFE.
C. ALL MAIN CONTACTS SHALL BE SILVER COMPOSITION. SWITCHES RATED 800
AMPERES AND ABOVE SHALL HAVE SEGMENTED, BLOW-ON CONSTRUCTION FOR
HIGH WITHSTAND AND CLOSE-ON CAPABILITY AND BE PROTECTED BY SEPARATE
ARCING CONTACTS.
D. DESIGNS, WHERE THE WIRING HARNESS, CONTROLLER, AND CONTACTOR ARE NOT
ALL FABRICATED AND ASSEMBLED BY ONE MANUFACTURER ARE NOT ACCEPTABLE.
E. INSPECTION OF ALL CONTACTS SHALL BE POSSIBLE FROM THE FRONT OF THE
SWITCH WITHOUT DISASSEMBLY OF OPERATING LINKAGES AND WITHOUT
DISCONNECTION OF POWER CONDUCTORS. SWITCHES RATED 600 AMPS AND HIGHER
SHALL HAVE FRONT REMOVABLE AND REPLACEABLE CONTACTS. ALL STATIONARY
AND MOVEABLE CONTACTS SHALL BE REPLACEABLE WITHOUT REMOVING POWER
CONDUCTORS AND/OR BUS BARS.
F. DESIGNS UTILIZING COMPONENTS OF MOLDED-CASE CIRCUIT BREAKERS,
CONTACTORS, OR PARTS THEREOF, WHICH ARE NOT INTENDED FOR CONTINUOUS
DUTY, REPETITIVE SWITCHING OR TRANSFER BETWEEN TWO ACTIVE POWER
SOURCES ARE NOT ACCEPTABLE.
H. WHERE NEUTRAL CONDUCTORS ARE TO BE SOLIDLY CONNECTED AS SHOWN ON THE
PLANS, A NEUTRAL CONDUCTOR PLATE WITH FULLY RATED AL-CU PRESSURE
CONNECTORS SHALL BE PROVIDED.
2. GROUP`G'CONTROLLER WITH INTEGRATED USER INTERFACE PANEL
A. THE CONTROLLER SHALL BE CONNECTED TO THE TRANSFER SWITCH BY AN
INTERCONNECTING WIRING HARNESS. THE HARNESS SHALL INCLUDE A KEYED
DISCONNECT PLUG TO ENABLE THE CONTROLLER TO BE DISCONNECTED FROM THE
TRANSFER SWITCH FOR ROUTINE MAINTENANCE.
B. THE CONTROLLER SHALL DIRECT THE OPERATION OF THE TRANSFER SWITCH. THE
CONTROLLER'S SENSING AND LOGIC SHALL BE CONTROLLED BY A BUILT-IN
MICROPROCESSOR FOR MAXIMUM RELIABILITY, MINIMUM MAINTENANCE,
INHERENT SERIAL COMMUNICATIONS CAPABILITY, AND THE ABILITY TO
COMMUNICATE VIA THE ETHERNET THROUGH OPTIONAL COMMUNICATIONS
MODULE.
C. A SINGLE CONTROLLER SHALL PROVIDE SINGLE AND THREE PHASE CAPABILITY FOR
MAXIMUM APPLICATION FLEXIBILITY AND MINIMAL SPARE PART REQUIREMENTS.
VOLTAGE SENSING SHALL BE TRUE RMS TYPE AND SHALL BE ACCURATE TO± 1%OF
NOMINAL VOLTAGE. FREQUENCY SENSING SHALL BE ACCURATE TO f O.1HZ. TIME
DELAY SETTINGS SHALL BE ACCURATE TO f 0.5%OF THE FULL SCALE VALUE OF THE
TIME DELAY. THE PANEL SHALL BE CAPABLE OF OPERATING OVER A TEMPERATURE
RANGE OF-20 TO+70 DEGREES C,AND STORAGE FROM-55 TO+85 DEGREES C.
Page 44 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
D. THE CONTROLLER SHALL BE ENCLOSED WITH A PROTECTIVE COVER AND BE
MOUNTED SEPARATE FROM THE TRANSFER SWITCH UNIT FOR SAFETY AND EASE OF
MAINTENANCE. SENSING AND CONTROL LOGIC SHALL BE PROVIDED ON PRINTED
CIRCUIT BOARDS.
E. THE CONTROLLER SHALL MEET OR EXCEED THE REQUIREMENTS FOR
ELECTROMAGNETIC COMPATIBILITY(EMC)AS FOLLOWS:
1. CISPR 11—CONDUCTED RF EMISSIONS AND RADIATED RF EMISSIONS
2. IEC 60947—6—1MULTIPLE FUNCTION EQUIPMENT TRANSFER SWITCHING
EQUIPMENT,61000-4 TESTING AND MEASUREMENT TECHNIQUES-OVERVIEW:
a. IEC 61000—4-2 ELECTROSTATIC DISCHARGE IMMUNITY
b. IEC 61000-4-3 RADIATED RF FIELD IMMUNITY
c. IEC 61000-4-4 ELECTRICAL FAST TRANSIENT/BURST IMMUNITY
d. IEC 61000—4-5 SURGE IMMUNITY
e. IEC 61000-4-6 CONDUCTED RF IMMUNITY
3. ENCLOSURE
A. THE SWITCH SHALL BE FURNISHED IN EITHER A NEMA 4X OR NEMA 3R ENCLOSURE.
B. PROVIDE STRIP HEATER WITH THERMOSTAT FOR NEMA 4X AND/OR NEMA 3R
ENCLOSURES.
C. UNLESS OTHERWISE NOTED,ALL ATS WILL BE FURNISHED IN ANSY 61 GRAY.
OPERATION
1. CONTROLLER DISPLAY AND KEYPAD
A. A 128*64 GRAPHICAL LCD DISPLAY AND KEYPAD SHALL BE AN INTEGRAL PART OF
THE CONTROLLER FOR, VIEWING ALL AVAILABLE DATA AND SETTING DESIRED
OPERATIONAL PARAMETERS. OPERATIONAL PARAMETERS SHALL ALSO BE
AVAILABLE FOR VIEWING AND LIMITED CONTROL THROUGH COMMUNICATIONS
PORT. THE FOLLOWING PARAMETERS SHALL ONLY BE ADJUSTABLE VIA DIP
SWITCHES ON THE CONTROLLER
1. NOMINAL LINE VOLTAGE AND FREQUENCY
2. SINGLE OR THREE PHASE SENSING ON NORMAL
3. OPERATING PARAMETER PROTECTION
4. TRANSFER OPERATING MODE CONFIGURATION: (OPEN TRANSITION OR
DELAYED TRANSITION)
ALL INSTRUCTIONS AND CONTROLLER SETTINGS SHALL BE EASILY ACCESSIBLE,
READABLE AND ACCOMPLISHED WITHOUT THE USE OF CODES, CALCULATIONS, OR
INSTRUCTION MANUALS.
2. VOLTAGE,FREQUENCY AND PHASE ROTATION SENSING
A. VOLTAGE AND FREQUENCY ON BOTH THE NORMAL AND EMERGENCY SOURCES (AS
NOTED BELOW) SHALL BE CONTINUOUSLY MONITORED, WITH THE FOLLOWING
PICKUP, DROPOUT AND TRIP SETTING CAPABILITIES (VALUES SHOWN AS % OF
NOMINAL UNLESS OTHERWISE SPECIFIED):
I PARAMETER I SOURCE DROPOUT/ PICKUP 1 RESET
i S - TRIP
- -
UNDERVOLTAGE ! N&E 70 TO 98% 85 TO 100%
Page 45 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
v OVERVOLTAGE_ i N&E _102 TO 115% 2_%BELOW TRIP
UND_ERF_REQUENCY N&E _85 TO 98% 90_TO100%
OVERFREQUENCY 3 N&E 102 TO 110% �2%BELOW TRIP1
B. REPETITIVE ACCURACY OF ALL SETTINGS SHALL BE WITHIN f 1% AT AN OPERATING
TEMPERATURE RANGE OF+250C.
C. VOLTAGE AND FREQUENCY SETTINGS SHALL BE FIELD ADJUSTABLE IN 1%
INCREMENTS EITHER LOCALLY WITH THE DISPLAY AND KEYPAD OR REMOTELY VIA
SERIAL COMMUNICATIONS PORT ACCESS.
D. SOURCE STATUS SCREENS SHALL BE PROVIDED FOR BOTH NORMAL & EMERGENCY
TO PROVIDE DIGITAL READOUT OF VOLTAGE AND FREQUENCY.NOTE: SINGLE PHASE
ON EMERGENCY.
E. THE BACKLIT 128*64 GRAPHICAL DISPLAY SHALL HAVE MULTIPLE LANGUAGE
CAPABILITY.LANGUAGES CAN BE SELECTED FROM THE USER INTERFACE.
3. TIME DELAYS
A. A TIME DELAY SHALL BE PROVIDED TO OVERRIDE MOMENTARY NORMAL SOURCE
OUTAGES AND DELAY ALL TRANSFER AND ENGINE STARTING SIGNALS,ADJUSTABLE
0 TO 6 SECONDS. IT SHALL BE POSSIBLE TO BYPASS THE TIME DELAY FROM THE
CONTROLLER USER INTERFACE.
B. A TIME DELAY SHALL BE PROVIDED ON TRANSFER TO EMERGENCY, ADJUSTABLE
FROM 0 TO 60 MINUTES 59 SECONDS FOR CONTROLLED TIMING OF TRANSFER OF
LOADS TO EMERGENCY. IT SHALL BE POSSIBLE TO BYPASS THE TIME DELAY FROM
THE CONTROLLER USER INTERFACE.
C. A GENERATOR STABILIZATION TIME DELAY SHALL BE PROVIDED AFTER TRANSFER
TO EMERGENCY ADJUSTABLE 0 OR 4 SECONDS.
D. A TIME DELAY SHALL BE PROVIDED ON RETRANSFER TO NORMAL,ADJUSTABLE 0 TO
9 HOURS 59 MINUTES 59 SECONDS. TIME DELAY SHALL BE AUTOMATICALLY
BYPASSED IF EMERGENCY SOURCE FAILS AND NORMAL SOURCE IS ACCEPTABLE.
E. A COOL DOWN TIME DELAY SHALL BE PROVIDED ON SHUTDOWN OF ENGINE
GENERATOR,ADJUSTABLE 0 TO 60 MINUTES 59 SECONDS.
F. ALL ADJUSTABLE TIME DELAYS SHALL BE FIELD ADJUSTABLE WITHOUT THE USE OF
SPECIAL TOOLS.
G. A TIME DELAY ACTIVATED OUTPUT SIGNAL SHALL ALSO BE PROVIDED TO DRIVE AN
EXTERNAL RELAY(S) FOR SELECTIVE LOAD DISCONNECT CONTROL. THE
CONTROLLER SHALL HAVE THE ABILITY TO ACTIVATE AN ADJUSTABLE 0 TO 5
MINUTES 59 SECONDS TIME DELAY IN ANY OF THE FOLLOWING MODES:
1. PRIOR TO TRANSFER ONLY.
2. PRIOR TO AND AFTER TRANSFER.
3. NORMAL TO EMERGENCY ONLY.
4. EMERGENCY TO NORMAL ONLY.
5. NORMAL TO EMERGENCY AND EMERGENCY TO NORMAL.
6. ALL TRANSFER CONDITIONS OR ONLY WHEN BOTH SOURCES ARE AVAILABLE.
H. IN THE EVENT THAT THE ALTERNATE SOURCE IS NOT ACCEPTED WITHIN THE
CONFIGURED FAILURE TO ACCEPT TIME DELAY, THE COMMON ALERT SHALL
BECOME ACTIVE.
I. THE CONTROLLER SHALL ALSO INCLUDE THE FOLLOWING BUILT-IN TIME DELAY FOR
TO DELAYED TRANSITION TRANSFER OPERATION:
1. A TIME DELAY FOR THE LOAD DISCONNECT POSITION FOR DELAYED TRANSITION
Page 46 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
OPERATION ADJUSTABLE 0 TO 5 MINUTES 59 SECONDS IN 1 SECOND INCREMENTS.
4. FEATURES
A. THE USER INTERFACE SHALL BE PROVIDED WITH SOFT KEYS FOR THE TEST/RESET
MODES. THE TEST MODE WILL SIMULATE A NORMAL SOURCE FAILURE. THE RESET
MODE SHALL BYPASS THE TIME DELAYS ON EITHER TRANSFER TO EMERGENCY OR
RETRANSFER TO NORMAL.
B. A SET OF CONTACTS RATED 5 AMPS, 30 VDC SHALL BE PROVIDED FOR A LOW-
VOLTAGE ENGINE START SIGNAL. THE START SIGNAL SHALL PREVENT DRY
CRANKING OF THE ENGINE BY REQUIRING THE GENERATOR SET TO REACH PROPER
OUTPUT, AND RUN FOR THE DURATION OF THE COOL DOWN. SETTING, REGARDLESS
OF WHETHER THE NORMAL SOURCE RESTORES BEFORE THE LOAD IS TRANSFERRED.
C. AUXILIARY CONTACTS, RATED 10 AMPS, 250 VAC SHALL BE PROVIDED CONSISTING
OF ONE CONTACT, CLOSED WHEN THE ATS IS CONNECTED TO THE NORMAL SOURCE
AND ONE CONTACT CLOSED WHEN THE ATS IS CONNECTED TO THE EMERGENCY
SOURCE.
D. A SINGLE ALARM INDICATION SHALL LIGHT UP THE ALERT INDICATOR, AND DE —
ENERGIZE THE CONFIGURED COMMON ALARM OUTPUT RELAY FOR EXTERNAL
MONITORING.
E. LED INDICATING LIGHTS SHALL BE PROVIDED; ONE TO INDICATE WHEN THE ATS IS
CONNECTED TO THE NORMAL SOURCE (GREEN) AND ONE TO INDICATE WHEN THE
ATS IS CONNECTED TO THE EMERGENCY SOURCE(RED).
F. LED INDICATING LIGHTS SHALL BE PROVIDED AND ENERGIZED BY CONTROLLER
OUTPUTS. THE LIGHTS" SHALL PROVIDE TRUE SOURCE AVAILABILITY OF THE
NORMAL (GREEN) AND EMERGENCY (RED) SOURCE, AS DETERMINED BY THE
VOLTAGE SENSING TRIP AND RESET SETTINGS FOR EACH SOURCE.
G. LED INDICATING LIGHT SHALL BE PROVIDED TO INDICATE SWITCH NOT IN
AUTOMATIC MODE (MANUAL); AND BLINKING (AMBER) TO INDICATE TRANSFER
INHIBIT.
H. LED INDICATING LIGHT SHALL BE PROVIDED TO INDICATE ANY ALARM CONDITION
OR ACTIVE TIME DELAY(RED).
I. PROVIDE THE ABILITY TO SELECT "COMMIT/NO COMMIT TO TRANSFER" TO
DETERMINE WHETHER THE LOAD SHOULD BE TRANSFERRED TO THE EMERGENCY
GENERATOR IF THE NORMAL SOURCE RESTORES BEFORE THE GENERATOR IS READY
TO ACCEPT THE LOAD.
J. AN ENGINE GENERATOR EXERCISING TIMER SHALL BE PROVIDED TO CONFIGURE
WEEKLY AND BIWEEKLY AUTOMATIC TESTING OF AN ENGINE GENERATOR SET WITH
OR WITHOUT LOAD •FOR 2 MINUTES FIXED. IT SHALL BE CAPABLE OF BEING
CONFIGURED TO INDICATE A DAY OF THE WEEK, AND TIME WEEKLY TESTING
SHOULD OCCUR.
K. TERMINALS SHALL BE PROVIDED FOR A REMOTE CONTACT TO SIGNAL THE
TRANSFER SWITCH TO TRANSFER TO EMERGENCY AND FOR REMOTE CONTACTS
WHICH OPEN TO INHIBIT TRANSFER TO EMERGENCY THIS INHIBIT SIGNAL CAN BE
ACTIVATED THROUGH THE KEYPAD OR SERIAL PORT.
L. SYSTEM STATUS — THE CONTROLLER LCD DISPLAY SHALL INCLUDE A "SYSTEM
STATUS" SCREEN WHICH SHALL BE READILY ACCESSIBLE FROM ANY POINT IN THE
MENU BY DEPRESSING THE "ESC" KEY A MAXIMUM OF TWO TIMES. THIS SCREEN
SHALL DISPLAY A CLEAR DESCRIPTION OF THE ACTIVE OPERATING SEQUENCE AND
SWITCH POSITION. FOR EXAMPLE,
■ NORMAL FAILED
■ LOAD ON NORMAL
Page 47 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
■ TD NORMAL TO EMERGENCY
■ 2MIN15S
CONTROLLERS THAT REQUIRE MULTIPLE SCREENS TO DETERMINE SYSTEM STATUS
OR DISPLAY "CODED" SYSTEM STATUS MESSAGES, WHICH MUST BE EXPLAINED BY
REFERENCES IN THE OPERATOR'S MANUAL,ARE NOT PERMISSIBLE.
M. SELF DIAGNOSTICS—THE CONTROLLER SHALL CONTAIN A DIAGNOSTIC SCREEN FOR
THE PURPOSE OF DETECTING SYSTEM ERRORS. THIS SCREEN SHALL PROVIDE
INFORMATION ON THE STATUS INPUT SIGNALS TO THE CONTROLLER WHICH MAY BE
PREVENTING LOAD TRANSFER COMMANDS FROM BEING COMPLETED.
N. COMMUNICATIONS INTERFACE — THE CONTROLLER SHALL BE CAPABLE OF
INTERFACING, THROUGH AN OPTIONAL SERIAL COMMUNICATION MODULE, WITH A
NETWORK OF TRANSFER SWITCHES, LOCALLY (UP TO 4000 FT.) OR REMOTELY
THROUGH MODEM SERIAL COMMUNICATIONS. STANDARD SOFTWARE SPECIFIC FOR
TRANSFER SWITCH APPLICATIONS SHALL BE AVAILABLE BY THE TRANSFER SWITCH
MANUFACTURER. THIS SOFTWARE SHALL ALLOW FOR THE MONITORING, CONTROL
AND SETUP OF PARAMETERS.
O. DATA LOGGING —THE CONTROLLER SHALL HAVE THE ABILITY TO LOG DATA AND
TO MAINTAIN THE LAST 300 EVENTS, EVEN IN THE EVENT OF TOTAL POWER LOSS.
THE FOLLOWING EVENTS SHALL BE TIME AND DATE STAMPED AND MAINTAINED IN
A NON-VOLATILE MEMORY:
1. EVENT LOGGING
a. DATA AND TIME AND REASON FOR TRANSFER NORMAL TO EMERGENCY.
b. DATA AND TIME AND REASON FOR TRANSFER EMERGENCY TO NORMAL.
c. DATA AND TIME AND REASON FOR ENGINE START.
d. DATA AND TIME ENGINE STOPPED.
e. DATA AND TIME EMERGENCY SOURCE AVAILABLE.
L DATA AND TIME EMERGENCY SOURCE NOT AVAILABLE.
2. STATISTICAL DATA
a. TOTAL NUMBER OF TRANSFERS.
b. TOTAL NUMBER OF TRANSFERS DUE TO SOURCE FAILURE.
c. TOTAL NUMBER OF DAYS'CONTROLLER IS ENERGIZED.
d. TOTAL NUMBER OF HOURS BOTH NORMAL AND EMERGENCY
SOURCES ARE AVAILABLE.
e. TOTAL TIME LOAD CONNECTED TO NORMAL.
f. TOTAL TIME LOAD CONNECTED TO EMERGENCY.
g. LAST ENGINE START.
h. LAST ENGINE START-UP TIME.
L INPUT AND OUTPUT STATUS.
Page 48 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
ADDITIONAL REQUIREMENTS
1. OPTIONAL FEATURES
A. ACCESSORY PACKAGE — AN ACCESSORY BUNDLE SHALL BE PROVIDED THAT
INCLUDES THE BELOW FEATURES (THIS PACKAGE SHALL BE EQUAL TO ASCO
ACCESSORY 11BE, AND-SHALL BE CAPABLE OF BEING ACTIVATED FOR EXISTING
SWITCHES THROUGH OPTIONAL ACCESSORY DONGLE):
• A FULLY PROGRAMMABLE ENGINE EXERCISER WITH SEVEN INDEPENDENT
ROUTINES TO EXERCISE THE ENGINE GENERATOR,WITH OR WITHOUT LOAD ON A
DAILY WEEKLY,BI—WEEKLY,OR MONTHLY BASIS.
• EVENT LOG DISPLAY THAT SHOWS EVENT NUMBER, TIME AND DATE OF EVENTS,
EVENT TYPE, AND REASON (IF APPLICABLE). A MINIMUM OF 300 EVENTS SHALL
BE STORED.
• RS—485 COMMUNICATIONS PORT ENABLED
• COMMON ALARM OUTPUT CONTACT.
B. CONTROLLER POWER SUPPLY — A BACKUP POWER UPS SHALL BE PROVIDED TO
ALLOW CONTROLLER TO RUN FOR 3 MINUTES MINIMUM WITHOUT AC POWER. (THIS
FEATURE SHALL BE EQUAL TO ASCO ACCESSORY IUP, AND SHALL BE CAPABLE OF
BEING ADDED TO EXISTING SWITCHES WITHOUT MODIFICATION).
C. EXPANSION MODULE — A RELAY EXPANSION MODULE (REX) IS A STANDARD
FEATURE WHEN DELAYED TRANSITION TRANSFER IS SPECIFIED. A REX MODULE
SHALL ALSO BE PROVIDED FOR OPEN TRANSITION TRANSFER THAT INCLUDES ONE
FORM C CONTACT FOR SOURCE AVAILABILITY OF THE NORMAL (18G) AND
EMERGENCY (18B) SOURCES. ADDITIONAL OUTPUT RELAY SHALL BE PROVIDED TO
INDICATE A COMMON ALARM. THE REX MODULE SHALL HAVE THE CAPABILITY OF
BEING DAISY CHAINED FOR MULTIPLE SETS OF CONTACTS. (THIS FEATURE SHALL BE
EQUAL TO ASCO ACCESSORY 18RX, AND SHALL BE CAPABLE OF BEING ADDED TO
EXISTING SWITCHES WITHOUT MODIFICATION).
D. COMMUNICATION INTERFACE — A QUAD-ETHERNET MODULE WITH AES-128 BIT
ENCRYPTION SHALL BE PROVIDED TO ALLOW SEVERAL DIFFERENT SERIAL DEVICES
THAT COMMUNICATE AT DIFFERENT BAUD RATES AND WITH DIFFERENT PROTOCOLS
TO A COMMON ETHERNET MEDIA.THE MODULE SHALL BE USED TO CONNECT SERIES
300 AND ASCO ATS ANNUNCIATORS TO THE STANDARD ETHERNET NETWORK. IT
SHALL INCLUDE (4) RJ — 45S AND I1BE FEATURE BUNDLE. THE MODULE SHALL BE
DESIGNED TO COMMUNICATE WITH MULTIPLE CLIENTS SUCH AS WEB BROWSERS,
AND POWERQUEST® SYSTEMS SIMULTANEOUSLY OVER THE ETHERNET
CONNECTION. (THIS FEATURE SHALL BE EQUAL TO ASCO ACCESSORY 72EE, AND
SHALL BE CAPABLE OF BEING ADDED TO EXISTING SWITCHES WITHOUT
MODIFICATION).
E. TRANSFER ALARM — AN AUDIBLE ALARM WITH SILENCING FEATURE SHALL BE
PROVIDED TO SIGNAL EACH TIME TRANSFER TO EMERGENCY OCCURS. (THIS
FEATURE SHALL BE EQUAL TO ASCO ACCESSORY 62W).
F. POWER METER(THIS FEATURE SHALL BE EQUAL TO ASCO ACCESSORY 135L):
• FURNISH POWER METERS AT LOCATIONS SHOWN TO MONITOR ALL FUNCTIONS
SPECIFIED BELOW.
• THE POWER METERS SHALL BE LISTED TO UL3111-1,CSA,CE MARK, AND
INDUSTRIALLY RATED FOR AN OPERATING TEMPERATURE RANGE OF -20-C TO
60-C.
• THE POWER METER SHALL BE ACCURATE TO 1% MEASURED, 2% COMPUTED
VALUES AND DISPLAY RESOLUTION TO 1%. VOLTAGE AND CURRENT FOR ALL
PHASES SHALL BE SAMPLED SIMULTANEOUSLY TO ASSURE HIGH ACCURACY IN
CONDITIONS OF LOW POWER FACTOR OR LARGE WAVEFORM DISTORTIONS
Page 49 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
(HARMONICS).
• THE POWER METER SHALL BE CAPABLE OF OPERATING WITHOUT MODIFICATION
AT NOMINAL FREQUENCIES OF 45 TO 66HZ AND OVER A CONTROL POWER INPUT
RANGE OF 9—36VDC.
• EACH POWER METER SHALL BE CAPABLE OF INTERFACING WITH AN OPTIONAL
COMMUNICATIONS MODULE TO PERMIT INFORMATION TO BE SENT TO CENTRAL
LOCATION FOR DISPLAY,ANALYSIS,AND LOGGING.
• THE POWER METER SHALL ACCEPT INPUTS FROM INDUSTRY STANDARD
INSTRUMENT TRANSFORMERS (120 VAC SECONDARY PTS AND 5A SECONDARY
CTS). DIRECT PHASE VOLTAGE CONNECTIONS, 600 VAC AND UNDER, SHALL BE
POSSIBLE WITHOUT THE USE OF PTS.
• THE POWER METER SHALL BE APPLIED IN SINGLE, 3 PHASE, OR THREE & FOUR
WIRE CIRCUITS. A FOURTH CT INPUT SHALL BE AVAILABLE TO MEASURE
NEUTRAL OR GROUND CURRENT.
• ALL SETUP PARAMETERS REQUIRED BY THE POWER METER SHALL BE STORED IN
NON—VOLATILE MEMORY AND RETAINED IN THE EVENT OF A CONTROL POWER
INTERRUPTION.
• THE POWER METER SHALL BE EQUIPPED WITH AN OPTIONAL CONTINUOUS DUTY,
LONG LIFE, 4 LINE X,20 CHARACTER LCD BACKLIT DISPLAY TO PROVIDE LOCAL
ACCESS TO THE BELOW METERED QUANTITIES. SAID QUANTITIES SHALL ALSO
HAVE THE CAPABILITY OF BEING COMMUNICATED BY THE POWER METER, VIA
SERIAL COMMUNICATION, WHEN EQUIPPED WITH OPTIONAL SERIAL
COMMUNICATIONS MODULE:
➢ CURRENT,PER PHASE RMS AND NEUTRAL(IF APPLICABLE)
CURRENT UNBALANCE%
VOLTAGE,PHASE—TO—PHASE AND PHASE—TO—NEUTRAL
➢ VOLTAGE UNBALANCE%
REAL POWER(KW),PER PHASE AND 3—PHASE TOTAL
➢ APPARENT POWER(KVA),PER PHASE AND 3—PHASE TOTAL
REACTIVE POWER(KVAR),PER PHASE AND 3—PHASE TOTAL
POWER FACTOR,3—PHASE TOTAL&PER PHASE
➢ FREQUENCY
ACCUMULATED ENERGY, (MWH,MVAH,AND MVARH)
➢ TOTAL HARMONIC DISTORTION
• THE FOLLOWING ENERGY READINGS SHALL BE COMMUNICATED BY THE POWER
METER:
NOTE:FOR REAL REACTIVE ENERGY REPORTED VALUES,SEPARATE TOTAL FOR
ENERGY FLOW FROM EACH SOURCE SHALL BE STORED,INCLUDING THE
ARITHMETIC SUM.
➢ ACCUMULATED REAL ENERGY KWH
ACCUMULATED REACTIVE ENERGY KVAH
ACCUMULATED APPARENT ENERGY KVARH
2. WITHSTAND AND CLOSING RATINGS
A. THE ATS SHALL BE RATED TO CLOSE ON AND WITHSTAND THE AVAILABLE RMS
SYMMETRICAL SHORT CIRCUIT CURRENT AT THE ATS TERMINALS WITH THE TYPE OF
OVERCURRENT PROTECTION SHOWN ON THE PLANS.WCR ATS RATINGS SHALL BE AS
FOLLOWS WHEN USED WITH SPECIFIC CIRCUIT BREAKERS:
Page 50 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
ATS.SIZE(A) WITHSTAND&CLOSING RATING
MC , WITH CLF
1 CB(480VM0HZ)
-__.
_:_....- _...
150-200 42,000A 200,000..__
230 42,000A 100,000
260-400_ 42,000A _ 200,000
600 _ 50,000A 200,000
800-1200_ 65,000A 200,000
1600-2000 85,000A 200,000
2600-3000 100,000A 200,000
3. TESTS AND CERTIFICATION
A. THE COMPLETE ATS SHALL BE FACTORY TESTED TO ENSURE PROPER OPERATION OF
THE INDIVIDUAL COMPONENTS AND CORRECT OVERALL SEQUENCE OF OPERATION
AND TO ENSURE THAT THE OPERATING TRANSFER TIME,VOLTAGE,FREQUENCY AND
TIME DELAY SETTINGS ARE IN COMPLIANCE WITH THE SPECIFICATION
REQUIREMENTS.
B. UPON REQUEST, THE MANUFACTURER SHALL PROVIDE A NOTARIZED LETTER
CERTIFYING COMPLIANCE WITH ALL OF THE REQUIREMENTS OF THIS SPECIFICATION
INCLUDING COMPLIANCE WITH THE ABOVE CODES AND STANDARDS, AND
WITHSTAND AND CLOSING RATINGS. THE CERTIFICATION SHALL IDENTIFY, BY
SERIAL NUMBER(S), THE EQUIPMENT INVOLVED. NO EXCEPTIONS TO THE
SPECIFICATIONS, OTHER THAN THOSE STIPULATED AT THE TIME OF THE SUBMITTAL,
SHALL BE INCLUDED IN THE CERTIFICATION.
C. THE ATS MANUFACTURER SHALL BE CERTIFIED TO ISO 9001:2008 INTERNATIONAL
QUALITY STANDARD AND THE MANUFACTURER SHALL HAVE THIRD PARTY
CERTIFICATION VERIFYING QUALITY ASSURANCE IN DESIGN/DEVELOPMENT,
PRODUCTION,INSTALLATION,AND SERVICING IN ACCORDANCE WITH ISO 9001:2008.
4. SERVICE REPRESENTATION
A. THE ATS MANUFACTURER SHALL MAINTAIN A NATIONAL SERVICE ORGANIZATION
OF COMPANY-EMPLOYED PERSONNEL LOCATED THROUGHOUT THE CONTIGUOUS
UNITED STATES. THE SERVICE CENTER'S PERSONNEL MUST BE FACTORY TRAINED
AND MUST BE ON CALL 24 HOURS A DAY,365 DAYS A YEAR.
B. THE MANUFACTURER SHALL MAINTAIN RECORDS OF EACH SWITCH, BY SERIAL
NUMBER,FOR A MINIMUM OF 20 YEARS.
5.- WARRANTY
A. MANUFACTURER SHALL PROVIDE A 5 YEAR OR GREATER WARRANTY FOR 100%
PARTS & LABOR THAT THE GENERATORS & ATS BE FREE FROM DEFECTS IN
MATERIAL AND WORKMANSHIP AND WILL CONFORM TO MANUFACTURER'S
STANDARD SPECIFICATIONS FOR THE GENERATORS AND ATS.
B. EXTENDED WARRANTY COVERAGE SHALL BE PURCHASED FROM THE
MANUFACTURER AT THE TIME OF ORIGINAL SALE. WARRANTY PERIOD SHALL BE
EXTENDED TO AN ADDITIONAL THIRTY-SIX (36) MONTHS BEYOND THE STANDARD
SIXTY (60) MONTHS SO AS TO PROVIDE EIGHT (8) YEAR COVERAGE FROM THE DATE
OF SHIPMENT APPLICABLE TO THE ABOVE REFERENCED PRODUCT(S).
Page 51 of 52
GENERATOR-EMERGENCY&AUTOMATIC TRANSFER SWITCHES GEATS-061015
VENDOR:THE AWARDED VENDOR IS LISTED BY COLUMN
6. LABOR—ELECTRICIAN—ELECTRICAL MAINTENANCE
A. REPAIR AND SERVICE - ALL BIDDERS MUST HAVE 24HR FACTORY AUTHORIZED
TECHNICIANS TO REPAIR AND SERVICE THE ITEMS THEY HAVE ON CONTRACT AND
MUST STOCK SUFFICIENT REPAIR PARTS/SPECIALTY TOOLS ON TECHNICIANS VANS.
B. ALL BIDDERS MUST HAVE A FACTORY AUTHORIZED TECHNICIAN TO RESPOND TO
EMERGENCY SERVICE CALLS WITHIN 2 HOURS AND NON-EMERGENCY CALL WITHIN
24 HOURS.THE COUNTY SHALL DEFINE WHAT THE STATUS OF THE CALL IS.
C. IF GENERATOR UTILIZES SOFTWARE TO PROGRAM OR REPAIR UNIT, THE VENDOR IS
TO SUPPLY SOFTWARE WITH ANY PASSWORDS REQUIRED. IF SOFTWARE TRAINING IS
REQUIRED,THE VENDER IS TO SUPPLY PRICE FOR ONSITE TRAINING OR SUPPLY COST
OF TRAINING OFFSITE WITH INCLUSIVE PRICE FOR TRAVEL, HOTEL AND FOOD FOR
ENTIRE TRAINING REQUIRED.
Page 52 of 52